The variable frequency drive (VFD) economizer minimum position reset strategy (VFD Econ Min Pos Reset) adjusts the economizer minimum position proportional to the supply fan speed to maintain the outdoor ventilation rate. When the supply fan is at 0%, the economizer minimum position is set to Economizer Damper Minimum Position Low Speed Fan. As the supply fan increases to 100%, the economizer minimum position decreases to either the user-specified Economizer Minimum Position Setpoint or the DCV reset-adjusted economizer minimum position.