Performance rating | COV rate | Token loop time |
---|---|---|
Low | > 500 messages per minute | > 3,000 ms |
Medium | Between 400 and 500 messages per minute | Between 2,000 and 3,000 ms |
High | < 400 messages per minute | < 2,000 ms |