If a V43/V243 Pressure-Actuated Water-Regulating Valve fails to operate within its specifications, replacement sensing elements, internal parts, and diaphragms are available for valve repair. See Servicing for servicing instructions.
To obtain replacement parts kit instructions and details, contact your nearest Johnson Controls® distributor. For replacement parts kit product code numbers, see Table 1 and Table 2.
Model1 | Diaphragm kit | Seat disc and diaphragm kit | Seat repair kit | Screen repair kit | Push rod kit2 | Sensing element kit | Disc body kit |
---|---|---|---|---|---|---|---|
V43AS-1C | DPM18A-600R | DSC16A-600R | STT19A-602R | SCN10A-600R | ROD18A-600R | SEP88A-600R | DBK11A-600R |
V43AS-2C | DPM18A-600R | DSC16A-600R | STT19A-602R | SCN10A-600R | ROD18A-600R | SEP88A-601R | DBK11A-600R |
V43AS-5C | DPM18A-600R | DSC16A-600R | STT19A-602R | SCN10A-600R | ROD18A-600R | SEP87A-600R | DBK11A-600R |
V43AT-1C | DPM18A-601R | DSC16A-601R | STT19A-603R | SCN10A-600R | ROD18A-601R | SEP88A-600R | DBK11A-601R |
V43AT-2C | DPM18A-601R | DSC16A-601R | STT19A-603R | SCN10A-600R | ROD18A-601R | SEP88A-601R | DBK11A-601R |
V43AT-5C | DPM18A-601R | DSC16A-601R | STT19A-603R | SCN10A-600R | ROD18A-601R | SEP87A-600R | DBK11A-601R |
V43AV-1C | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-600R | ROD18A-601R | SEP88A-600R | DBK11A-602R |
V43AV-2C | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-600R | ROD18A-601R | SEP88A-601R | DBK11A-602R |
V43AV-5C | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-600R | ROD18A-601R | SEP87A-600R | DBK11A-602R |
V43AW-1C | DPM18A-603R | DSC16A-603R | STT19A-608R | SCN10A-600R | ROD18A-602R | SEP88A-600R | DBK11A-603R |
V43AW-2C | DPM18A-603R | DSC16A-603R | STT19A-608R | SCN10A-600R | ROD18A-602R | SEP88A-601R | DBK11A-603R |
V43AW-5C | DPM18A-603R | DSC16A-603R | STT19A-608R | SCN10A-600R | ROD18A-602R | SEP87A-600R | DBK11A-603R |
V43BS-1C1 | DPM18A-600R | DSC16A-600R | STT19A-602R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK11A-600R |
V43BS-2C1 | DPM18A-600R | DSC16A-600R | STT19A-602R | SCN10A-601R | ROD18A-602R | SEP88A-601R | DBK11A-600R |
V43BS-3C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-600R |
V43BS-6C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-600R |
V43BS-7C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-602R | SEP88A-601R | DBK10A-600R |
V43BT-1C1 | DPM18A-601R | DSC16A-601R | STT19A-603R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK11A-601R |
V43BT-2C1 | DPM18A-601R | DSC16A-601R | STT19A-603R | SCN10A-601R | ROD18A-603R | SEP88A-601R | DBK11A-601R |
V43BT-3C | DPM18A-601R | DSC16A-601R | STT19A-605R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-602R |
V43BT-6C | DPM18A-601R | DSC16A-601R | STT19A-605R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-602R |
V43BT-7C | DPM18A-601R | DSC16A-601R | STT19A-605R | SCN10A-601R | ROD18A-603R | SEP88A-601R | DBK10A-602R |
V43BV-1C1 | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK11A-602R |
V43BV-2C1 | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-601R | ROD18A-603R | SEP88A-601R | DBK11A-602R |
V43BV-4C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-601R |
V43BV-5C1 | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK11A-602R |
V43BV-6C1 | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-601R | ROD18A-603R | SEP88A-601R | DBK11A-602R |
V43BV-7C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP88A-601R | DBK10A-601R |
V43BV-8C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-601R |
V43BV-9C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP88A-601R | DBK10A-601R |
V43BV-10C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-601R |
V43BW-1C | DPM18A-603R | DSC16A-603R | STT19A-609R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-603R |
V43BW-2C | DPM18A-603R | DSC16A-603R | STT19A-609R | SCN10A-601R | ROD18A-602R | SEP88A-601R | DBK10A-603R |
V43BW-5C | DPM18A-603R | DSC16A-603R | STT19A-609R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-603R |
V43BW-6C | DPM18A-603R | DSC16A-603R | STT19A-609R | SCN10A-601R | ROD18A-602R | SEP88A-601R | DBK10A-603R |
V43BW-7C | DPM18A-603R | DSC16A-603R | STT19A-609R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-603R |
V43CS-1C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-600R |
V43CS-2C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-602R | SEP88A-600R | DBK10A-600R |
V43CS-3C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-604R | SEP88A-600R | DBK10A-600R |
V43CT-1C | DPM18A-601R | DSC16A-601R | STT19A-605R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-602R |
V43CT-2C | DPM18A-601R | DSC16A-601R | STT19A-605R | SCN10A-601R | ROD18A-603R | SEP86A-600R | DBK10A-602R |
V43CV-1C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP86A-600R | DBK10A-601R |
V43CV-2C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP88A-600R | DBK10A-601R |
V243GS-1C | DPM18A-600R | DSC16A-600R | STT19A-602R | SCN10A-600R | ROD18A-600R | SEP90A-600R | DBK11A-600R |
V243GT-1C | DPM18A-601R | DSC16A-601R | STT19A-603R | SCN10A-600R | ROD18A-601R | SEP90A-600R | DBK11A-601R |
V243GV-1C | DPM18A-602R | DSC16A-602R | STT19A-606R | SCN10A-600R | ROD18A-601R | SEP90A-600R | DBK11A-602R |
V243GW-1C | DPM18A-603R | DSC16A-603R | STT19A-608R | SCN10A-600R | ROD18A-600R | SEP90A-600R | DBK11A-603R |
V243HS-1C | DPM18A-600R | DSC16A-600R | STT19A-600R | SCN10A-601R | ROD18A-602R | SEP90A-600R | DBK10A-600R |
V243HT-1C | DPM18A-601R | DSC16A-601R | STT19A-605R | SCN10A-601R | ROD18A-603R | SEP90A-600R | DBK10A-601R |
V243HV-1C | DPM18A-602R | DSC16A-602R | STT19A-607R | SCN10A-601R | ROD18A-603R | SEP90A-600R | DBK10A-602R |
V243HW-1C | DPM18A-603R | DSC16A-603R | STT19A-609R | SCN10A-601R | ROD18A-602R | SEP90A-600R | DPK10A-603R |
The following valves, manufactured after date code 8702, contain MONEL interior trim. To order replacement kits, see Table 1 or refer to V43xx and V243xx Series Repair Parts Kits Technical Bulletin (LIT-121690).
Valve model | Order parts kits for: |
---|---|
V43BS-1C | V43BS-6C |
V43BS-2C | V43BS-7C |
V43BT-1C | V43BT-6C |
V43BT-2C | V43BT-7C |
V43BV-1C | V43BV-10C |
V43BV-2C | V43BV-7C |
V43BV-5C | V43BV-10C |
V43BV-6C | V43BV-9C |
1 Repair parts are supplied in kits only and include
all parts that you need to recondition that portion of the valve. To
order, specify the code number only.
2 Replacement push rod kit requires a seat repair kit or a diaphragm
kit when you replace it.