RTU
The RTU adjusts the supply air temperature to meet its discharge cooling setpoint. When the unit is in occupied mode, the supply fan runs continuously. In unoccupied mode, the fan does not run unless a call for cooling occurs.
The RTU adjusts the supply air temperature to meet its discharge cooling setpoint. When the unit is in occupied mode, the supply fan runs continuously. In unoccupied mode, the fan does not run unless a call for cooling occurs.