Procedure
-
Select the Navigation Views tab (Figure 1). The available views
appear in the Navigation Views folder.
-
Click the view to assign access permissions. The Roles and Users
Access Permissions tables appear in the right pane.
-
Assign access to Roles in the Roles Access Permissions
table:
-
Click the Allow Access column header to assign
access to all roles. If all roles are already assigned permission,
clicking the column header removes all selections. If one or more roles
are not currently assigned permission to the view, clicking the column
header selects and assigns access to all roles.
-
Click individual rows or cells to assign access to particular roles.
Click to select or remove selections as desired.
-
Assign access to users in the Users Access Permissions
table:
-
Click the Allow Access column header to assign
access to all users. If you have already assigned all users permission,
clicking the column header removes all selections. If you have not
currently assigned one or more users permission to the view, clicking
the column header selects and assigns access to all users.
-
Click individual rows or cells to assign access to particular users.
Click to select or remove selections as desired.
-
In the File menu, click Save. The
circle icon next to the view name in the left pane updates to reflect the
changes (filled = at least one role or user assigned, empty = no roles or users
assigned).
-
Repeat Steps 2 through 5 to assign access to other available user navigation views.