Air temp °F |
Altitude, ft |
||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
|
0* |
1,000 |
2,000 |
3,000 |
4,000 |
5,000 |
6,000 |
7,000 |
8,000 |
9,000 |
10,000 |
|
|
40 |
1.060 |
1.022 |
0.986 |
0.95 |
0.916 |
0.822 |
0.849 |
0.818 |
0.788 |
0.758 |
0.729 |
|
50 |
1.039 |
1.002 |
0.966 |
0.931 |
0.898 |
0.864 |
0.832 |
0.802 |
0.772 |
0.743 |
0.715 |
|
60 |
1.019 |
0.982 |
0.948 |
0.913 |
0.880 |
0.848 |
0.816 |
0.787 |
0.757 |
0.729 |
0.701 |
|
70 |
1.000 |
0.964 |
0.930 |
0.896 |
0.864 |
0.832 |
0.801 |
0.772 |
0.743 |
0.715 |
0.688 |
|
80 |
0.982 |
0.947 |
0.913 |
0.88 |
0.848 |
0.817 |
0.787 |
0.758 |
0.73 |
0.702 |
0.676 |
|
90 |
0.964 |
0.929 |
0.897 |
0.864 |
0.833 |
0.802 |
0.772 |
0.744 |
0.716 |
0.689 |
0.663 |
|
100 |
0.946 |
0.912 |
0.880 |
0.848 |
0.817 |
0.787 |
0.758 |
0.730 |
0.703 |
0.676 |
0.651 |
The information below must be used to assist in application of product when applied at altitudes equal to or above 1000 ft above sea level.
The following examples assist in determining the airflow performance of Sun Premier units at specific altitudes.
Example 1: What are the corrected cubic ft per minute (CFM), static pressure, and brake horse power (BHP) at an elevation of 5,000 ft if the airflow performance data is 19,000 CFM, 1.4 in. of water gauge (iwg), and 15.0 BHP?
Solution: At an elevation of 5,000 ft, the supply fan still delivers 19,000 CFM if the revolutions per minute (RPM) is unchanged. However, the altitude correction must be used to determine the static pressure and BHP. Since no temperature data is given, we assume an air temperature of 70.0°F. Table 1 shows the correction factor to be 0.832.
Corrected static pressure = 1.4 x 0.832 = 1.16 iwg
Corrected BHP = 15.0 x 0.832 = 12.48
Example 2: A system, located at 5,000 ft of elevation is to deliver 19,000 CFM at a static pressure of 1.4 iwg. Use the unit blower tables to select the RPM, blower speed, and the BHP requirement.
Solution: As in the example above, no temperature information is given, so 70.0°F is assumed.
The 1.4 iwg static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.
Sea level static pressure = 1.4 iwg / 0.832 = 1.68 iwg
Enter Table 5 at 19,000 CFM and static pressure of 1.68 iwg. The RPM listed is the same RPM needed at 5,000 ft.
Using interpolation, the corresponding BHP listed in the table is 10.8. This value must be corrected for elevation.
BHP at 5,000 ft = 10.8 x 0.832 = 8.98
Example 3: Plot fan performance using Table 5.
Plot the fan performance at cooling sea level (0 ft) elevation. Design conditions are a 60 ton unit producing 20,000 CFM at 2.0 external static pressure (ESP) with additional static losses for a wet evaporator coil, bottom return air, bottom supply air, and angled filter rack with 2 in. MERV 8 filters. Refer to Table 1 onwards for component static pressure drops (iwg)
Wet evaporator coil standard capacity additional static loss = 0.62 iwg
Bottom return air additional static loss = 0.10 iwg
Bottom supply air additional static loss = 0.11 iwg
Air filter additional static loss = 0.13 iwg
Add the ESP and all additional losses (internal static loss):
ESP loss = 2.0 iwg
Total internal static loss = 0.96 iwg
Total system static = 2.96 iwg