Procedure
- Remove the top cover of the ZFR1825 Coordinator by simultaneously pushing in both flexible tabs on one side of the unit, followed by pushing in the tabs on the other side of the unit.
- Remove the top portion of the unit.
-
Apply the antenna wire firmly to the connection point (see Figure 1) until it locks into
place.
Important: The connection from the antenna cable to the ZFR1825 Coordinator is intended to be made only once. Do not remove it once you have inserted it into the jack. If you must remove the antenna, only pull on the knurled end of the antenna's connector. Pulling on the antenna cable from anywhere else can result in damage to the antenna. Avoid any repeat removals and re-insertions as this may impact wireless connection integrity and unit performance.
- Replace the top portion and cover of the ZFR1825 Coordinator.