You can find the objects and parameters for the different Verasys System controllers in the following tables and documents:
  • SSE RTU controller: Table 1
  • VZC100: Table 2
  • BYP200: Table 3
  • ZEC510: Table 4
  • ZEC310: Table 5
  • TEC363x: Table 6
  • Generic IOM LC-VAC1002-0: Table 7
  • Lighting controller LC-VAC1001-0: Table 8
  • VEC100: refer to the application note for the application that you use.
    • VEC100 Generic RTU Controller, Modulated Heating and Modulated Cooling Application Note (LIT-12013484)
    • VEC100 Generic RTU Controller, Modulated Heating and Staged Cooling Application Note (LIT-12013361)
    • VEC100 Generic RTU Controller, Staged Heating and Modulated Cooling Application Note (LIT-12013485)
    • VEC100 Generic RTU Controller, Staged Heating and Staged Cooling Application Note (LIT-12013443)
    • VEC100 Generic RTU Heat Pump Controller Application Note (LIT-12013452)
Table 1. SSE RTU controller
Menu Object or Parameter Description Adjustable
Status: Thermostat Y1 - Thermostat First stage cooling thermostat call Read Only
Y2 - Thermostat Second stage cooling thermostat call Read Only
Y3 - Thermostat Third stage cooling thermostat call Read Only
Y4 - Thermostat Fourth stage cooling thermostat call Read Only
W1 - Thermostat First stage heating thermostat call Read Only
W2 - Thermostat Second stage heating thermostat call Read Only
W3 - Thermostat Third stage heating thermostat call Read Only
G - Thermostat Binary fan thermostat call Read Only
Local Occupancy Input - Thermostat Local occupancy mode of the unit Read Only
Status: Smoke Control Operating Purge Command Displays if unit is purged or not Read Only
Purge Command Source Command source of purge command Read Only
Local Purge Command Input Economizer Purge command input Read Only
Network Override Purge Command Network Override purge command Adjustable: False/True
Shutdown Input/Smoke Detector Smoke detector input; a closed contact equates an alarm condition Read Only
Status: Status Unit Status The current status or state of the unit Read Only
Economizer Status The Economizer operational status Read Only
Exhaust Fan Status The Exhaust Fan operational status Read Only
Fan Status The current status of the fan Read Only
Hot Gas Reheat Status The Hot Gas Reheat operational status Read Only
Cooling Status The Cooling Control operational status Read Only
Dirty Filter Switch The switch that suggests that the filter is dirty Read Only
UCB 24VAC Input Analog input stating the current status of VAC supply Read Only
Status: Control Econ Controller The current connection status of the economizer board. Not present means that the board has not been installed. Offline means that the board is installed but not online. Online means that the board is installed and online. Read Only
4 Stage Controller This input is the current communication status of the four stage add-on board. Read Only
FDD Master Controller This input is the current communication status of the FDD1 add-on board. Read Only
FDD Subordinate Controller This input is the current communication status of the FDD2 add-on board. Read Only
Summary: Sensors: Operational Mode Operational Outdoor Air Temperature Analog input of the current operational outdoor air temperature Read Only
Operational Space Temperature Analog input of the current operational space temperature Read Only
Operational Space Temperature Setpoint Offset Analog input of current space temperature setpoint offset Read Only
Operational Space Humidity Analog input of the current operational space humidity Read Only
Operational Outdoor Air Humidity Analog input of the current operational outdoor humidity Read Only
Operational Indoor Air Quality Analog input of the current operational indoor humidity Read Only
Operational Outdoor Air Quality Analog input of the current operational outdoor humidity Read Only
Operating Purge Command Indicates if unit is purged or not Read Only
Summary: Sensors: Sensors Supply Air Temperature The present value of the supply air temperature analog input. Read Only
Return Air Temperature The present value of the Return Air Temperature analog input Read Only
Outdoor Air Temperature Input The present value of the Outdoor Air Temperature analog input Read Only
Outdoor Air Temperature Source The source of the Outdoor Air Temperature analog input Read Only
Space Temperature Input The present value of the Space Temperature Input Read Only
Space Temperature Source The source of the Space Temperature Input Read Only
Space Temperature Alarm Setpoint Offset The present value of the Space Temperature Alarm Setpoint Offset set by the user Adjustable: 0 to 25°F
Space Temperature Alarm Time Delay The present value of the Space Temperature Alarm Time Delay set by the user Adjustable: 0 to 120 minutes
Space Temp Setpoint Offset Input The present value of the Space Temp Setpoint Offset Input Read Only
Space Temperature Setpoint Offset Source The source of the Space Temperature Setpoint Offset input Read Only
Space Temperature Setpoint Offset Range The Space Temperature Setpoint Offset range set by the user Adjustable: 0 to 5 delta °F
Space Humidity RAH Input The present value of the Space Humidity RAH Input Read Only
Space Humidity Source The source of the Space Humidity input Read Only
Outdoor Air Humidity Input The present value of the Outdoor Air Humidity Input Read Only
Outdoor Air Humidity Source The source of the Outdoor Air Humidity input Read Only
Indoor Air Quality The present value of the Indoor Air Quality Read Only
Indoor Air Quality Source The source of the Indoor Air Quality input Read Only
Outdoor Air Quality Input The present value of the Outdoor Air Quality Input Read Only
Outdoor Air Quality Source The source of the Outdoor Air Quality input Read Only
Purge Command Source The source of the Purge Command input Read Only
Supply Air Humidity The present value of the Supply Air Humidity Read Only
Mixed Air Temperature The present value of the Mixed Air Temperature Read Only
Building Static Pressure The present value of the Building Static Pressure Read Only
Duct Static Pressure The present value of the Duct Static Pressure Read Only
Summary: Unit Unit Name The name of the Unit Adjustable
Unit Model Number Indicates the firmware version of the controller Adjustable
Unit Serial Number Indicates the serial number of the controller Adjustable
Model Name Indicates the model name of the controller Read Only
Unit Status Indicates in current status of the controller Read Only
Unit Enable Indicates if the unit is enabled by the user Adjustable: Shutdown/Enable
Hardware Reset Indicates if the hardware is being reset by the user Adjustable: No/Yes
Reset Lockouts Indicates if any reset lockouts are present Adjustable: Off/On
Commissioning: Quick Start Number of Cooling Stages Installed Sets the number of Cooling Stages installed Adjustable: 1 to 4
Number of Heating Stages Installed Sets the number of Heating Stages installed Adjustable: 0 to 3
Number of Heat Pump Stages Installed Sets the number of Heat Pump Stages installed Adjustable: 0 to 2
Number of Refrig Systems Installed Sets the number of Refrig Systems installed Adjustable: 0 to 4
Fan Control Type Sets the Fan Control Type Adjustable: SE RTU Fan Control Type
Thermostat Only Control Enabled Sets the control to Thermostat Only mode Adjustable: No/Yes
Continuous Fan Operation in Occupied Mode Sets the control for Continuous Fan during Occupied Adjustable: No/Yes
Economizer Minimum Position Setpoint Sets the Economizer Minimum Position Adjustable: 0 to 100
Supply Air Temperature The current Supply Air Temperature Read Only
Return Air Temperature The current Return Air Temperature Read Only
Outdoor Air Temperature Input The current Outdoor Air Temperature (Input) Read Only
Cooling Status The current Cooling Control Status Read Only
Heating Status The current Heating Control Status Read Only
Cooling Mode Enabled For Operation Allows Cooling Mode to be enabled for operation Adjustable: No/Yes
Heating Mode Enabled For Operation Allows Heating Mode to be enabled for operation Adjustable: No/Yes
Unique Equipment Identifier Sets the current Equipment configuration specific to the unit Adjustable: SE RTU Equipment Configuration
Commissioning: Standard Occupancy Mode Sets the Occupancy Mode of the controller Adjustable: SE Occupancy Mode
Thermostat Only Control Enabled Sets the control to Thermostat Only mode Adjustable: No/Yes
Cooling Mode Enabled For Operation Allows Cooling Mode to be enabled for operation Adjustable: No/Yes
Number of Cooling Stages Installed Sets the number of Cooling Stages installed Adjustable: 1 to 4
Heating Mode Enabled For Operation Allows Heating Mode to be enabled for operation Adjustable: No/Yes
Number of Heating Stages Installed Sets the number of Heating Stages installed Adjustable: 0 to 3
Economizer Enabled For Operation Determines if an Economizer is enabled for operation Adjustable: No/Yes
Economizer Minimum Position Setpoint Determines the Economizer minimum position Adjustable: 0 to 100%
Economizer Damper Minimum Position Low Speed Fan Determines the Economizer min position on low fan speed Adjustable: 0 to 100%
Continuous Fan Operation in Occupied Mode Sets the control for Continuous Fan during Occupied Adjustable: Yes/No
SAT Limit for Cooling Enable Allows option for SAT limit for cooling enable Adjustable: No/Yes
SAT Limit for Cooling Setpoint Sets the SAT Limit for Cooling Adjustable: 40 to 65°F
OAT Cooling Cutout Enabled Allows optional for Cooling Cutout to be enabled Adjustable: No/Yes
OAT Cooling Cutout Sets the Cooling Cutout Temperature Adjustable: 0 to 100°F
Commissioning: Options Fan Control Type Sets the Fan Control Type Adjustable: SE RTU Fan Control Type
Exhaust Type Sets the Exhaust Setup Adjustable: SE RTU Exhaust Setup
Number of Refrig Systems Installed Sets the number of Refrig Systems installed Adjustable: 0 to 4
Low Ambient Enabled Allows Low Ambient to be enabled/disabled Adjustable: No/Yes
Lead/Lag Equalize Cooling Stage Runtime Enabled Sets if Lead/Lag functionality should be used for Compressor runtimes Adjustable: No/Yes
Hot Gas Bypass Present Determines if Hot Gad Bypass is present in the system Adjustable: No/Yes
Heating Mode Enabled For Operation Allows Heating Mode to be enabled for operation Adjustable: No/Yes
Heating Control Type Sets the Heating Control Type Adjustable: Heat Cool Type
SAT Air Temp Limit for Heating Enabled Allows option for SAT Air Temp Limit for Heating Adjustable: No/Yes
SAT Air Temp Limit For Heating Setpoint Sets the SAT Air Temp Limit for Heating Adjustable: 100 to 180°F
Outdoor Air Temp Heating Cutout Setpoint Sets the OAT Heating Cutout Setpoint Adjustable: 0 to 100°F
Air Proving Switch Setup Sets the Air Proving Switch Setpoint Adjustable: Fan Setup
Dirty Filter Switch Installed Determines if Dirty Filter Switch is installed Adjustable: No/Yes
Demand Ventilation Mode of Operation Sets the Demand Ventilation Mode of Operation for the system Adjustable: SE RTU DCV Mode
Hot Gas Reheat Enabled For Operation Determines in Hot Gas Reheat is enabled Adjustable: No/Yes
Morning Warmup Enabled Determines if Morning Warmup is enabled Adjustable: No/Yes
Number of Heat Pump Stages Installed Sets the number of Heat Pump Stages installed Adjustable: 0 to 2
Low Ambient Fan Pre-run Time For Cooling Sets the Low Ambient Fan Pre-Run Time for Cooling Adjustable: 0 s to 255 s
PID Tuning Reset Determines if the PID should be reset or not Adjustable: False/True
Low Ambient Start Determines if Low Ambient should be set on start Adjustable: No/Yes
SZ VAV Enabled Determines if SZ VAV is enabled Adjustable: Off/On
Network Occupancy Timeout Enable Determines if Network Occupancy Timeout is enabled Adjustable: Disable/Enable
Network Occupancy Timeout Time Sets the Network Occupancy Timeout Time Adjustable: 5 to 60 minutes
Pressurize Instead of Purge Sets the option to Pressurize instead of purging the system Adjustable: No/Yes
Cooling Allowed During Heat Limit Sets the option to Cool during Heat limit operation Adjustable: No/Yes
FDD Alarm Enable Determines if FDD Alarm is Enabled Adjustable: Disable/Enable
Econ Sensor Fault Indications Sets the Econ Sensor Fault Indications are present Adjustable- Disable/Enable
Commissioning: Network Setup FC Comm Mode Set to wired field bus Read Only
Address The address of the controller. This address is Adjustable via the smart building hub and the display on the controller. Adjustable: 4 to 127
Device OID The BACnet Device Object Identifier for the system bus. If on a standalone Verasys System this parameter is not used, but if connected to a 3rd party facility management system it sets the BACnet ID for the zone coordinator. Adjustable: 0 to 4,194,302
Baud Rate The ability to set the baud rate. When set to auto the zone coordinator will set the baud rate for the controller. Adjustable: MSTPDL Baud Rate
Device Name The name of the device. This name shows up on the device list. Adjustable
BACnet Encoding Type The encoding type set the character set that the controller uses. Adjustable: Legacy BACnet Encoding Type
Commissioning: Commissioning Mode Commissioning Mode Sets the controller into Commissioning Mode Adjustable: Disable/Enable
Commissioning Time Remaining The time remaining until Commissioning Mode ends Read Only
Extend Commissioning Time Allows the user to extend Commissioning Mode Adjustable: Disable/Enable
Unit Enable Sets the Unit to Shutdown/Enable Adjustable: Shutdown/Enable
Supply Fan Command Sets the Fan to Off/On Adjustable: Off/On
Fan % Command Adjusts Fan Speed to 0 to 100% Adjustable: 0 to 100
Compressor Stage Command 1 Turns On/Off Compressor Stage 1 Adjustable: Off/On
Compressor Stage Command 2 Turns On/Off Compressor Stage 2 Adjustable: Off/On
Compressor Stage Command 3 Turns On/Off Compressor Stage 3 Adjustable: Off/On
Compressor Stage Command 4 Turns On/Off Compressor Stage 4 Adjustable: Off/On
Condenser Fan 1 Turns On/Off Condenser Fan 1 Adjustable: Off/On
Condenser Fan 2 Turns On/Off Condenser Fan 2 Adjustable: Off/On
Heating Stage Command 1 Turns On/Off Heating Stage 1 Adjustable: Off/On
Heating Stage Command 2 Turns On/Off Heating Stage 2 Adjustable: Off/On
Heating Stage Command 3 Turns On/Off Heating Stage 3 Adjustable: Off/On
Hot Gas Reheat (Binary) Enables Hot Gas Reheat Adjustable: Off/On
Hot Gas Reheat (Analog) Sets the Hot Gas Reheat percentage 0 to 100% Adjustable: 0 to 100
Hot Gas Reheat Bleed Valve Command Sets the Hot Gas Reheat Bleed Valve Open/Close Adjustable: Close/Open
Economizer Damper % Command Adjusts the Economizer Damper % Command Adjustable: 0 to 100
Exhaust Fan VFD % Command Adjusts The Exhaust Fan VFD % Command Adjustable: 0 to 100
Exhaust Fan Command Sets the Exhaust Fan Command Off/On Adjustable: Off/On
Exhaust Damper % Adjusts the Exhaust Damper % Adjustable: 0 to 100
Cancel ASCD Timers Clears any ASCD Timers to test the controller in a more time efficient manner Adjustable: No/Yes
Controller: Network Device Name The name of the device. This name shows up on the device list. Adjustable
Address The address of the controller. This address is Adjustable via the smart building hub and the display on the controller. Adjustable: 4 to 127
Time Zone The time zone the controller is using Adjustable: SE RTU Time Zone
Description The description of the device. This description shows up on the device list. Adjustable
Communication Status The status of the zone bus communication. Read Only
FC Comm Mode Set to wired field bus Read Only
Operating Baud Rate Shows the baud rate the controller is talking. Read Only
Baud Rate The ability to set the baud rate. When set to auto the zone coordinator will set the baud rate for the controller. Adjustable: MSTPDL Baud Rate
Device OID The BACnet Device Object Identifier for the system bus. If on a standalone Verasys System this parameter is not used, but if connected to a 3rd party facility management system it sets the BACnet ID for the zone coordinator. Adjustable: 0 to 4,194,302
Language Sets the language the controller uses Adjustable: SE RTU Languages
Units Sets the units the controller uses Adjustable: Unit Set
Number of Network Sensors Online Indicates how many Network sensors are online Read Only
Relearn System Relearns the sensors connected to the controller Adjustable: Relearn
BACnet Encoding Type The encoding type set the character set that the controller uses. Adjustable: Legacy BACnet Encoding Type
Radio Code Version This is the current radio code version Read Only
Active Channel This is the active channel Read Only
Signal Strength This is the signal strength of the connectivity Read Only
Connection Status This is the status of the connection Read Only
Network State This is the state of the network Read Only
Short Address This is the short address for the control Read Only
Baud Rate The ability to set the baud rate. When set to auto the zone coordinator will set the baud rate for the controller. Adjustable: Baud Rate
Parity A parity bit, or check bit, is a bit added to a string of binary code to ensure that the total number of 1-bits in the string is even or odd. Parity bits are used as the simplest form of error detecting code. Adjustable: Pager Parity
Stop Bits The stop bit is used to signal the end of a frame. The data is contained in the data bits and the parity bit is an extra bit that is often used to detect transmission errors Adjustable: Stop bits
Controller: Firmware: UCB Firmware Status Indicates the status of the Firmware Read Only
Firmware Version Indicates the firmware version of the controller. Read Only
Firmware Main Version Indicates what firmware is in the controller Read Only
Application Version Indicates the version of the application. Read Only
Hardware Version Indicates the hardware version of the controller Read Only
Controller: Firmware: Econ Firmware Main Version Indicates what firmware is in the controller Read Only
Application Version Indicates the version of the application. Read Only
Hardware Version Indicates the hardware version of the controller Read Only
Controller: Firmware: 4 Stage Firmware Main Version Indicates what firmware is in the controller Read Only
Application Version Indicates the version of the application. Read Only
Hardware Version Indicates the hardware version of the controller Read Only
Controller: Firmware: FDD Master Firmware Main Version Indicates what firmware is in the controller Read Only
Application Version Indicates the version of the application. Read Only
Hardware Version Indicates the hardware version of the controller Read Only
Controller: Firmware: FDD Subordinate Firmware Main Version Indicates what firmware is in the controller Read Only
Application Version Indicates the version of the application. Read Only
Hardware Version Indicates the hardware version of the controller Read Only
Controller: Network Inputs Network Override Space Temperature Overrides the Space Temperature per user request Adjustable: 0 to 100°F
Network Override Space Setpoint Offset Overrides the Space Temperature Setpoint Offset per user request Adjustable: -5 to 5 delta °F
Network Override Zone Humidity Overrides the Zone Humidity per user request Adjustable: 0 to 100% RH
Network Occupancy Request Overrides the Occupancy Request per user request Adjustable: Occ Sensor
Network Temporary Occupancy Request Overrides the Temporary Occupancy Request per user request Adjustable: False/True
Network Override Indoor Air Quality Overrides the Indoor Air Quality per user request Adjustable: 0 to 5,000 ppm
Network Override Fan Request Overrides the Fan Request per user Request Adjustable: Off/On
Network Override Outdoor Air Temperature Overrides the Outdoor Air Temperature per user request Adjustable: -50 to 125°F
Network Override Outdoor Air Humidity Overrides the Outdoor Air Humidity per user request Adjustable: 0 to 100% RH
Network Override Outdoor Air Quality Overrides the Outdoor Air Quality per user request Adjustable: 0 to 5,000 ppm
Network Override Purge Command Overrides the Purge Command per user request Adjustable: False/True
Direct Loadshed Overrides the Direct Loadshed per user request Adjustable: No/Yes
Redline Overrides the Redline per user request Adjustable: No/Yes
Controller: FDD Unit Type Selects the SE RTU equipment type for the FDD board. Adjustable: SE RTU Equipment Type
EER Selects the energy efficient ration based on the system configuration Adjustable: 0 to 20
Subcooling Goal Selects the subcooling temperature decrease Adjustable: -10 to 20°F
Refrigerant Type Selects which refrigerant is being used in the system Adjustable: SE RTU Refrigerant Type
High Side Port Location Selects where the High Side port is located Adjustable: SE RTU High Side Port
Evaporator Coil Type Selects which types of evaporator coil is being used Adjustable: Cooling Coil Type
Condenser Coil Type Selects which type of condenser coil is being used Adjustable: Cooling Coil Type
Indoor Metering Device Type Selects which Indoor metering device is sensing the expansion valve Adjustable: SE RTU Expansion Device
Outdoor Metering Device Type Select which Outdoor metering device is sensing the expansion valve Adjustable: SE RTU Expansion Device
Unit Capacity Selects the Unit capacity based on the equipment configuration Adjustable: 0 to 130 tons
Fan Power Selects the Fan power based on the equipment configuration Adjustable: 0 to 19 kW
Super Heat Goal Selects the super heat temperature increase Adjustable: 10 to 30°F
Altitude Selects the altitude in which the system is installed Adjustable: -1,500 to 30,000 ft
Controller: Time Time The time setting that the controller is using Read Only
Date The date that the controller is using Read Only
Time Zone The time zone that the controller is using Adjustable: SE RTU Time Zone
Daylight Savings Enable Enable or disables daylight savings time Adjustable: No/Yes
Time Format This controls which format the time should be displayed Adjustable: States
Controller: Description Rooftop Controller Type Indicates which type the Rooftop Controller is Adjustable: LCCS Controller Type
Rooftop Equipment Type Indicates which equipment configuration the system is using Adjustable: LCCS Equipment Type
Details: Occupancy Status Occupancy Mode Sets the Occupancy Mode that the controller will use Adjustable: SE Occupancy Mode
Occupancy Input Indicates if the controller is occupied or unoccupied Read Only
Operational Occupancy This output shows the current value of the Effective Occupancy. This allows the Setpoint Determination module to switch to the Standby mode setpoints. Read Only
Occupancy Input Source Indicates the input source in which the controller is reading from Read Only
Temporary Occupancy Input Allows the Temp Occ feature to be disabled. This only applies to a SE RTU that is not connected to a Verasys system. Some building owners do not want this feature. Adjustable: Disable/Enable
Temporary Occupancy Timeout The amount of time(secs) that the module will be in the Temp Occ (Bypass) mode. Adjustable: 30 to 480 minutes
Off During Unoccupied Enables and disables heating and cooling during unoccupied. Adjustable: No/Yes
Optimal Start Enabled Boolean input provides an indication that this module will use the information from the Optimal Start block as it determines the current Warm-Up or Cool-Down mode. Adjustable: No/Yes
Early Start Period This is the early start period that is used when Occupancy BI Enable is true. It is also used to determine when to start if Optimal Start Enable is false. Adjustable: 0 to 120 minutes
Pre Occupancy Purge Enable Control input to determine if the Differential CO2 mode is used. Adjustable: Disable/Enable
Pre Occupancy Purge Time This value is the amount of time (in minutes) prior to the system switching to occupied mode that the pre-occupancy purge sequence will run. Adjustable: 1 to 120 minutes
Pre Occupancy Purge Upper SAT Setpoint This is the maximum value of the supply air temperature that the system will allow. Adjustable: 80 to 100°F
Pre Occupancy Purge Lower SAT Setpoint This is the minimum value of the supply air temperature that the system will allow. Adjustable: 35°F to 55°F
Details: Cooling: Setup Cooling Mode Enabled For Operation This allows cooling mode to be enabled or disabled. Adjustable: No/Yes
Number of Cooling Stages Installed This is the number of cooling stages installed. Adjustable: 1 to 4
Number of Refrig Systems Installed This is the number of refrigeration systems installed Adjustable: 0 to 4
CV Occupied Cooling Setpoint This is the Control Volume Occupied Cooling Setpoint Adjustable: 45 to 98°F
CV Unoccupied Cooling Setpoint This is the Control Volume Unoccupied Cooling Setpoint Adjustable: 46 to 99°F
SZ VAV Occupied Cooling Setpoint This is the Single Zone Variable Air Volume Occupied Cooling Setpoint Adjustable: 45 to 98°F
SZ VAV Unoccupied Cooling Setpoint This is the Single Zone Variable Air Volume unoccupied Cooling Setpoint Adjustable: 45 to 98°F
Common Setpoint This is the common setpoint; available in common setpoint mode. This setpoint will not be in effect in the individual setpoint mode Adjustable: 45 to 98°F
Auto Changeover Differential that is used to limit switching between heating and cooling (present when Heat Cool Setpoint Mode = Common Setpoint) Adjustable: 2 to 5°F
Heat Cool Setpoint Mode This allows user to switch between single occupied setpoint and individual heating/cooling setpoint Adjustable: Common Setpoint / Individual Setpoints
Compressor Stage 1 Enabled This is enabled if there is 1 stage of cooling in the system Adjustable: Yes/No
Compressor Stage 2 Enabled This is enabled if there is 2 stages of cooling in the system Adjustable: Yes/No
Compressor Stage 3 Enabled This is enabled if there is 3 stages of cooling in the system Adjustable: Yes/No
Compressor Stage 4 Enabled This is enabled if there is 4 stages of cooling enabled Adjustable: Yes/No
Minimum Runtime for a Cooling Stage This is the minimum runtime a cooling stage must be running before it will turn off. The cooling stage will continue to run even for this duration even if the cooling call is lost. Adjustable: 3 to 10 minutes
Cooling Adaptive Tuning Enable This determines whether adaptive tuning is allowed to operate. When set to False, adaptive-tuning is disabled Adjustable: No/Yes
Low Ambient Enabled Control input to determine if the Low ambient setpoint is used Adjustable: No/Yes
Low Ambient Cooling Stages 10 on 5 off Setpoint This is the temperature that the Outdoor Air temperature (OAT) is compared with in order to detect the low ambient condition Adjustable: 0 to 60°F
Lead/Lag Equalize Cooling Stage Runtime Enabled This input is used to determine if runtime/start count equalization functionality is being used. If enabled, resetting the stage from a direct thermostat signal is not possible. Adjustable: No/Yes
OAT Cooling Cutout Enabled Specifies whether Cooling is locked out when free cooling is available. Adjustable: No/Yes
OAT Cooling Cutout This is the value the outside air temperature must go below in order to lockout the cooling. ie change from False to True Note: True=Lockout Cooling, False=Enable Cooling Adjustable: 0 to 100°F
Details: Cooling: Setup (continued) SAT Limit for Cooling Enable This input Indicates that SAT Cooling Limit control is determining the damper minimum position in the Damper Minimum Position Determination module. Adjustable: No/Yes
SAT Limit for Cooling Setpoint This is the minimum value that the supply air temperature is allowed to assume. Adjustable: 40 to 65°F
Hot Gas Bypass Present Determines if the Hot Gas Bypass stream is present in the system Adjustable: No/Yes
Freeze Condition Setpoint Determines what temperature the freeze condition is at Adjustable: 20 to 32°F
Pump Out Enable Determines if the pump out is enabled or disabled Adjustable: Disable/Enable
Low Ambient Fan Pre-run Time For Cooling Determines if the Low Ambient Fan Pre-run time. In cooling conditions and is in low ambient conditions, the fan will turn on before compressors begin Adjustable: 0 s to 255 s
Cooling Manual Tuning Selects the range when Cooling manual tuning begins Adjustable: 1 to 2.5 delta °F
Low Ambient Start Determines if Low Ambient should be set on start Adjustable: No/Yes
4 Pipe Split Enable Determines if the system is set up in a 4 pipe split configuration Adjustable: No/Yes
Details: Cooling: Service: Unit Staged Cooling Command Indicates the staged cooling command Read Only
CV Operating Cooling Setpoint Indicates the calculated control volume operating cooling setpoint Read Only
SZ VAV Operating Cooling Setpoint Indicates the SZ VAV operating cooling setpoint Read Only
Cooling Status Indicates the status of the cooling control Read Only
Operational Outdoor Air Temperature Indicates the calculated operating outdoor air temperature for cooling Read Only
Operational Space Temperature Indicates the calculated operational space temperature for cooling Read Only
Return Air Temperature Indicates the return air temperature Read Only
Econ Free Cooling Available Indicates if economizer free cooling is available rooting from the outdoor conditions Read Only
Supply Air Temperature Indicates the current supply air temperature being discharged from the duct Read Only
Y1 - Thermostat Indicates the Y1 cooling call from the Thermostat Read Only
Y2 - Thermostat Indicates the Y2 cooling call from the Thermostat Read Only
Y3 - Thermostat Indicates the Y3 cooling call from the Thermostat Read Only
Y4 - Thermostat Indicates the Y4 cooling call from the Thermostat Read Only
Condenser Fan 1 Indicates the status of Condenser Fan 1 Read Only
Condenser Fan 2 Indicates the status of Condenser Fan 2 Read Only
Details: Cooling: Service: Stage 1 Compressor Stage 1 Status Indicates the status of compressor stage 1 Read Only
Compressor Stage Command 1 Indicates the command of compressor stage 1 Read Only
Min On Time Remaining 1 Indicates the remaining minimum runtime for the compressor. Once the timer expires, and cooling call is removed, the compressor may turn off. Read Only
Anti-Short Cycle Delay Time Remaining 1 Indicates the remaining anti-short cycle delay time. Read Only
Compressor Stage Accumulated Runtime 1 Indicates the accumulated runtime for compressor stage 1. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Efficiency Index 1 Indicates the current efficiency index rating based for cooling stage 1 Read Only
Capacity Index 1 Indicates the capacity index for cooling stage 1 Read Only
Condensing Temperature over Ambient 1 Indicates the condensing temperature during ambient conditions for stage 1 Read Only
Evaporating Temperature Value Circuit 1 Indicates the evaporating temperature value in the refrigeration circuit for cooling stage 1 Read Only
Cooling Circuit Test Status The status of the cooling circuit test Read Only
Superheat Indicates the Superheat temperature Read Only
Subcooling Indicates the Subcooling temperature Read Only
Details: Cooling: Service: Stage 2 Compressor Stage 2 Status Indicates the status of compressor stage 2 Read Only
Compressor Stage Command 2 Indicates the command of compressor stage 2 Read Only
Min On Time Remaining 2 Indicates the remaining minimum runtime for the compressor. Once the timer expires, and cooling call is removed, the compressor may turn off. Read Only
Anti-Short Cycle Delay Time Remaining 2 Indicates the remaining anti-short cycle delay time. Read Only
Compressor Stage Accumulated Runtime 2 Indicates the accumulated runtime for compressor stage 2. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Efficiency Index 2 Indicates the current efficiency index rating based for cooling stage 2 Read Only
Capacity Index 2 Indicates the capacity index for cooling stage 2 Read Only
Condensing Temperature over Ambient 2 Indicates the condensing temperature during ambient conditions for stage 2 Read Only
Evaporating Temperature Value Circuit 2 Indicates the evaporating temperature value in the refrigeration circuit for cooling stage 2 Read Only
Cooling Circuit Test Status The status of the cooling circuit test Read Only
Superheat Indicates the Superheat temperature Read Only
Subcooling Indicates the Subcooling temperature Read Only
Details: Cooling: Service: Stage 3 Compressor Stage 3 Status Indicates the status of compressor stage 3 Read Only
Compressor Stage Command 3 Indicates the command of compressor stage 3 Read Only
Min On Time Remaining 3 Indicates the remaining minimum runtime for the compressor. Once the timer expires, and cooling call is removed, the compressor may turn off. Read Only
Anti-Short Cycle Delay Time Remaining 3 Indicates the remaining anti-short cycle delay time. Read Only
Compressor Stage Accumulated Runtime 3 Indicates the accumulated runtime for compressor stage 3. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Efficiency Index 3 Indicates the current efficiency index rating based for cooling stage 3 Read Only
Capacity Index 3 Indicates the capacity index for cooling stage 3 Read Only
Condensing Temperature over Ambient 3 Indicates the condensing temperature during ambient conditions for stage 3 Read Only
Evaporating Temperature Value Circuit 3 Indicates the evaporating temperature value in the refrigeration circuit for cooling stage 3 Read Only
Cooling Circuit Test Status The status of the cooling circuit test Read Only
Superheat Indicates the Superheat temperature Read Only
Subcooling Indicates the Subcooling temperature Read Only
Details: Cooling: Service: Stage 4 Compressor Stage 4 Status Indicates the status of compressor stage 4 Read Only
Compressor Stage Command 4 Indicates the command of compressor stage 4 Read Only
Min On Time Remaining 4 Indicates the remaining minimum runtime for the compressor. Once the timer expires, and cooling call is removed, the compressor may turn off. Read Only
Anti-Short Cycle Delay Time Remaining 4 Indicates the remaining anti-short cycle delay time. Read Only
Compressor Stage Accumulated Runtime 4 Indicates the accumulated runtime for compressor stage 4. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Efficiency Index 4 Indicates the current efficiency index rating based for cooling stage 4 Read Only
Capacity Index 4 Indicates the capacity index for cooling stage 4 Read Only
Condensing Temperature over Ambient 4 Indicates the condensing temperature during ambient conditions for stage 4 Read Only
Evaporating Temperature Value Circuit 4 Indicates the evaporating temperature value in the refrigeration circuit for cooling stage 4 Read Only
Cooling Circuit Test Status The status of the cooling circuit test Read Only
Superheat Indicates the Superheat temperature Read Only
Subcooling Indicates the Subcooling temperature Read Only
Details: Cooling: Sensors Evaporator Coil Temp 1 The temperature reading for Evaporator Coil 1 Read Only
Condenser Coil Temp 1 The temperature reading for Condenser Coil 1 Read Only
Suction Pressure 1 The pressure reading in Suction Line 1 Read Only
Liquid Pressure 1 The pressure reading in Liquid Line 1 Read Only
Suction Temperature 1 The temperature reading in Suction Line 1 Read Only
Liquid Temperature 1 The temperature reading in Suction Line 1 Read Only
Evaporator Coil Temp 2 The temperature reading for Evaporator Coil 2 Read Only
Condenser Coil Temp 2 The temperature reading for Condenser Coil 2 Read Only
Suction Pressure 2 The pressure reading in Suction Line 2 Read Only
Liquid Pressure 2 The pressure reading in Liquid Line 2 Read Only
Suction Temperature 2 The temperature reading in Suction Line 2 Read Only
Liquid Temperature 2 The temperature reading in Suction Line 2 Read Only
Evaporator Coil Temp 3 The temperature reading for Evaporator Coil 3 Read Only
Condenser Coil Temp 3 The temperature reading for Condenser Coil 3 Read Only
Suction Pressure 3 The pressure reading in Suction Line 3 Read Only
Liquid Pressure 3 The pressure reading in Liquid Line 3 Read Only
Suction Temperature 3 The temperature reading in Suction Line 3 Read Only
Liquid Temperature 3 The temperature reading in Suction Line 3 Read Only
Evaporator Coil Temp 4 The temperature reading for Evaporator Coil 4 Read Only
Condenser Coil Temp 4 The temperature reading for Condenser Coil 4 Read Only
Suction Pressure 4 The pressure reading in Suction Line 4 Read Only
Liquid Pressure 4 The pressure reading in Liquid Line 4 Read Only
Suction Temperature 4 The temperature reading in Suction Line 4 Read Only
Liquid Temperature 4 The temperature reading in Suction Line 4 Read Only
Details: Cooling: Safeties High Pressure Limit 1 This is the High Pressure Alarm No. 1 input from the High Pressure Event Primitive. Read Only
High Pressure Lockout 1 If High Pressure Limit 1 is tripped enough times, High Pressure Lockout 1 will take effect. Read Only
Low Pressure Limit 1 This is the Low Pressure Alarm No. 1 input from the Low Pressure Event Primitive. Read Only
Low Pressure Lockout 1 If the Low Pressure Limit 1 is tripped enough times, Low Pressure Lockout 1 will take effect. Read Only
Freeze Condition 1 This is the Freeze condition for evaporator coil 1. If the temperature goes below this, it will trigger an alarm. Read Only
Freeze Condition Lockout 1 If the Freeze Condition 1 is tripped enough times, the Freeze Condition Lockout 1 will take effect. Read Only
High Pressure Limit 2 This is the High Pressure Alarm No. 2 input from the High Pressure Event Primitive. Read Only
High Pressure Lockout 2 If High Pressure Limit 2 is tripped enough times, High Pressure Lockout 2 will take effect. Read Only
Low Pressure Limit 2 This is the Low Pressure Alarm No. 2 input from the Low Pressure Event Primitive. Read Only
Low Pressure Lockout 2 If the Low Pressure Limit 2 is tripped enough times, Low Pressure Lockout 2 will take effect. Read Only
Freeze Condition 2 This is the Freeze condition for evaporator coil 2. If the temperature goes below this, it will trigger an alarm. Read Only
Freeze Condition Lockout 2 If the Freeze Condition 2 is tripped enough times, the Freeze Condition Lockout 2 will take effect. Read Only
High Pressure Limit 3 This is the High Pressure Alarm No. 3 input from the High Pressure Event Primitive. Read Only
High Pressure Lockout 3 If High Pressure Limit 3 is tripped enough times, High Pressure Lockout 3 will take effect. Read Only
Low Pressure Limit 3 This is the Low Pressure Alarm No. 3 input from the Low Pressure Event Primitive. Read Only
Low Pressure Lockout 3 If the Low Pressure Limit 3 is tripped enough times, Low Pressure Lockout 3 will take effect. Read Only
Freeze Condition 3 This is the Freeze condition for evaporator coil 3. If the temperature goes below this, it will trigger an alarm. Read Only
Freeze Condition Lockout 3 If the Freeze Condition 3 is tripped enough times, the Freeze Condition Lockout 3 will take effect. Read Only
High Pressure Limit 4 This is the High Pressure Alarm No. 4 input from the High Pressure Event Primitive. Read Only
High Pressure Lockout 4 If High Pressure Limit 4 is tripped enough times, High Pressure Lockout 4 will take effect. Read Only
Low Pressure Limit 4 This is the Low Pressure Alarm No. 4 input from the Low Pressure Event Primitive. Read Only
Low Pressure Lockout 4 If the Low Pressure Limit 4 is tripped enough times, Low Pressure Lockout 4 will take effect. Read Only
Freeze Condition 4 This is the Freeze condition for evaporator coil 4. If the temperature goes below this, it will trigger an alarm. Read Only
Freeze Condition Lockout 4 If the Freeze Condition 4 is tripped enough times, the Freeze Condition Lockout 4 will take effect. Read Only
Details: Cooling: Misc Maximum Temperature / Humidity Setpoint Offset This is the maximum temperature humidity setpoint offset. Adjustable: 0 to 5 delta °F
Temperature/Humidity Setpoint This input defines the dehumidification set point during the Occupied mode. Adjustable: 20 to 80% RH
Temperature/Humidity (Return) Control Enable This enables the return temperature/humidity control. Adjustable: No/Yes
Operational Space Humidity This is the present value of the operational space humidity. Read Only
CV Occupied Cooling Setpoint The Occupied Cooling Setpoint Adjustable: 45 to 98°F
CV Operating Cooling Setpoint The operating cooling setpoint used by the controller. Operating setpoints are calculated setpoints to make the system more efficient Read Only
SZ VAV Occupied Cooling Setpoint The Single Zone Variable Air Volume occupied setpoint used by the controller Adjustable: 45 to 98°F
SZ VAV Operating Cooling Setpoint The Single Zone Variable Air Volume operating setpoint used by the controller. Operating setpoints are calculated setpoints to make the system more efficient Read Only
Common Setpoint The common setpoint is used when the control is in Common Setpoint mode. This setpoint controls both heating and cooling Adjustable: 45 to 98°F
Auto Changeover Differential that is used to limit switching between heating and cooling (present when Heat Cool Setpoint Mode = Common Setpoint) Adjustable: 2 to 5°F
Temperature / Humidity Value per Degree Offset The humidity per degree offset to compensate for uncomfortable dry or wet conditions Adjustable: 1 to 10% RH
Details: Heating: Setup Heating Mode Enabled For Operation Enables heating mode for operation. If No, the heating mode still be disabled Adjustable: No/Yes
Number of Heating Stages Installed The number of heating stages installed. The maximum allowable stages is 3. Adjustable: 0 to 3
Heating Control Type Determines the Heating control type for the system Adjustable: Heat Cool Type
CV Occupied Heating Setpoint The occupied heating setpoint when configured to individual setpoint mode Adjustable: 46 to 99°F
CV Unoccupied Heating Setpoint The unoccupied setpoint when configured to individual setpoint mode Adjustable: 45 to 98°F
VAV Occupied Heating Setpoint The Variable Air Volume occupied heating setpoint Adjustable: 46 to 99°F
VAV Unoccupied Heating Setpoint The Variable Air Volume unoccupied heating setpoint Adjustable: 45 to 98°F
SZ VAV Occupied Heating Setpoint The Single Zone Variable Air Volume occupied heating setpoint in individual setpoint mode Adjustable: 46 to 99°F
SZ VAV Unoccupied Heating Setpoint The Single Zone Variable Air Volume unoccupied heating setpoint in individual setpoint mode Adjustable: 45 to 98°F
Common Setpoint The common setpoint is used when the control is in Common Setpoint mode. This setpoint controls both heating and cooling Adjustable: 45 to 98°F
Auto Changeover Differential that is used to limit switching between heating and cooling (present when Heat Cool Setpoint Mode = Common Setpoint) Adjustable: 2 to 5°F
Heat Cool Setpoint Mode This allows user to switch between single occupied setpoint and individual heating/cooling setpoint Adjustable: Common Setpoint / Individual Setpoints
Heating Adaptive Tuning Enable This allows adaptive tuning to be enabled for heating control Adjustable: No/Yes
SAT Air Temp Limit for Heating Enabled This allowing the maximum supply air temperature limit to be set Adjustable: No/Yes
SAT Air Temp Limit For Heating Setpoint The supply air temperature limit for heating. This is the maximum the heating setpoint can be set to Adjustable: 100 to 180°F
Outdoor Air Temp Heating Cutout Setpoint The outdoor air temp heating cutout setpoint determines when the damper should be open/closed. Adjustable: 0 to 100°F
Number of Gas Valves Installed Configured to the system to determine how many gas valves are installed. The maximum number of gas valves this control supports is 3. Adjustable: 0 to 3
Number of Limit Switches Configured to the system to determine how many limit switches are installed. Read Only
Low Limit Enable Allows Low limit control to be enabled/disabled Adjustable: Disable/Enable
Low Limit Upper SAT Setpoint This is the low limit upper supply air temperature setpoint Adjustable: 65 to 85°F
Low Limit Lower SAT Setpoint This is the low limit lower supply air temperature setpoint. Adjustable: 60 to 80°F
Heating Manual Tuning Allows the range for manual tuning to be set in heating setup. Adjustable: 1 to 2.5 delta °F
Cooling Allowed During Heat Limit Enables cooling allowed while control is in heating limit Adjustable: Off/On
Details: Heating: Service Staged Heating Command Indicates the staged heating command Read Only
CV Operating Heating Setpoint The control volume calculated operating setpoint Read Only
SZ VAV Operating Heating Setpoint The single zone variable air volume calculated operating setpoint Read Only
VAV Operating Heating Setpoint the variable air volume calculated operating heating setpoint Read Only
Heating Status The current status of the heating control Read Only
Operational Outdoor Air Temperature The current operational outdoor air temperature Read Only
Operational Space Temperature The current operational space temperature Read Only
Return Air Temperature The current return air temperature Read Only
W1 - Thermostat Indicates the W1 heating call from the thermostat Read Only
W2 - Thermostat Indicates the W2 heating call from the thermostat Read Only
W3 - Thermostat Indicates the W3 heating call from the thermostat Read Only
G - Thermostat Indicates the G fan call from the thermostat Read Only
Heating Stage 1 Status The current status of heating stage 1 Read Only
Heating Stage Command 1 The current command of heating stage 1 Read Only
Heating Stage 1 Min On Time Remaining The remaining minimum on time for heating stage 1. Once expired, heating is allowed to turn off. Read Only
Heating Stage 1 Anti-Short Cycle Delay Time Remaining The time remaining on the Anti-Short-Cycle-Delay (ASCD) for heating stage 1 Read Only
Heating Stage 1 Accumulated Runtime The accumulated runtime for heating stage 1 Adjustable: 0 to 10,000 hours
Heating Stage Command 2 The current command of heating stage 2 Read Only
Heating Stage 2 Status The current status of heating stage 2 Read Only
Heating Stage 2 Min On Time Remaining The remaining minimum on time for heating stage 2. Once expired, heating is allowed to turn off. Read Only
Heating Stage 2 Anti-Short Cycle Delay Time Remaining The time remaining on the Anti-Short-Cycle-Delay (ASCD) for heating stage 2 Read Only
Heating Stage 2 Accumulated Runtime The accumulated runtime for heating stage 2 Adjustable: 0 to 10,000 hours
Heating Stage Command 3 The current command of heating stage 3 Read Only
Heating Stage 3 Status The current status of heating stage 3 Read Only
Heating Stage 3 Min On Time Remaining The remaining minimum on time for heating stage 3. Once expired, heating is allowed to turn off. Read Only
Heating Stage 3 Anti-Short Cycle Delay Time Remaining The time remaining on the Anti-Short-Cycle-Delay (ASCD) for heating stage 3 Read Only
Heating Stage 3 Accumulated Runtime The accumulated runtime for heating stage 3 Adjustable: 0 to 10,000 hours
Details: Heating: Safeties Heat Limit1 Switch This is the first limit switch. If triggered, the fan will turn on Read Only
Heat Limit1 Switch Lockout If the first limit switch is triggered enough, the heat limit switch lockout will turn on and lock the fan on Read Only
Heat Limit2 Switch This is the second limit switch. If triggered, the fan will turn on Read Only
Heat Limit2 Switch Lockout If the second limit switch is triggered enough, the heat limit switch lockout will turn on and lock the fan on Read Only
Heat Limit3 Switch This is the third limit switch. If triggered, the fan will turn on Read Only
Heat Limit3 Switch Lockout If the third limit switch is triggered enough, the heat limit switch lockout will turn on and lock the fan on Read Only
Gas Valve1 Input Indicates that the first gas valve is open/closed Read Only
Gas Valve2 Input Indicates that the second gas valve is open/closed Read Only
Gas Valve3 Input Indicates that the third gas valve is open/closed Read Only
Details: Heating: Proportional: Setup Hydronic Heating Stage #1 Supply Air Setpoint This is the supply air setpoint for the first stage of hydronic heating. These setpoints are traditionally higher because they must radiate their heat through a medium. Adjustable: 80 to 180°F
Hydronic Heating Stage #2 Supply Air Setpoint This is the supply air setpoint for the second stage of hydronic heating. These setpoints are traditionally higher because they must radiate their heat through a medium. Adjustable: 80 to 180°F
Hydronic Heat SAT Tempering Enabled Allows Hydronic supply air temperature to be enabled Adjustable: No/Yes
Hydronic Heat SAT Tempering Setpoint Determines the hydronic heating supply air temperature setpoint Adjustable: 40 to 60°F
Hydronic Heat Valve Reverse Acting Allows the hydronic heating valve to enable the reverse acting functionality Adjustable: No/Yes
Details: Heating: Proportional: Service CV Occupied Heating Setpoint The control volume occupied heating setpoint Adjustable: 46 to 99°F
CV Unoccupied Heating Setpoint The control volume unoccupied heating setpoint Adjustable: 45 to 98°F
CV Operating Heating Setpoint The control volume calculated operating heating setpoint Read Only
VAV Operating Heating Setpoint the variable air volume calculated operating heating setpoint Read Only
SZ VAV Operating Setpoint The single zone variable air volume calculated operating setpoint Read Only
Operational Space Temperature The present value of the operational space temperature Read Only
Supply Air Temperature The present value of the supply air temperature Read Only
W1 - Thermostat Indicates the W1 heating call from the thermostat Read Only
W2 - Thermostat Indicates the W2 heating call from the thermostat Read Only
Hydronic Heat Valve % Command The % command for the hydronic heating valve Read Only
Hydronic Heat Valve Reverse Acting Determines if the hydronic heat valve is reverse acting or not Adjustable: No/Yes
Hot Water Freeze Stat Indicates if the hot water line is experiencing frost on it. Usually occurs when hydronic heat is idle for longer durations in low ambient conditions Read Only
Details: Indoor Fan: Setup Fan Control Type Determines the fan control type that the system uses Adjustable: SE RTU Fan Control Type
Continuous Fan Operation in Occupied Mode Allows fan to run continuously during occupied state Adjustable: Yes/No
Fan On Delay for Heat Determines the Fan On Delay when heating is called Adjustable: 0 to 30 seconds
Fan Off Delay for Heat Determines the Fan Off Delay when heating is removed Adjustable: 0 s to 255 s
Turn Off Continuous Fan Operation When Starting Heat Allows continuous fan mode to be turned off during heating mode Adjustable: Yes/No
Fan On Delay for Cool Determines the Fan On Delay when cooling is called Adjustable: 0 to 30 seconds
Fan Off Delay for Cool Determines the Fan Off Delay when cooling is removed Adjustable: 0 s to 255 s
Occupied: No Heat or Cool % Command Indicates the occupied no heat/cool fan percent command for the indoor Adjustable: 0 to 100%
Occupied: One Stage of Cool % Command Indicates the occupied first stage of cooling fan percent command for the indoor fan Adjustable: 0 to 100%
Occupied: Two Stage of Cool % Command Indicates the occupied second stage of cooling fan percent command for the indoor fan Adjustable: 0 to 100%
Occupied: Three Stage of Cool % Command Indicates the occupied third stage of cooling fan percent command for the indoor fan Adjustable: 0 to 100%
Occupied: Four Stage of Cool % Command Indicates the occupied fourth stage of cooling fan percent command for the indoor fan Adjustable: 0 to 100%
Occupied: One Stage of Heat % Command Indicates the occupied first stage of heating fan percent command for the indoor fan Adjustable: 0 to 100%
Occupied: Two Stage of Heat % Command Indicates the occupied second stage of heating fan percent command for the indoor fan Adjustable: 0 to 100%
Occupied: Three Stage of Heat % Command Indicates the occupied third stage of heating fan percent command for the indoor fan Adjustable: 0 to 100%
Dehumidification % Command Indicates the fan percent command during dehumidification for the indoor fan Adjustable: 0 to 100%
Low Ambient Fan Pre-run Time For Cooling Indicates how long the fan will blow in low ambient conditions before cooling starts up. This strategy blows the ambient cool air through the system before engaging the compressors Adjustable: 0 s to 255 s
Air Proving Switch Setup Indicates if the air proving switch is set up for the indoor fan Adjustable: Fan Setup
Dirty Filter Switch Indicates if the indoor fan filter is dirty or not. If dirty, it may be time to change the filter Read Only
Details: Indoor Fan: Service G - Thermostat Indicates the G fan call from the thermostat Read Only
Fan Status Indicates the current status of the indoor fan Read Only
Fan Command Indicates the current fan percent command for the indoor fan Read Only
Fan Accumulated Runtime Indicates how long the fan has been running. This value is adjustable; however should not be changed unless a software update requires it Adjustable: 0 to 10,000 hours
Operating Fan Request Indicates the calculated operating fan request for the indoor fan Read Only
Fan Request Source Indicates where the fan request is coming from. This could be from the user or controller. Read Only
Air Proving Switch Indicates the status of the air proving switch for the indoor fan Read Only
Fan Overload Indicates if the fan load exceeded the maximum percent. Read Only
Fan VFD Fault Indicates if the Variable Frequency Drive indoor fan is in fault or not Read Only
Details: Economizer: Setup Economizer Enabled For Operation Determines if the installed economizer is installed or not. If an economizer is not installed, this should be set to no Adjustable: No/Yes
Economizer Minimum Position Setpoint Determines the economizer minimum position setpoint Adjustable: 0 to 100%
Economizer Damper Minimum Position Low Speed Fan Determines the economizer minimum position when the fan is running at low speed Adjustable: 0 to 100%
Low Ambient Economizer Minimum Position Determines the economizer minimum position in low ambient conditions Adjustable: 0 to 100%
Low Ambient Economizer Setpoint Determines when the economizer should be enabled/disabled in low ambient conditions Adjustable: 0 to 60°F
Free Cooling Selection Determines the economizer type that has been installed. Single Temperature, Single Enthalpy, Dual Enthalpy and Auto are the types of support economizers Adjustable: Economizer Type
Free Cooling Current Mode The current free cooling status Read Only
All Compressors Off in Free Cooling Determines if all compressors should be off in free cooling mode. This allows the system to only use the outdoor air damper to cool the system in free cooling mode Adjustable: No/Yes
Economizer Outdoor Air Temp Enable Setpoint Determines the setpoint for when the economizer should be enabled. Adjustable: 40 to 80°F
Economizer Outdoor Air Enthalpy Setpoint Determines the outdoor air enthalpy setpoint for when the economizer should be enabled. Adjustable: 10 to 50 Btu/lb dry air
Demand Ventilation Mode of Operation Determines the mode for when the economizer should be enabled. This allows the economizer to open/close based on IAQ and OAQ Adjustable: SE RTU DCV Mode
Demand Ventilation Maximum Economizer Position Determines the maximum position for the economizer when it receives a ventilation request Adjustable: 0 to 100%
Demand Ventilation Indoor Air Quality Setpoint Determines the indoor air quality setpoint for when the economizer should begin ventilation Adjustable: 0 to 5,000 ppm
Demand Ventilation Differential Setpoint Determines when the economizer should begin ventilation based on indoor and outdoor air quality differential Adjustable: 0 to 5,000 ppm
Indoor Air Quality Sensor Range Determines the Indoor air quality sensor range Adjustable: 0 to 5,000 ppm
Outdoor Air Quality Sensor Range Determines the outdoor air quality sensor range Adjustable: 0 to 5,000 ppm
Economizer Loading Enabled Determines if the economizer should adjusted based indoor desired setpoint and outdoor air temperature Adjustable: No/Yes
Fresh Air Intake Setpoint Determines how much air should be taken in when receiving a ventilation request Adjustable: 0 to 50000 cfm
Fresh Air Intake Max Sensor Range Determines the maximum sensor range for the air velocity Adjustable: 0 to 50,000 cfm
EconMech Setup Determines if economizer + mechanical cooling is setup Adjustable: SE RTU EconMech Setup
Economizer Fault Detection Enable Determines if the economizer fault detection sensor is enabled Adjustable: Disable/Enable
Calibration Fault Detect Enable Determines if the calibration fault detection sensor is enabled. Adjustable: Disable/Enable
Details: Economizer: Service Cooling Status Indicates the current cooling status Read Only
Economizer Status Indicates the current economizer status Read Only
Econ Free Cooling Available Indicates if free cooling is available Read Only
Economizer Damper % Command Indicates the economizer damper percent command Read Only
Supply Air Temperature Indicates the supply air temperature of the economizer Read Only
Operational Outdoor Air Temperature Indicates the operational outdoor air temperature Read Only
Outdoor Air Enthalpy Indicates the outdoor air enthalpy Read Only
Return Air Enthalpy Indicates the return air enthalpy Read Only
Operational Indoor Air Quality Indicates the operational indoor air quality Read Only
Operational Outdoor Air Quality Indicates the operational outdoor air quality Read Only
Fresh Air Intake Value Indicates the amount of fresh air coming into the system Read Only
Economizer Damper Position Indicates the damper position of the economizer Read Only
FDD Economizer Alarm Delay Determines the FDD economizer alarm delay Adjustable: 0 to 3,600 seconds
FDD Economizer Damper Allowed Error Determines the allowable error for the economizer Adjustable: 0 to 100%
FDD Damper Min Position Tolerance Determines the damper min position tolerance Adjustable: 0 to 100%
Details: Demand Ventilation Economizer Enabled For Operation Determines if the economizer is enabled for ventilation Adjustable: No/Yes
Demand Ventilation Mode of Operation Determines the demand ventilation mode of operation Adjustable: SE RTU DCV Mode
Demand Ventilation Maximum Economizer Position Determines the maximum economizer position during demand ventilation Adjustable: 0 to 100%
Demand Ventilation Indoor Air Quality Setpoint Determines the IAQ setpoint for demand ventilation Adjustable: 0 to 5,000 ppm
Demand Ventilation Differential Setpoint Determines the Air quality differential setpoint for demand ventilation Adjustable: 0 to 5,000 ppm
Indoor Air Quality Sensor Range Determines the IAQ sensor range for Demand Ventilation Adjustable: 0 to 5,000 ppm
Outdoor Air Quality Sensor Range Determines the OAQ sensor range for demand ventilation Adjustable: 0 to 5,000 ppm
Operational Indoor Air Quality Indicates the current operational IAQ Read Only
Operational Outdoor Air Quality Indicates the current operational OAQ Read Only
Economizer Damper Position Indicates the current economizer damper position Read Only
Details: Air Monitor Station Economizer Enabled For Operation Determines if the economizer is enabled for air monitor station Adjustable: No/Yes
Fresh Air Intake Enable Determines if the economizer is available to intake fresh air Adjustable: Disable/Enable
Fresh Air Intake Setpoint Determines how much air should be taken in at the air monitor station Adjustable: 0 to 50,000 cfm
Fresh Air Intake Max Sensor Range Determines the maximum cfm that should be taken in at the air monitor station Adjustable: 0 to 50,000 cfm
Fresh Air Intake Value Indicates the current CFM that the economizer is taking in Read Only
Economizer Damper Position Indicates the current damper position of the economizer Read Only
Fresh Air Range Determines the cfm range for fresh air to be taken in Adjustable: 0 to 5,000 cfm
Details: Power Exhaust: Setup Exhaust Type Determines the exhaust type used in the Power exhaust configuration Adjustable: SE RTU Exhaust Setup
Economizer Damper Position for Exhaust Fan to Turn On Determines the economizer damper position that allows the exhaust fan to turn on Adjustable: 20 to 99%
Economizer Damper Position for Exhaust Fan to Turn Off Determines the economizer damper position that turns off the exhaust fan Adjustable: 10 to 89%
Exhaust Damper Position for Exhaust Fan to Turn On Determines the damper position that allows the exhaust fan to turn on Adjustable: 20 to 99%
Exhaust Damper Position for Exhaust Fan to Turn Off Determines the damper position that turns off the exhaust fan Adjustable: 10 to 89%
Building Pressure Setpoint Determines the Building pressure setpoint to be used by the power exhaust configuration Adjustable: -0.25 to 0.25 in wc
Duct Static Pressure Indicates the current duct static pressure Read Only
Details: Power Exhaust: Service Exhaust Fan Status Indicates the current exhaust fan status Read Only
Exhaust Fan Command Indicates the exhaust fan percent command Read Only
Building Static Pressure Indicates the building static pressure Read Only
Exhaust Damper % Command Indicates how far exhaust damper is open Read Only
Exhaust Fan VFD % Command Indicates how fast the exhaust fan vfd is running Read Only
Exhaust Fan Accumulated Runtime Indicates how long the exhaust fan has been running Read Only
Exhaust Fan VFD Fault Indicates if the exhaust fan is experiencing a VFD fault Read Only
Details: FanVFD: Setup Fan Control Type Determines the Fan control type Adjustable: SE RTU Fan Control Type
Duct Pressure Setpoint Determines the Duct Pressure setpoint Adjustable: 0 to 5 in wc
Duct Pressure Shutdown Setpoint Determines the duct pressure shutdown setpoint. The fan will shutdown if this setpoint is hit. Adjustable: 0 to 5 in wc
VAV Cooling Supply Air Temp Upper Setpoint Determines the upper VAV cooling SAT setpoint Adjustable: 41 to 70°F
VAV Cooling Supply Air Temp Lower Setpoint Determines the lower VAV cooling setpoint Adjustable: 40 to 69°F
VAV Supply Air Temp Reset Setpoint Determines the SAT setpoint after reset Adjustable: 40 to 85°F
VAV Unoccupied Cooling Setpoint Determines the unoccupied VAV cooling setpoint Adjustable: 46 to 99°F
Morning Warmup Enabled Determines if the morning warmup algorithm should be enabled Adjustable: No/Yes
Morning Warmup/Return Air Temp Setpoint If enabled, determines the warmup and return air temperature setpoints Adjustable: 50 to 85°F
VAV Occupied Heating Enabled Determines if VAV heating during occupied should be enabled Adjustable: No/Yes
VAV Occupied Heating Setpoint If enabled, determines the VAV occupied heating setpoint Adjustable: 40 to 85°F
Unoccupied Heating Enabled Determines if VAV heating during unoccupied is enabled Adjustable: No/Yes
VAV Unoccupied Heating Setpoint If enabled, determines the VAV occupied heating setpoint Adjustable: 45 to 98°F
Morning Cooldown Enabled Determines if morning cooldown is enabled Adjustable: No/Yes
Morning Cooldown/Return Air Temp Setpoint If enabled, determines the morning cooldown/return air temp setpoints Adjustable: 50 to 85°F
Optimal Start Enabled Determines if optimal start is enabled Adjustable: No/Yes
Early Start Period Determines how early the optimal start should begin before occupancy Adjustable: 0 to 120 minutes
Discharge Air Static Pressure Minimum Determines the minimum discharge air static pressure Adjustable: 0.01 to 1 in. wc.
Discharge Air Static Pressure Alarm Delay Determines how long it will take for the alarm to trigger once it has been sensed Adjustable: 0 to 600 seconds
COBP Occupied Heating Enabled Determines if COBP occupied heating is enabled Adjustable: No/Yes
Details: FanVFD: Service Fan % Command Indicates the current Fan % command for the VFD fan Read Only
Duct Static Pressure Indicates the current duct static pressure Read Only
Duct Pressure Setpoint Determines the duct pressure setpoint Adjustable: 0 to 5 in wc
VAV Operating Cooling Supply Air Temp Setpoint Indicates the VAV Operating cooling SAT SP Read Only
Supply Air Temperature Indicates the current SAT Read Only
Staged Cooling Command Indicates the current staged cooling command Read Only
Cooling Status Indicates the current status of cooling operation Read Only
Econ Free Cooling Available Indicates if the economizer free cooling is available Read Only
Compressor Stage Command 1 Indicates the current command for Compressor Stage 1 Read Only
Compressor Stage Command 2 Indicates the current command for Compressor Stage 2 Read Only
Compressor Stage Command 3 Indicates the current command for Compressor Stage 3 Read Only
Compressor Stage Command 4 Indicates the current command for f Compressor Stage 4 Read Only
VAV Operating Heating Setpoint Indicates the current VAV operating heating setpoint Read Only
Staged Heating Command Indicates the current staged heating command Read Only
Operational Space Temperature Indicates the calculated operational space temperature Read Only
Heating Status Displays the current status of heating operation Read Only
Heating Stage Command 1 Indicates the current command for Heating Stage 1 Read Only
Heating Stage Command 2 Indicates the current command for Heating Stage 2 Read Only
Heating Stage Command 3 Indicates the current command for Heating Stage 3 Read Only
VAV Box Heat Command Indicates the heat command of the VAV box. This value will indicate if the VAV box is being used to heat the space Read Only
Details: Single Zone VAV: Setup SZ VAV Enabled Determines if Single Zone VAV is installed and enabled Adjustable: Off/On
SZ VAV Minimum Fan Speed Determines the minimum fan speed for the SZ VAV Adjustable: 0 to 100%
SZ VAV Occupied Cooling Setpoint Determines the occupied cooling setpoint for the SZ VAV Adjustable: 45 to 98°F
SZ VAV Unoccupied Cooling Setpoint Determines the unoccupied cooling setpoint for SZ VAV Adjustable: 45 to 98°F
VAV Occupied Heating Setpoint Determines the Occupied Heating Setpoint for the VAV Adjustable: 40 to 85°F
VAV Unoccupied Heating Setpoint Determines the unoccupied heating setpoint for the VAV Adjustable: 45 to 98°F
DAT Max Heating SP Determines the maximum allowable heating setpoint for the discharge air temperature Adjustable: 80 to 110°F
DAT Satisfied SP Determines the satisfied setpoint discharge air temperature setpoint Adjustable: 65 to 75°F
VAV Cooling Supply Air Temp Upper Setpoint Determines the Upper cooling SAT setpoint for the VAV Adjustable: 41 to 70°F
VAV Cooling Supply Air Temp Lower Setpoint Determines the Lower cooling SAT setpoint for the VAV Adjustable: 40 to 69°F
Details: Single Zone VAV: Service SZ VAV Operating Cooling Setpoint Indicates the calculated operational cooling setpoint for SZ VAV Read Only
SZ VAV Cooling Load Indicates the current cooling load for SZ VAV Read Only
SZ VAV Heating Load Indicates the current heating load for SZ VAV Read Only
Operational Space Temperature Indicates the calculated operational space temperature in the zone in which the SZ VAV is feeding into Read Only
Supply Air Temperature Indicates the current SAT for the SZ VAV Read Only
Fan % Command Indicates the current fan % command in the VAV box. Read Only
Economizer Damper % Command Indicates the current economizer damper position for the VAV box Read Only
Compressor Stage Command 1 Indicates the current command for Compressor Stage 1 Read Only
Compressor Stage Command 2 Indicates the current command for Compressor Stage 2 Read Only
Compressor Stage Command 3 Indicates the current command for Compressor Stage 3 Read Only
Compressor Stage Command 4 Indicates the current command for f Compressor Stage 4 Read Only
Details: Hot Gas Reheat: Setup Hot Gas Reheat Enabled For Operation Determines if Hot Gas Reheat is installed and enabled Adjustable: No/Yes
Dehumidify In Satisfied Displays if the dehumidification requirements are satisfied and requires no humidification process Read Only
Hot Gas Reheat Alternate Operation Enabled Used for selecting whether the hot gas reheat alternate operation is in effect Adjustable: No/Yes
Hot Gas Reheat Alternate Operation Writeable This input tells the control application if the alternate operation mode is writeable Adjustable: No/Yes
Hot Gas Reheat Humidity Setpoint Determines the HGR humidity setpoint Adjustable: 0 to 100% RH
HGR Enabled for Unoccupied Operation Determines if HGR will be enabled for unoccupied operation Adjustable: No/Yes
HGR Unoccupied Humidity Setpoint If enabled, determines the unoccupied humidity setpoint Adjustable: 0 to 100%
HGR Humidity Setpoint Differential Determines the HGR setpoint differential. This can be seen as a dead band for the setpoint when HGR should turn on Adjustable: 1 to 10%
Aux Mode Determines if auxiliary mode should be used for HGR Adjustable: Off/On
Use DFS for Dehum Determines if the Dirty Filter Switch binary input, used for detecting when the system needs to enter dehumidification, should be used Read Only
VAV Cooling Supply Air Temp Upper Setpoint Determines the Upper cooling SAT setpoint for the VAV Adjustable: 41 to 70°F
VAV Cooling Supply Air Temp Lower Setpoint Determines the Lower cooling SAT setpoint for the VAV Adjustable: 40 to 69°F
VAV Supply Air Temp Reset Setpoint Determines the setpoint that should be used after reboot cycles Adjustable: 40 to 85°F
Dehum Evap Low Setpoint Determines the dehumidification evap low setpoint Adjustable: 40 to 7017°F
Occupied Cooling Setpoint Determines the occupied cooling setpoint for HGR Adjustable: 45 - 98°F
Dehumidification % Command Determines the dehumidification % command during HGR Adjustable: 0 to 100%
Proportional Min Out Value Determines the proportional min out value for HGR Adjustable: 0 to 100%
Proportional Max Out Value Determines the proportional max out value for HGR Adjustable: 0 to 100%
Condenser Fan 2 OAT Cutout Setpoint Determines when CF2 should cut out due to OAT Adjustable: 50 to 85°F
Modulating HGR Value Full Open Allowed Determines if modulating HGR should be able to open fully. Adjustable: No/Yes
Details: Hot Gas Reheat: Service Staged Cooling Command Displays the current staged cooling command for hot gas reheat Read Only
CV Operating Cooling Setpoint Displays the current CV operating cooling setpoint for hot gas reheat Read Only
Operational Space Temperature Displays the calculated operational space temperature used by HGR Read Only
Operational Evap Temperature Setpoint Displays the calculated operational evap temperature setpoint used by HGR Read Only
Evaporator Coil Temp Displays the current temperature of the evaporator coil Read Only
Hot Gas Reheat Humidity Setpoint Determines the HGR humidity setpoint. Adjustable: 0 to 100% RH
Operational Space Humidity Displays the calculated operational space humidity based on controller logic Read Only
Hot Gas Reheat Status Displays the current status of hot gas reheat Read Only
Hot Gas Reheat Command Displays the current HGR command outputted by the control Read Only
Operational HGR Temperature Setpoint Displays the calculated operational HGR temperature setpoint Read Only
Supply Air Temperature Displays the current supply air temperature used by HGR Read Only
Hot Gas Reheat Bleed Valve Command Displays the HGR bleed valve command. This will indicate the position of the bleed valve Read Only
Compressor Stage Command 1 Indicates the current command for Compressor Stage 1 Read Only
Compressor Stage Command 2 Indicates the current command for Compressor Stage 2 Read Only
Compressor Stage Command 3 Indicates the current command for Compressor Stage 3 Read Only
Compressor Stage Command 4 Indicates the current command for f Compressor Stage 4 Read Only
Space Humidity RAH Input Indicates the return air humidity inputted from the space Read Only
Details: Heat Pump Number of Heat Pump Stages Installed Determines the number of heat pump stages installed in the system Adjustable: 0 to 2
Test Defrost Enable Determines if the defrost functionality should be tested Adjustable: False/True
Compressor Delay Enable Determines if there should be a compressor delay when using heat pump Adjustable: False/True
Defrost Curve Selection Determines the Defrost Curve that should be used for the unit. When the current curve selection equals 6 this value is used for the current Defrost Terminate Curve value. This value is adjustable at the factory. Adjustable: SE RTU Defrost Curves
Reversing Valve Indicates the status of the reversing valve Read Only
Auxiliary Heat Indicates if Aux heat is enabled Read Only
Mode Indicates which mode the heat pump is currently in Read Only
OAT Defrost Permission Determines the OAT in which the defrost cycle can perform Adjustable: 45 to 60°F
Details: ERV ERV Enabled Determines if energy recovery ventilators are installed Adjustable: No/Yes
ERV Unoccupied Fan Enabled Determines if ERV will run fan during unoccupied Adjustable: No/Yes
Fan Control Type Determines the fan control type for the energy recovery ventilator Adjustable: SE RTU Fan Control Type
Fan Command Indicates the current fan for the energy recovery ventilator Read Only
Econ Free Cooling Available Indicates if the economizer is available to benefit the ERV Read Only
Exhaust Fan Command Indicates the current exhaust fan command outputted from the system Read Only
Details: Load Shed Load Shed Rate Limit Determines the load shed rate limit Adjustable: 0 to 1°F/min
Load Shed Adjust Determines the load shed offset/adjust Adjustable: 0 to 8 delta °F
Load Shed Active Determines if the load shed functionality should be used Adjustable: No/Yes
Clone: Full Clone Device Name Determines the device name of the clone Adjustable
Unit Name Determines the name of the unit Adjustable
Unit Model Number Determines the model number of the clone Adjustable
Unit Serial Number Determines the serial number of the clone Adjustable
Model Name Determines the model name of the clone Read Only
Fan Accumulated Runtime Indicates how long the fan has been running. This value is adjustable; however should not be changed unless a software update requires it Adjustable: 0 to 10,000 hours
Compressor Stage Accumulated Runtime 1 Indicates the accumulated runtime for compressor stage 1. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Compressor Stage Accumulated Runtime 2 Indicates the accumulated runtime for compressor stage 2. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Compressor Stage Accumulated Runtime 3 Indicates the accumulated runtime for compressor stage 3. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Compressor Stage Accumulated Runtime 4 Indicates the accumulated runtime for compressor stage 4. This is how long the compressor has run since last power cycle Adjustable: 0 to 10,000 hours
Heating Stage 1 Accumulated Runtime The accumulated runtime for heating stage 1. This is how long the heating element has run since last power cycle Adjustable: 0 to 10,000 hours
Heating Stage 2 Accumulated Runtime The accumulated runtime for heating stage 2. This is how long the heating element has run since last power cycle Adjustable: 0 to 10,000 hours
Heating Stage 3 Accumulated Runtime The accumulated runtime for heating stage 3. This is how long the heating element has run since last power cycle Adjustable: 0 to 10,000 hours
Time Zone Determines which time zone the controller is using Adjustable: SE RTU Time Zone
Address Determines the IP address for the controller Adjustable: 4 to 127
Device OID (Device ID) Determines the Device ID of the controller Adjustable: 0 to 99,999
Clone: Partial Clone 1 Duct Pressure Setpoint Determines the Duct Pressure setpoint Adjustable: 0 to 5 in. wc.
Duct Pressure Shutdown Setpoint Determines the duct pressure shutdown setpoint. The fan will shutdown if this setpoint is hit. Adjustable: 0 to 5 in. wc.
Continuous Fan Operation in Occupied Mode Sets the control for Continuous Fan during Occupied for the clone Adjustable: Yes/No
Turn Off Continuous Fan Operation When Starting Heat Allows continuous fan mode to be turned off during heating mode Adjustable: Yes/No
Occupied : No Heat or Cool $ Command Indicates the occupied no heat/cool fan percent command for the clone Adjustable: 0 to 100%
Occupied : One Stage of Cool % Command Indicates the occupied first stage of cooling fan percent command for the clone Adjustable: 0 to 100%
Occupied: Two Stage of Cool % Command Indicates the occupied second stage of cooling fan percent command for the clone Adjustable: 0 to 100%
Occupied: Three Stage of Cool % Command Indicates the occupied third stage of cooling fan percent command for the clone Adjustable: 0 to 100%
Occupied: Four Stage of Cool % Command Indicates the occupied fourth stage of cooling fan percent command for the clone Adjustable: 0 to 100%
Occupied: One Stage of Heat % Command Indicates the occupied first stage of heating fan percent command for the clone Adjustable: 0 to 100%
Occupied: Two Stage of Heat % Command Indicates the occupied second stage of heating fan percent command for the clone Adjustable: 0 to 100%
Occupied: Three Stage of Heat % Command Indicates the occupied third stage of heating fan percent command for the clone Adjustable: 0 to 100%
VAV Cooling Supply Air Temp Upper Setpoint Determines the upper VAV cooling SAT setpoint Adjustable: 41 to 70°F
VAV Cooling Supply Air Temp Lower Setpoint Determines the lower VAV cooling setpoint Adjustable: 40 to 69°F
VAV Supply Air Temp Reset Setpoint Determines the SAT setpoint after reset Adjustable: 40 to 85°F
VAV Operating Cooling Supply Air Temp Setpoint Indicates the VAV Operating cooling SAT SP Read Only
CV Occupied Cooling Setpoint This is the Control Volume Occupied Cooling Setpoint Adjustable: 45 to 98°F
CV Unoccupied Cooling Setpoint This is the Control Volume Unoccupied Cooling Setpoint Adjustable: 46 to 99°F
VAV Occupied Heating Enabled Determines if VAV heating during occupied should be enabled Adjustable: No/Yes
VAV Occupied Heating Setpoint If enabled, determines the VAV occupied heating setpoint Adjustable: 40 to 85°F
Unoccupied Heating Enabled Determines if VAV heating during unoccupied is enabled Adjustable: No/Yes
VAV Unoccupied Heating Setpoint If enabled, determines the VAV unoccupied heating setpoint Adjustable: No/Yes
SZ VAV Occupied Cooling Setpoint This is the Single Zone Variable Air Volume Occupied Cooling Setpoint Adjustable: 45 to 98°F
SZ VAV Unoccupied Cooling Setpoint This is the Single Zone Variable Air Volume unoccupied Cooling Setpoint Adjustable: 45 to 98°F
Morning Warmup Enabled Determines if the morning warmup algorithm should be enabled Adjustable: No/Yes
Morning Warmup/Return Air Temp Setpoint If enabled, determines the warmup and return air temperature setpoints Adjustable: 50 to 85°F
CV Occupied Heating Setpoint The occupied heating setpoint when configured to individual setpoint mode Adjustable: 46 to 99°F
Clone: Partial Clone 1 (continued) CV Unoccupied Heating Setpoint The unoccupied setpoint when configured to individual setpoint mode Adjustable: 45 to 98°F
Low Ambient Economizer Setpoint Determines when the economizer should be enabled/disabled in low ambient conditions Adjustable: 0 to 60°F
Low Ambient Economizer Minimum Position Determines the economizer minimum position in low ambient conditions Adjustable: 0 to 100%
Language Sets the language the controller uses Adjustable: SE RTU Languages
Units Sets the units the controller uses Adjustable: IP/SI
BAS Communication Displays the current status of the BAS communication Read Only
Clone: Network Override Network Override Space Temperature Overrides the space temperature to what the user desires Adjustable: 0 to 100°F
Network Override Indoor Air Quality Overrides the indoor air quality to what the user desires Adjustable: 0 to 5,000 ppm
Network Override Zone Humidity Overrides the zone humidity to what the user desires Adjustable: 0 to 100% RH
Network Override Fan Request Overrides the fan request to what the user desires Adjustable: Off/On
Network Override Space Setpoint Offset Overrides the space temperature setpoint offset to what the user desires Adjustable: -5 to 5 delta °F
Network Override Outdoor Air Temperature Overrides the outdoor air temperature to what the user desires Adjustable: -50 to 125°F
Network Override Outdoor Air Humidity Overrides the outdoor air humidity to what the user desires Adjustable: 0 to 100% RH
Network Override Outdoor Air Quality Overrides the outdoor air quality to what the user desires Adjustable: 0 to 5000 ppm
Network Override Purge Command Overrides the purge command to what the user desires Adjustable: False/True
Self Test Results Fan Result The Fan results from the Self Test Read Only
C1 Result The Compressor 1 results from the Self Test Read Only
C2 Result The Compressor 2 results from the Self Test Read Only
C3 Result The Compressor 3 results from the Self Test Read Only
C4 Result The Compressor 4 results from the Self Test Read Only
H1 Result The Heating 1 results from the Self Test Read Only
H2 Result The Heating 2 results from the Self Test Read Only
H3 Result The Heating 3 results from the Self Test Read Only
Econ Result The Economizer results from the Self Test Read Only
Exhaust Result The Exhaust results from the Self Test Read Only
Trend: Status Network Override Network Override trend Read Only
Network Override Network Override trend Read Only
Cooling Status Cooling Status trend Read Only
Heating Status Heating Status trend Read Only
Economizer Status Economizer Status trend Read Only
Hot Gas Reheat Status Hot Gas Reheat Status trend Read Only
Operational Occupancy Operational Occupancy trend Read Only
Operational Space Temperature Operational Space Temperature trend Read Only
Supply Air Temperature Supply Air Temperature trend Read Only
Mixed Air Temperature Mixed Air Temperature trend Read Only
Operational Outdoor Air Temperature Operational Outdoor Air Temperature trend Read Only
Return Air Temperature Return Air Temperature trend Read Only
Outdoor Air Enthalpy Outdoor Air Enthalpy trend Read Only
Trend: Cooling: Status Cooling Status Cooling Status trend Read Only
Supply Air Temperature Supply Air Temperature trend Read Only
VAV Operating Cooling Supply Air Temp Setpoint VAV Operating Cooling Supply Air Temp Setpoint trend Read Only
CV Operating Cooling Setpoint CV Operating Cooling Setpoint trend Read Only
Trend: Cooling: Stage 1 Y1 - Thermostat The Y1 cooling call trend from the thermostat Read Only
Compressor Stage 1 Status The Status trend for Compressor Stage 1 Read Only
Compressor Stage Command 1 The Command trend from Compressor 1 Read Only
Trend: Cooling: Stage 2 Y2 - Thermostat The Y2 cooling call trend from the thermostat Read Only
Compressor Stage 2 Status The Status trend for Compressor Stage 2 Read Only
Compressor Stage Command 2 The Command trend from Compressor 2 Read Only
Trend: Cooling: Stage 3 Y3 - Thermostat The Y3 cooling call trend from the thermostat Read Only
Compressor Stage 3 Status The Status trend for Compressor Stage 3 Read Only
Compressor Stage Command 3 The Command trend from Compressor 3 Read Only
Trend: Cooling: Stage 4 Y4 - Thermostat The Y4 cooling call trend from the thermostat Read Only
Compressor Stage 4 Status The Status trend for Compressor Stage 4 Read Only
Compressor Stage Command 4 The Command trend from Compressor 4 Read Only
Trend: Heating: Status Heating Status Heating Status trend Read Only
Supply Air Temperature Supply Air Temperature trend Read Only
VAV Operating Heating Setpoint VAV Operating Heating Setpoint trend Read Only
CV Operating Heating Setpoint CV Operating Heating Setpoint trend Read Only
Trend: Heating: Stage 1 W1 - Thermostat The W1 heating call trend from the thermostat Read Only
Heating Stage Command 1 The Command trend for first stage of heating Read Only
Heating Stage 1 Enabled The Status trend for the first stage of heating Read Only
Trend: Heating: Stage 2 W2 - Thermostat The W2 heating call trend from the thermostat Read Only
Heating Stage Command 2 The Command trend for second stage of heating Read Only
Heating Stage 2 Status The Status trend for the second stage of heating Read Only
Trend: Heating: Stage 3 W3 - Thermostat The W3 heating call trend from the thermostat Read Only
Heating Stage Command 3 The Command trend for third stage of heating Read Only
Heating Stage 3 Status The Status trend for the third stage of heating Read Only
Trend: Fan: Indoor Fan G - Thermostat The G fan call trend from the thermostat Read Only
Fan Status The Fan Status trend from the indoor fan Read Only
Fan Command The Fan command trend from the indoor fan Read Only
Fan % Command The Fan % command trend from the indoor fan Read Only
Air Proving Switch The Air Proving switch trend from the indoor fan Read Only
Trend: Fan: Exhaust Fan Exhaust Fan Command Exhaust Fan Command trend Read Only
Exhaust Fan VFD % Command Exhaust Fan VFD % Command trend Read Only
Trend: Fan: Condenser Fans Condenser Fan 1 Condenser Fan 1 trend Read Only
Condenser Fan 2 Condenser Fan 2 trend Read Only
Trend: Sensors Space Temperature Input Space Temperature Input trend Read Only
Supply Air Temperature Supply Air Temperature trend Read Only
Mixed Air Temperature Mixed Air Temperature trend Read Only
Supply Air Humidity Supply Air Humidity trend Read Only
Operational Space Temperature Operational Space Temperature trend Read Only
Operational Indoor Air Quality Operational Indoor Air Quality trend Read Only
Operational Space Humidity Operational Space Humidity trend Read Only
Operational Outdoor Air Temperature Operational Outdoor Air Temperature trend Read Only
Operational Outdoor Air Quality Operational Outdoor Air Quality trend Read Only
Trend: Economizer Economizer Damper % Command Economizer Damper % Command trend Read Only
Econ Free Cooling Available Econ Free Cooling Available trend Read Only
Economizer Status Economizer Status trend Read Only
Return Air Enthalpy Return Air Enthalpy trend Read Only
Building Pressure Setpoint Building Pressure Setpoint trend Read Only
Building Static Pressure Building Static Pressure trend Read Only
Reversing Valve Reversing Valve trend Read Only
Trend: Misc: Hot Gas Reheat Hot Gas Reheat Command Hot Gas Reheat Command trend Read Only
Hot Gas Reheat Status Hot Gas Reheat Status trend Read Only
Hot Gas Reheat Humidity Setpoint Hot Gas Reheat Humidity Setpoint trend Read Only
Trend: Misc: Demand Ventilation Fresh Air Intake Setpoint Fresh Air Intake Setpoint trend Read Only
Fresh Air Intake Value Fresh Air Intake Value trend Read Only
Trend: Fault: Misc X-OUT X-OUT trend Read Only
Dirty Filter Switch Dirty Filter Switch trend Read Only
Trend: Fault: Heating Stage 1 Heat Limit1 Switch Heat Limit1 Switch trend Read Only
Heat Limit1 Switch Lockout Heat Limit1 Switch Lockout trend Read Only
Trend: Fault: Heating Stage 2 Heat Limit2 Switch Heat Limit2 Switch trend Read Only
Heat Limit2 Switch Lockout Heat Limit2 Switch Lockout trend Read Only
Trend: Fault: Heating Stage 3 Heat Limit3 Switch Heat Limit3 Switch trend Read Only
Heat Limit3 Switch Lockout Heat Limit3 Switch Lockout trend Read Only
Trend: Fault: Cooling Stage 1 High Pressure Limit High Pressure Limit trend Read Only
High Pressure Lockout High Pressure Lockout trend Read Only
Low Pressure Limit Low Pressure Limit trend Read Only
Low Pressure Lockout Low Pressure Lockout trend Read Only
Freeze Condition Freeze Condition trend Read Only
Freeze Condition Lockout Freeze Condition Lockout trend Read Only
Evaporator Coil Temp Evaporator Coil Temp trend Read Only
Condenser Coil Temp Condenser Coil Temp trend Read Only
Trend: Fault: Cooling Stage 2 High Pressure Limit High Pressure Limit trend Read Only
High Pressure Lockout High Pressure Lockout trend Read Only
Low Pressure Limit Low Pressure Limit trend Read Only
Low Pressure Lockout Low Pressure Lockout trend Read Only
Freeze Condition Freeze Condition trend Read Only
Freeze Condition Lockout Freeze Condition Lockout trend Read Only
Evaporator Coil Temp Evaporator Coil Temp trend Read Only
Condenser Coil Temp Condenser Coil Temp trend Read Only
Trend: Fault: Cooling Stage 3 High Pressure Limit High Pressure Limit trend Read Only
High Pressure Lockout High Pressure Lockout trend Read Only
Low Pressure Limit Low Pressure Limit trend Read Only
Low Pressure Lockout Low Pressure Lockout trend Read Only
Freeze Condition Freeze Condition trend Read Only
Freeze Condition Lockout Freeze Condition Lockout trend Read Only
Evaporator Coil Temp Evaporator Coil Temp trend Read Only
Condenser Coil Temp Condenser Coil Temp trend Read Only
Trend: Fault: Cooling Stage 4 High Pressure Limit High Pressure Limit trend Read Only
High Pressure Lockout High Pressure Lockout trend Read Only
Low Pressure Limit Low Pressure Limit trend Read Only
Low Pressure Lockout Low Pressure Lockout trend Read Only
Freeze Condition Freeze Condition trend Read Only
Freeze Condition Lockout Freeze Condition Lockout trend Read Only
Evaporator Coil Temp Evaporator Coil Temp trend Read Only
Condenser Coil Temp Condenser Coil Temp trend Read Only
Trend: Diagnostics: Cooling Stage 1 Suction Pressure Suction Pressure trend Read Only
Liquid Pressure Liquid Pressure trend Read Only
Suction Temperature Suction Temperature trend Read Only
Liquid Temperature Liquid Temperature trend Read Only
Superheat Superheat trend Read Only
Subcooling Subcooling trend Read Only
Condensing Temperature over Ambient Condensing Temperature over Ambient trend Read Only
Efficiency Index Efficiency Index trend Read Only
Capacity Index Capacity Index trend Read Only
Trend: Diagnostics: Cooling Stage 2 Suction Pressure Suction Pressure trend Read Only
Liquid Pressure Liquid Pressure trend Read Only
Suction Temperature Suction Temperature trend Read Only
Liquid Temperature Liquid Temperature trend Read Only
Superheat Superheat trend Read Only
Subcooling Subcooling trend Read Only
Condensing Temperature over Ambient Condensing Temperature over Ambient trend Read Only
Efficiency Index Efficiency Index trend Read Only
Capacity Index Capacity Index trend Read Only
Trend: Diagnostics: Cooling Stage 3 Suction Pressure Suction Pressure trend Read Only
Liquid Pressure Liquid Pressure trend Read Only
Suction Temperature Suction Temperature trend Read Only
Liquid Temperature Liquid Temperature trend Read Only
Superheat Superheat trend Read Only
Subcooling Subcooling trend Read Only
Condensing Temperature over Ambient Condensing Temperature over Ambient trend Read Only
Efficiency Index Efficiency Index trend Read Only
Capacity Index Capacity Index trend Read Only
Trend: Diagnostics: Cooling Stage 4 Suction Pressure Suction Pressure trend Read Only
Liquid Pressure Liquid Pressure trend Read Only
Suction Temperature Suction Temperature trend Read Only
Liquid Temperature Liquid Temperature trend Read Only
Superheat Superheat trend Read Only
Subcooling Subcooling trend Read Only
Condensing Temperature over Ambient Condensing Temperature over Ambient trend Read Only
Efficiency Index Efficiency Index trend Read Only
Capacity Index Capacity Index trend Read Only
Set Schedule Occupancy Schedule The set occupancy schedule determined in system configuration Read Only
Table 2. VZC100 parameters and objects
Menu Object or parameter Description Adjustable
Home Page Fan Status This is the fan status of the change over bypass or VAV unit that is suppling air to the zones. Read only
Supply Air Temperature This is the SAT of the change over bypass or VAV unit that is suppling air to the zones. Read only
Unit Status This is the unit status of the change over bypass or VAV unit that is suppling air to the zones. Read only
Zone Temperature This is the zone temperature of the zone(s) connected to the zone coordinator. The list shows each zone temperature of each zone connected. Read only
Zone Vote This is the vote sent from the COBP systems to the zone coordinator from the connected zones. The vote is for either Urgent Heat, Heat, Satisfied, Cool or urgent Cool. The zone coordinator determines what state the unit controls to based on all of the votes from the zones. Read only
Zone Can Vote In COBP systems, this parameter indicates if the zone is currently allowed to vote. This parameter shows false if a zone is locked out from voting by a manual setting or because it cannot reach the temperature within the Lockout Time. Read only
Active Mode On VAV systems, this is the current state the zone is in. Heating, Cooling or Satisfied. Each zone shows their mode. Read only
Firmware Main Version Displays the firmware version for the given zone controller. The list shows this parameter for each connected zone controller. Read only
Application Version Displays the application version for the given zone controller. The list shows this parameter for each connected zone controller. Read only
Application Name Displays the application name for the given zone controller. It can be Verasys Incremental Heating Application, Verasys Staged Heating Application, Verasys SCR Heating Application, or Verasys Zone Damper Application. The list shows this parameter for each connected zone controller. Read only
Unit Unit Enable With this object you can command the RTU to shut down. This will shut down all of the zones. Adjustable: Enable/Shutdown
Network Temporary Occupancy Request If any zone associated with a group is in a temporary occupancy state this flags as true. The temporary occupancy command is then sent to that group for the length of the temporary occupancy timeout. Adjustable: False/True
Operational Occupancy Effective occupancy status of a group Read only
Temporary Occupancy Timeout The duration of a temporary occupancy request. This value is sent to the rooftop unit controller when adjusted. Adjustable: 30 min to 480 min
Representative Zone On VAV systems this is the zone that represents night setup and setback zone. You can use this to reset the SAT if it is enabled. Adjustable: Range: 46°F to 99°F
Load Shed Active The status of the load shed command to the zone coordinator. When active, all zones are in load shed if the zones are enabled for load shed. Read only
Zoning System State This is a trouble shooting object that identifies missing rooftop units, or unsupported rooftop units, a bypass damper when it is not needed, or an unsupported zone. Read only
Device Being Provisioned While performing a VZC100 update, this menu parameter indicates the device that is currently being provisioned and can be either the VZC or one of the ZECs connected on the zone bus. When no update is in process, this parameter is empty. Read only
Provisioning Command Provides a high level description of the state of the provisioning. Read only
Provisioning Detail Code Provides a detailed description of the state of the provisioning. Read only
Provisioning Error Code Indicates if there was an error with provisioning. Read only
Provisioning Status Shows the status of provisioning. Read only
System Package Mismatch Information Indicates if the current version of any of the ZECs or the VZC do not match the expected package version. Most often this occurs when an older ZEC is connected to a newer VZC. The red fault LED on the VZC slowly blinks while in a mismatch state. Read only
Commissioning Control Mode Sets the mode of the unit RTU or VAV/COBP unit. Adjustable:
  • Auto

  • Cool

  • Heat

  • Fan Only

  • Off

Balancer Mode When initiated, zone dampers index to their maximum positions, VAV boxes index to their cooling maximum flow positions and the bypass damper closes. Adjustable: Enable/Disable
Title 24 Test Mode When you are in title 24 test mode, the economizer damper ramp rate drops from 5% every 30 minutes to 5% every two minutes, so you can test the demand ventilation mode sequence faster. This does not test the Title 24 load shed. Adjustable: False/True
Construction Mode Sets the mode of the unit during construction. This ignores typical shutdown conditions. Use this feature to temper the space during construction. Only available during change over bypass. Also make sure zone dampers are blocked open when you run the unit in construction mode to relieve duct pressure. Adjustable:
  • Not in Use

  • Heat

  • Cool

  • Fan Only

Controller Firmware Version Displays the firmware version of the controller. Read only
Relearn System Alerts the zone coordinator to rediscover all of the devices that are connected to the zone bus.
Note: Only applicable when VZC firmware version is 4.x or greater.
Adjustable: False/True
Address Shows the address of the controller. The address is set by the dip switches on the controller. Read only
Device OID This is the BACnet device OID for the system bus. If on a standalone Verasys System this parameter is not used, but if connected to a 3rd party facility management system it sets the BACnet ID for the zone coordinator. Adjustable: Range: 1 to 4,194,303
Time The time that was set by the SBH. To change the date and time, navigate to settings > systems on the SBH and adjust the date and time. This adjustment syncs to all online devices. Read only
Date Shows the date that the controller is set to. Read only
Details: Setpoints Supply Temperature Cooling Setpoint On change over bypass systems, this is the setpoint the RTU controls to when the system calls for cooling. Adjustable: 40°F to 69°F
Supply Temperature Heating Setpoint On change over bypass systems, this is the setpoint the RTU controls to when the system calls for heating. Adjustable: 90°F to 130°F
Supply Air Temperature Setpoint On VAV systems, if the supply air temp reset strategy is set to true, this is the setpoint the RTU controls to. Adjustable: 40°F to 70°F
Maximum Supply Temp Setpoint Adjust On VAV systems, if the supply air temp reset strategy is set to true, this is the maximum adjustment the of the supply air setpoint plus or minus what it is set to. Adjustable: 0°F to 5°F
Duct Pressure Setpoint On VAV systems, if the duct static setpoint reset strategy is set to true, this is the setpoint the RTU controls to. Adjustable: 0.5 in. wc to 4.5 in. wc
Max Duct Static SP Adjust On VAV systems, if the duct static setpoint reset is set to true, this is the maximum adjustment of the duct pressure setpoint plus or minus what it is set to. Adjustable: 0 in. wc to 0.5 in. wc
Economizer Minimum Position Setpoint Sets the economizer minimum position if the economizer is installed on the unit. Adjustable: 0% to 100%
Details: Control Supply Temp Reset Strategy On VAV Systems, if set to true the zone coordinator resets the SAT based on the zone that is set as the representative zone. If the zone is providing as much cooling as it can, it adjusts the SAT down towards the supply air setpoint minus maximum SAT adjust. If the zone is satisfied it adjusts the SAT up towards the supply air setpoint plus maximum SAT adjust. Adjustable: Enable/Disable
Duct Static Setpoint Reset Enable On VAV Systems, if set to true the zone coordinator resets the duct static pressure setpoint based on the zone that has the most open damper trying to control it between 85% and 95% open. If the zone is less than 85% it adjusts the duct pressure down. If the zone is greater than 95% it adjusts the duct pressure up. Using the Max Duct Static setpoint adjust to set the limits. Adjustable: Enable/Disable
Unocc Heating Cooling Enable On VAV systems, this enables the night setup and setback of the unit based on the conditions of the representative zone. Adjustable: Enable/Disable
VFD Econ Min Pos Reset On VAV Systems, the VFD economizer minimum position reset strategy adjusts the economizer minimum position proportional to the supply fan speed to maintain the outdoor ventilation rate. Adjustable: False/True
Details: Changeover Min Requests to Change The system changes from heat to cool when the cooling requests exceeds the minimum number of requests to change modes and all heating requests have been satisfied below this value. The system changes from cool to heat when the heating requests exceeds the minimum number of requests to change modes and all cooling requests have been satisfied below this value. Adjustable: 1 to 4
Min Urgent Requests to Change The system changes from heat to cool when the urgent cooling requests exceeds the minimum number of urgent requests to change modes. The system changes from cool to heat when the urgent heating requests exceeds the minimum number of urgent requests to change modes. Adjustable: 1 to 4
Urgent Heat Requests Number of zones with urgent requests for heat. Ready only
Total Heat Requests Number of zones with requests for heat. A combination of urgent and regular requests. Ready only
Urgent Cool Requests Number of zones with urgent requests for cooling. Ready only
Total Cool Requests Number of zones with requests for cooling. A combination of urgent and regular requests. Ready only
Changeover Min Time A user-set timer prevents cycling between the heat and cool modes. The timer begins running when it enters either the heat or cool mode. Once it expires, the system may change modes if the other conditions are met. The timer restarts when the mode changes. Adjustable: 10 min to 60 min
Changeover State The current state of the changeover timer Read only
Table 3. BYP200 parameters and objects
Menu Object or Parameter Description Adjustable
Home Page Duct Static Pressure The Duct Static Pressure reading from the differential pressure sensor. Read only
Duct Static Pressure Setpoint This is the setpoint the controller is modulating the bypass damper(s) to. Adjustable: 0 in. wc to 5.0 in. wc
Damper Position The commanded position of the bypass damper(s). Read only
Unit Enable The command given to the bypass damper by the zone coordinator. Adjustable: Enable/Shutdown
Setup Duct Pressure Setpoint This is the setpoint the controller is modulating the bypass damper(s) to. Adjustable: 0 in. wc to 5.0 in. wc
Damper Maximum Position Sets the maximum position the damper moves to. Adjustable: Range 0% to 100%
Heat Cool Mode Shows what state the unit is in. Heating, Cooling, Fan Only, Balancing, Satisfied or Off. Read only
Unit Enable The command given to the bypass damper by the zone coordinator. Adjustable: Enable/Shutdown
Damper Direction to Close Sets the direction to close the bypass damper that is a part of the controller. To set the second bypass damper direction you must set a jumper on the actuator. Adjustable: clockwise/counter clockwise
Power Fail Restart Enable Upon a power fail the controller delays 5 minutes before it comes back operational. This is done so electrical demand is not spiked. Adjustable: Enable/Disable
Controller Firmware Version Displays the firmware version of the controller. Read only
Address Shows the address of the controller. The address is set by the dip switches on the controller. Read only
Unit Model Number Shows the model number of the controller. Read only
Trends Duct Static Pressure 288 samples are taken at a 15 minute period. Read only
Scheduled Occupancy 10 samples in total. 1 sample taken every change of value. Read only
Damper Position 288 samples are taken at a 15 minute period. Read only
Table 4. ZEC510 objects and parameters
Menu Object or Parameter Description Adjustable
Home Page Zone Temperature Zone temperature reading from the zone sensor. Read only
Effective Heating Setpoint This is the actual calculated heating setpoint the zone controls to based on occupancy and the warmer/cooler adjustment applied from the NS8000 sensor. Read only
Effective Cooling Setpoint This is the actual calculated cooling setpoint the zone controls to, taking into account occupancy and the warmer/cooler adjustment applied from the NS8000 sensor. Read only
Operational Occupancy This is the commanded occupancy from the zone coordinator. The zone is either in an occupied, unoccupied or standby state. Temporary occupancy can switch this from unoccupied to occupied. If a motion sensor is connected and motion is not sensed it switches to standby. Read only
Active Mode This is the current state the box is in. Heating, Cooling, Satisfied or Temperature Unreliable. This object only shows up on VAV systems. Read only
Zone Vote This is the vote sent to the zone coordinator. The zone votes for either Urgent Heat, Heat, Satisfied, Cool or urgent Cool. The zone coordinator determines what state the unit controls to based on all of the votes from the zones. This object only shows up on change over bypass systems. Read only
Network Override Supply Air Temperature This is the supply air temperature as measured by the RTU/AHU and shared over the network to the ZEC through the VZC100. Read only
Damper Position The commanded position of the zone damper. Read only
Discharge Air Temperature This is the temperature of the air that leaves the VAV box. The discharge air temperature sensor is typically installed to measure the heat rise of the box heater. This parameter is only visible if DA-T sensor is installed. Read only
Supply Flow The supply air flow measured by the VAV box. Read only
Supply Flow Setpoint The flow setpoint the damper is controlling the supply air flow to. Read only
Indoor Air Quality This is the measurement of CO2 in the space. If it is too high, the system drives more fresh air into the space. This parameter is only visible if CO2 sensor is installed. Read only
Fan Command The VAV box fan command. This parameter is only visible if ZEC is set up for fan. Read only
Heating Stage Command 1 The first stage of heating command.
Note: This parameter is visible if you use staged or proportional SCR heat. If you use proportional SCR heat, this parameter shows whether SCR heat is enabled.
Read only
Heating Stage Command 2 The second stage of heating command.
Note: This parameter is visible if ZEC is configured for two stages of heat.
Read only
Heating Stage Command 3 The third stage of heating command.
Note: This parameter is visible if ZEC is configured for three stages of heat.
Read only
Box Heating Status This parameter shows when the box heating is able to activate based on when supply flow is greater than stage reheat minimum flow setpoint. Read only
Supplemental Heating Stage Command The supplemental heating stage command.
Note: This parameter is visible if you use staged heat.
Read only
Home Page (continued) Heating Percent Command The box heating percent command.
Note: This parameter is visible when control application type is set to incremental or proportional SCR heat.
Read only
Supplemental Heating Percent Command The supplemental heating percent command.
Note: This parameter is visible when control application type is set to incremental or proportional SCR heat.
Read only
Temp Occ Temporary Occupancy. If enabled, any adjustment to the zone sensor during the unoccupied mode places the zone in the occupied state and this parameter sets to true. The Network Temporary Occupancy Request parameter also sets to true, and the unit starts and runs for the temporary occupancy duration. Read only
Ventilation Request Indicates whether the zone CO2 level is currently higher than the setpoint and the zone needs additional ventilation. Read only
Box Heating Type Shows the type of heat installed in the VAV box. Read only
Supplemental Heating Type Shows the type of heat installed for supplemental or perimeter heat. Read only
Cooling PID Saturation Status Overview of the cooling PID loop status. A normal status indicates that cooling can occur at any time or cooling is currently on. The timing high status indicates that the output is at 100%, and the high status indicates 100% for more than five minutes. Over-ridden means cooling is inactive. Read only
Heating PID Saturation Status Overview of the heating PID loop status. A normal status indicates that heating can occur at any time or heating is currently on. The timing high status indicates that the output is at 100%, and the high status indicates 100% for more than five minutes. Over-ridden means cooling is inactive. Read only
Setpoints Occupied Cooling Setpoint When occupied the thermostat controls cooling to this level. Set above occupied heating setpoint. Defaults to 72°F. Adjustable: 46°F to 99°F
Occupied Heating Setpoint When occupied the thermostat controls heating to this level. Set below occupied cooling setpoint. Defaults to 68°F. Adjustable: 45°F to 98°F
Unoccupied Cooling Setpoint When unoccupied the thermostat controls cooling to this level. Defaults to 80°F. Adjustable: 46°F to 99°F
Unoccupied Heating Setpoint When unoccupied the thermostat controls heating to this level. Set below unoccupied cooling setpoint. Defaults to 60°F. Adjustable: 45°F to 98°F
Standby Cooling Setpoint In order for the standby cooling setpoint to appear, set the occupancy mode to external. When set to external the zone switches to this setpoint when motion is no longer sensed and the unit is occupied. Defaults to 74°F. Adjustable: 46°F to 99°F
Standby Heating Setpoint In order for the standby Heating setpoint to appear, set the occupancy mode to external. When set to external, the zone switches to this setpoint when motion is no longer sensed and the unit is occupied. Defaults to 66°F. Adjustable: 45°F to 98°F
Supply Air Temperature Setpoint When the space temperature drops below the heating setpoint, the zone controller starts from the supply air temperature setpoint and resets to the supply air setpoint heating Max. Once the Heating Max setpoint is reached the supply air flow resets from heating minimum flow to cooling maximum flow. Adjustable: 45°F to 130°F
Warmer/Cooler Adjust Range This is the range that the warmer cooler adjustment on the zone sensor can affect the setpoint. Setting it to zero means the user has no adjustment at the sensor. Default is 5°F Adjustable: 0°F to 5°F
Warmup Diff This parameter indicates the amount with which the supply temperature must exceed the current zone temperature so that the controller detects a warmup condition. Adjustable: -25 delta °F to 100 delta °F
Commissioning: Flow Cooling Maximum Flow Sets the maximum supply air flow of the VAV box when cooling. This flow is also used if the ZEC is in warmup mode, this occurs when the network override supply air temperature is greater than the zone temperature plus warmup differential and the ZEC calls for heat. Adjustable: 0 cfm to 10,000 cfm
Occupied Cooling Min Flow Sets the minimum supply air flow of the VAV box when cooling. Adjustable: 0 cfm to 10,000 cfm
Occupied Heating Min Flow Sets the minimum supply air flow of the VAV box when heating.
Note: When the zone is in heating mode, the supply air flow is constant. Thus, no maximum heating air flow.
Adjustable: 0 cfm to 10,000 cfm
Unoccupied Cooling Min Flow Sets the minimum supply air flow of the VAV box when unoccupied cooling and in the cooling mode. Adjustable: 0 cfm to 10,000 cfm
Unoccupied Heating Min Flow Sets the minimum supply air flow of the VAV box when unoccupied heating and in the heating mode. Adjustable: 0 cfm to 10,000 cfm
Warmup Min Flow During warmup mode this is the minimum flow to the VAV box. If the box does not call for heat, the box controls to this minimum flow setpoint. Adjustable: 0 cfm to 10,000 cfm
Staged Reheat Min Flow Sets the minimum heating flow for electric box reheat control. This parameter serves an additional control safety to the high-limit switches in the box. It is best practice to set this parameter to 70 cfm per kW of electric heat. Adjustable: 0 cfm to 10,000 cfm
DCV Max Flow The DCV maximum ventilation flow. As determined by the CO2 setpoint and proportional band, this is the maximum flow the DCV is set to. For example, if this is set to 700cfm and the controller is requiring maximum ventilation as determined by the DCV sequence, the system controls to 700cfm. However, if the system requires more flow because of temperature control, the flow setpoint may increase to the occupied cooling maximum flow setpoint in this section. Adjustable: 0 cfm to 10,000 cfm
DCV Occupied Cooling Min Flow While in demand control ventilation (CO2 Control) the minimum cooling supply air flow starts with this and span to the DCV maximum flow. Adjustable: 0 cfm to 10,000 cfm
DCV Occupied Heating Min Flow While in demand control ventilation (CO2 Control) the minimum heating supply air flow starts with this and span to the DCV maximum flow. Adjustable: 0 cfm to 10,000 cfm
Supply Flow Shows the supply air flow measured by the VAV box. Read only
Supply Flow Setpoint Shows the flow setpoint the damper is controlling the supply air flow to. Read only
Supply Area Shows the supply inlet area used to calculate the supply flow. Adjustable: 0 sq. ft. to 8.0 sq. ft.
Pickup Gain Shows the K factor for the box. Also used to adjust and calibrate the flow. Adjustable: 0.1 to 9.9
Velocity Pressure Shows the velocity pressure sensed by the VAV box. Read only
Auto Calibration Command This feature drives the VAV box damper shut and when it is shut, it offsets the differential pressure sensor so that it reads zero. Adjustable: False/True
Auto Calibration Status The current status of the automatic calibration mode. Read only
Auto Calibration Offset The resulting offset of the differential pressure sensor after an automatic calibration. Read only
Commissioning: Load Shed Load Shed Adjust This sets how the setpoint moves when a load shed command is issued. For example, if the Occupied Cooling Setpoint is 72°F, the cooling setpoint moves towards 76°F if the adjustment is set to four. If the Occupied Heating Setpoint is 70°F, the heating setpoint moves towards 66°F. Adjustable: 0°F to 8°F
Load Shed Rate Limit This sets the rate at which the controller adjusts the setpoint until it hits the load shed adjust. Adjustable: 0 to 1°F/min
Load Shed Allowed Enables the user to remove zones from the load shed command. Set this to false and the zone is removed from a load shed. Adjustable: False/True
Load Shed Active Shows the current command for a load shed event. Read only
Commissioning: DCV Demand Ventilation Indoor Air Quality Setpoint Sets the point where the CO2 level starts demand control ventilation. Above this level the zone switches to DCV and starts using the DCV positions. When you exceed this limit it issues a DCV call to the rooftop unit if DCV is enabled on the RTU. Adjustable: 0 ppm to 5,000 ppm
Indoor Air Quality Prop Band Sets the rate at which the damper goes from minimum to maximum position. For example: If set at 400ppm and the indoor air quality setpoint is at 700ppm, the sensor needs to reach 1100ppm in order for the maximum position to be set. The controller proportionally opens until it reaches that point. Adjustable: 0 ppm to 1,000 ppm
Ventilation Timer This timer starts when you fall below the demand ventilation indoor air quality setpoint and after this time expires, the DCV call to the rooftop unit expires and goes back to economizer minimum position. Adjustable: 5 min to 30 min
Control Setup Active Mode Shows the current mode of the system. Adjustable: Cool Only/Heat Only/Fan Only/Purge/Auto
Control Application Type This parameter sets the type of box heating installed.
Important: When you change this parameter, the controller reboots and all other parameter settings are lost.
Adjustable: Incremental/Staged/Proportional SCR
Unit Enable Enables or shuts down the zone control. Adjustable: Enable/Shutdown
Power Fail Restart Enable When the power fails, the controller delays the amount of time defined in Power Fail Restart Time before it comes back operational. This is done so electrical demand is not spiked. Adjustable: Enable/Disable
Warmer/Cooler Adjust Enable Enables the warmer/cooler adjustment on the NS8000 to offset the effective heating/cooling setpoint. Adjustable: False/True
DCV Enable When set to CO2 the DCV section in commissioning appears and a CO2 sensor, when connected, controls the zone damper to add more ventilation when the CO2 demand increases above setpoint. Adjustable: None/CO 2
Temp Occ Enable Temporary Occupancy. If enabled, any adjustment to the zone sensor during the unoccupied mode places the zone in the occupied state and this parameter sets to true. In addition the zone coordinators Network Temporary Occupancy Request parameter sets to true and the unit starts and run for the temporary occupancy duration. Setting the parameter to disable does not allow this function to take place for this zone. Adjustable: Enable/Disable
Zone Weight Enables the user to increase the importance of a zone. For example, if zone weight is set to three, it counts the vote of the zone three times as much than a zone set to one. This parameter only shows up on COBP systems. Adjustable: 0 to 3
Zone Vote Allowed Enables the user to remove a zone from voting. This parameter only shows up on change over bypass systems. Adjustable: False/True
Lockout Enable This parameter enables or disables the rogue zone logic that takes a zone out of voting if it remains far away from the setpoint for too long. Adjustable: Disable/Enable
Lockout Time If the zone stays 3°F away from temperature setpoint for this duration, the zone is removed from the voting until the zone gets back in range is satisfied at some point. Adjustable: 15 min to 90 min
Occupancy Mode When set to Schedule the zone switches occupancy state, using the occupancy schedule of the zone coordinator only. When set to External, the controller reads the occupancy sensor contact and toggle between occupancy setpoints and standby setpoints during occupied mode of the schedule. When the schedule is unoccupied the unit switches to unoccupied setpoint and turns off. Adjustable: External/Schedule
Auto Tuning Enable Allows PRAC+ auto tuning algorithm to continuously tune the loops in the controller. Setting this to Disable turns off this feature. Adjustable: Enable/Disable
Control Setup (continued) PID Tuning Reset Resets the PRAC+ tuning to the default values. Adjustable: Enable/Disable
Power Fail Restart Time Use this parameter to set how long the control remains idle before starting after a power loss. Adjustable: 30 s to 600 s
Standalone Mode Use this parameter to set whether the controller is in standalone mode and determines occupancy based on flow, or it is connected to a BAS. If the ZEC is connected to a zone coordinator as part of a Verasys zoning system, set standalone mode to off. Adjustable: Off/On
Occ Min Flow 1 Use this parameter in standalone mode to set the minimum expected flow when the RTU or AHU is running. The box flow must be greater than this parameter for the ZEC to switch to occupied mode. Adjustable: 0 cfm to 1,000 cfm
SAT Limit Control Use this parameter to enable the checking of supply air that enters the VAV box and to disable box heating if the supply air temperature exceeds the setpoint. Adjustable: False/True
High SAT Limit Setpoint Configure this setpoint when you enable SAT limit control. If the supply air temperature exceeds this setpoint, box heating is disabled because the RTU or AHU already supplies hot air. Adjustable: 50°F to 150°F
Zone Group Number Use this parameter to indicate to the VZC100 the group schedule that this zone follows. You can choose from four independent schedules. Adjustable: 1 to 4
Equipment Setup Min Valve Position Use this parameter to set the position of the heating valve when no heat is needed.
Note: This parameter is used when control application type is set to proportional SCR heat.
Adjustable: 0% to 100%
Max Valve Position Use this parameter to set the position of the heating valve when maximum heat is needed.
Note: This parameter is used when control application type is set to proportional SCR heat.
Adjustable: 0% to 100%
Box Heating Stroke Time Sets the actuator stroke time for the incremental heating valve.
Note: This parameter is used when control application type is set to incremental.
Adjustable: Range: 30 s to 120 s
Supplemental Heating Stroke Time Sets the actuator stroke time for the incremental supplemental heating valve.
Note: This parameter is used when control application type is set to incremental.
Adjustable: Range: 30 s to 120 s
Actuator Stroke Time Sets the damper actuator stroke time.
Note: The ZEC510 actuator is a 60-second motor.
Adjustable: Range: 30 s to 120 s
Damper Direction to Close Sets the direction to close the zone damper. Adjustable: clockwise/counter clockwise
Box Heating Polarity Reverses the direction of the incremental heating valve. You can either switch this or reverse the wiring to the actuator. Adjustable: Normal/Reverse
Supplemental Heating Polarity Reverses the direction of the incremental supplemental heating valve. You can either switch this or reverse the wiring to the actuator. Adjustable: Normal/Reverse
Number of Heating Stages Installed Sets the number of box heating stages. Adjustable: 0 - 3
Fan Control Type Sets the type of fan for the VAV Box. Adjustable:
  • None

  • Parallel

  • Series

SAT Offset Used to calibrate the supply air temperature sensor. This is only available if a SAT sensor is connected to input-3. Adjustable: -5°F to 5°F
ZNT Sensor Offset Used to calibrate the zone temperature sensor. Adjustable: -5°F to 5°F
CO 2 Altitude Compensation Altitude compensation used to calibrate the Netstat CO2 sensor. Adjustable: 700 hPa to 1,200 hPa
IAQ Offset Used to Calibrate the CO2 Sensor. Only used for hardwired CO2 sensors not Netstat. Adjustable: -250 ppm to 250 ppm
Heating Priority Use this parameter to set whether to use box heat or supplemental heat first when both are installed. Adjustable: Box/Supplemental
Heating Stage Command 1 Polarity Use this parameter to set the output action to either normally open or normally closed for heating stage 1.
Note: This parameter is used when control application type is set to staged.
Adjustable: Normal/Reverse
Heating Stage Command 2 Polarity Use this parameter to set the output action to either normally open or normally closed for heating stage 2.
Note: This parameter is used when control application type is set to staged.
Adjustable: Normal/Reverse
Heating Stage Command 3 Polarity Use this parameter to set the output action to either normally open or normally closed for heating stage 3.
Note: This parameter is used when control application type is set to staged.
Adjustable: Normal/Reverse
Controller Firmware Version Displays the firmware version of the controller. Read only
Application Version This string indicates the build number for the current application. Read only
Application Name This string indicates the name of the application that is loaded on the controller. Read only
Address Shows the address of the controller. The address is set by the dip switches on the controller. Read only
Unit Model Number Shows the model number of the controller. Read only
Trends Zone Temperature 288 samples are taken at a 15 minute period. Read only
Indoor Air Quality 288 samples are taken at a 15 minute period. Read only
Supply Air Temperature 288 samples are taken at a 15 minute period. Read only
Heating Percent Command 288 samples are taken at a 15 minute period. Read only
Supplemental Heating Percent Command 288 samples are taken at a 15 minute period. Read only
Heating Stage Command 1 10 samples total. 1 sample taken every change of value. Read only
Heating Stage Command 2 10 samples total. 1 sample taken every change of value. Read only
Fan Command 10 samples total. 1 sample taken every change of value. Read only
Supplemental Heating Stage Command 10 samples total. 1 sample taken every change of value. Read only
Supply Flow 288 samples are taken at a 15 minute period. Read only
Note: In order for the Commissioning: DCV tab to appear, you must set the DCV Enable parameter to CO2.
Table 5. ZEC310 parameters and objects
Menu Object or Parameter Description Adjustable
Home Page Zone Temperature Zone temperature reading from the zone sensor. Read only
Active Setpoint This is the setpoint the zone is controlling to taking into account occupancy and the warmer/cooler adjustment. Read only
Operational Occupancy This is the commanded occupancy from the zone coordinator. The zone is either in an occupied, unoccupied or standby state. Temporary occupancy can switch this from unoccupied to occupied. If a motion sensor is connected and motion is not sensed, it switches to standby. Read only
Zone Vote This is the vote sent to the zone coordinator. The vote is either for Urgent Heat, Heat, Satisfied, Cool or urgent Cool. The zone coordinator determines what state the unit controls to, based on all of the votes from the zones. Read only
Damper Position The commanded position of the zone damper. Read only
Temp OCC Temporary Occupancy. If enabled, any adjustment to the zone sensor during the unoccupied mode places the zone in the occupied state and this parameter sets to true. In addition the zone coordinators Network Temporary Occupancy Request parameter sets to true and the unit starts and run for the temporary occupancy duration. Read only
Warmer/Cooler Adjustment The output value of the adjustment applied by the operator at the zone sensor. The range of this adjustment is set by the warmer/cooler adjustment range parameter. Read only
Damper Mode Indicates the mode of the zone damper. It can be heating, cooling, satisfied, or temperature unreliable. Read only
Network Override Supply Air Temperature This is the supply air temperature as measured by the RTU and shared over the network to the ZEC through the VZC100. Read only
Ventilation Request

Indicates whether the zone CO2 level is currently higher than the setpoint and the zone needs additional ventilation.

Note: This point is only visible if DCV enable is set to CO2.
Read only
Heating PID Saturation Status This parameter indicates the status of the PID loop for heating. Normal indicates normal control, timing high is when the heating loop is at 100% and high is when the loop is at 100% for more than 5 minutes. Over-ridden means heating is inactive. Read only
Cooling PID Saturation Status This parameter indicates the status of the PID loop for cooling. Normal indicates normal control, timing high is when the cooling loop is at 100% and high is when the loop is at 100% for more than 5 minutes. Over-ridden means cooling is inactive. Read only
Setpoints Occupied Cooling Setpoint When occupied, the thermostat controls cooling to this level. Set above occupied heating setpoint. Defaults to 72°F. Adjustable: 46°F to 99°F.
Occupied Heating Setpoint When occupied, the thermostat controls heating to this level. Set below occupied cooling setpoint. Defaults to 68°F. Adjustable: 45°F to 98°F
Unoccupied Cooling Setpoint When unoccupied, the thermostat controls cooling to this level. Defaults to 80°F. Adjustable: 46°F to 99°F
Unoccupied Heating Setpoint When unoccupied, the thermostat controls heating to this level. Set below unoccupied cooling setpoint. Defaults to 60°F. Adjustable: 45°F to 98°F
Standby Cooling Setpoint In order for the standby cooling setpoint to appear, set the occupancy mode to external. When set to external, the zone switches to this setpoint when motion is no longer sensed and the unit is occupied. Defaults to 74°F. Adjustable: 46°F to 99°F
Standby Heating Setpoint In order for the standby heating setpoint to appear, set the occupancy mode to external. When set to external, the zone switches to this setpoint when motion is no longer sensed and the unit is occupied. Defaults to 66°F. Adjustable: 45°F to 98°F
Warmer/Cooler Adjust Range This is the range that the warmer cooler adjustment on the sensor can affect the setpoint. Setting it to zero means the user has no adjustment at the sensor. Default is 3°F. Adjustable: 0°F to 5°F
Commissioning: Flow Damper Cooling Min Position Sets the minimum position that the damper adjust to when the damper is cooling. Default is 50%. Adjustable: 0% to 100%
Damper Heating Min Position Sets the minimum position that the damper adjusts to when the damper is heating. Default is 50%. Adjustable: 0% to 100%
Damper Max Position This sets the maximum that the damper can open. Use this to reduce flow or noise. Default is 100%. Adjustable: 0% to 100%
Damper Satisfied Min Position Sets the minimum position that the damper adjusts to when the damper is satisfied. Default is 10%.  
Commissioning: Title 24 Load Shed Load Shed Adjust The sets how the setpoints move when a load shed command is issued. For example, if the Occupied Cooling Setpoint is 72°F the cooling setpoint moves towards 76°F if the adjustment is set to four. If the Occupied Heating Setpoint is 70°F the heating setpoint moves towards 66°F. Adjustable: 0°F to 8°F
Load Shed Rate Limit This sets the rate at which the controller adjusts the setpoint until it hits the load shed adjust. Adjustable: 0 to 1°F/min
Load Shed Allowed The user can remove zones from the load shed command. Set this to false and the zone is removed from a load shed. Adjustable: False/True
Load Shed Active Shows the current command for a load shed event. Read only
Commissioning: DCV Demand Ventilation Indoor Air Quality Setpoint Sets the point where the CO2 level starts demand control ventilation. Above this level the zone switches to DCV and starts using the DCV positions. When you exceed this limit it issues a DCV call to the rooftop unit if DCV is enabled on the RTU. Adjustable: 0 ppm to 5,000 ppm
Indoor Air Quality Prop Band Sets the rate at which the damper goes from minimum to maximum position. Example: If set at 400ppm and the indoor air quality setpoint is at 700ppm, the sensor needs to reach 1100ppm in order for the maximum position to be set. The controller proportionally opens until it reaches that point. Adjustable: 0 ppm to 1,000 ppm
Ventilation Timer This timer starts when you fall below the demand ventilation indoor air quality setpoint and after this time expires the DCV call to the rooftop unit expires and goes back to economizer minimum position. Adjustable: 5 min to 30 min
DCV Cooling Min Value The minimum damper position when cooling during a demand ventilation control state. Adjustable: 0% to 100%
DCV Heating Min Value The minimum damper position when heating during a demand ventilation control state. Adjustable: 0% to 100%
DCV Max Vent Position The maximum ventilation position. As determined by the setpoint and proportional band, this is the maximum position to set the ventilation. For example, if this is set to 50% and the controller is requiring maximum ventilation in the system, the damper adjusts to 50%. However, if the system requires more heating or cooling that damper may open further to the maximum position set in the Commisioning > Flow section. Adjustable: 0% to 100%
Control Setup Active Mode Shows the mode of the system. Adjustable: Cool Only/Heat Only/Fan Only/Water Flush/Purge/Auto
Unit Enable Enables or shuts down the zone control. Adjustable: Enable/Shutdown
Power Fail Restart Enable Upon a power fail the controller delays five minutes before it comes back operational. This is done so electrical demand is not spiked. Adjustable: Enable/Disable
Warmer/Cooler Adjust Enable The warmer/cooler adjustment to offset the current setpoint. Adjustable: False/True
DCV Enable When set to CO2 the DCV section in commissioning appears and a CO2 sensor when connected, controls the zone damper to add more ventilation when the CO2 demand increases above setpoint. Adjustable: None/CO 2
Temp OCC Enable Setting this parameter to enable means you can adjust the zone sensor during the unoccupied mode, thus placing the zone in the occupied state. In addition, the zone coordinators Network Temporary Occupancy Request parameter sets to true and the unit starts and runs for the temporary occupancy duration. Setting the parameter to disable means this function cannot take place in this zone. Adjustable: Enable/Disable
Zone Weight The user can increase the importance of a zone. For example, if the zone weight is set to three, it counts the vote of the zone three times as much than a zone set to one. Adjustable: 0 to 3
Zone Vote Allowed The user can remove a zone from voting. Adjustable: False/True
Lockout Enable This parameter enables or disables the rogue zone logic that takes a zone out of voting if it remains far away from the setpoint for too long. Adjustable: Disable/Enable
Lockout Time If the zone stays at 3°F away from the temperature setpoint for the duration of the lockout time, the zone is removed from the voting until the zone is satisfied at some point. Adjustable: 15 min to 90 min
Occupancy Mode When set to schedule, the zone switches occupancy state using the occupancy schedule of the zone coordinator only. When set to external, the controller looks at the occupancy sensor contact and toggle between occupancy setpoints and standby setpoints during occupied mode of the schedule. When the schedule is unoccupied the unit switches to unoccupied setpoint and turn off. Adjustable: External/Schedule
Auto Tune Enable Allows PRAC+ auto tuning algorithm to continuously tune the loops in the controller. Setting this to disable turns off this feature. Adjustable: Enable/Disable
PID Tune Reset Resets the PRAC+ tuning to the default values. Adjustable: Enable/Disable
Zone Group Number Use this parameter to indicate to the VZC100 the group schedule that this zone follows. You can choose from four independent schedules. Adjustable: 1 to 4
Equipment Setup Min Valve Position
Use this parameter to set the position of the heating valve when no heat is needed.
Note: This parameter is used for proportional SCR heat.
Adjustable: 0% to 100%
Max Valve Position
Use this parameter to set the position of the heating valve when maximum heat is needed.
Note: This parameter is used for proportional SCR heat.
Adjustable: 0% to 100%
Box Heating Installed Use this parameter to specify whether box heating is installed. Adjustable: No/Yes
Box Heating Polarity This reverses the direction of the incremental heating valve. You can either switch this or reverse the wiring to the actuator. Adjustable: Normal/Reverse
Heating Priority Use this parameter to set whether to first use box heat or supplemental heat when both are installed. Adjustable: Box/Supplemental
CO2 Altitude Compensation Altitude compensation used to calibrate the Netstat CO2 sensor. Adjustable: 700 hPa to 1,200 hPa
Supplemental PWM Enable   Adjustable: False/True
Supplemental Heating Installed Use this parameter to specify whether supplemental heating is installed. Adjustable: No/Yes
Actuator Stroke Time Sets the damper actuator stroke time. Note: The ZEC310 actuator is a 60 second motor. Adjustable: 30 s to 120 s
Damper Direction to Close Sets the direction to close the zone damper. Adjustable: clockwise/counter clockwise
ZNT Sensor Offset Used to calibrate the zone temperature sensor. Adjustable: -5°F to 5°F
Controller Firmware Version Displays the firmware version of the controller. Read only
Application Name Displays the name of the application. Read only
Application Version Displays the version of the application. Read only
Address Shows the address of the controller. The address is set by the dip switches on the controller. Read only
Unit Model Number Shows the model number of the controller. Read only
Trends Zone Temperature 288 samples are taken at a 15 minute period. Read only
Indoor Air Quality 288 samples are taken at a 15 minute period. Read only
Note: In order for the Commissioning: DCV tab to appear, you must set the DCV Enable parameter to CO2.
Table 6. TEC363x objects and parameters
Menu Object or Parameter Description Adjustable
Home Page Zone Temperature On the edge of the circle of comfort, the zone temperature reading from the zone sensor appears in one of the outer circles. Read only
Operating Setpoint Inside the circle of comfort, this is the setpoint the zone controls to, taking into account occupancy and the warmer/cooler adjustment. Read only
Occupied Status Inside the circle of comfort, the unit occupancy status appears. Read only
Unit Status Inside the circle of comfort, the unit status shows the current status of the unit. If the unit is satisfied or off, the circle appears gray. If the unit is in cooling, the circle appears blue. If the unit is in heating, the circle appears red. Read only
Fan Status Arrows rotate around the circle when the fan is on. Read only
Cooling Status Shows the cooling status of the unit. Read only
Heating Status Shows the heating status of the unit. Read only
Supply Air Temperature Shows the supply air temperature of the unit. Read only
Outdoor Air Temperature If install shows the outside air temperature. Read only
Alarms The Alarms tab displays all alarms that are active. Click on All Alarms to see the history of alarms. Read only
Overview Setpoint Offset This object shows how much was added or subtracted to the setpoint by the up/down arrows on the front screen. It is adjustable and the limit is adjustable by the MAX Setpoint Offset value. Adjustable: MAX Setpoint Offset sets range
Hold/Run If set to hold, the thermostat controls to this setpoint until it is placed back to run. Adjustable: Hold/Run
Active Setpoint This is the setpoint the zone controls to, taking into account occupancy and the warmer/cooler adjustment. Read only
Unit Enable Enables or shuts down the unit. If set to Shutdown, the unit remains off until set to enable. Adjustable: Enable/Shutdown
Fan Override
  • If set to On, the fan turns to keep the fan on.

  • If set to Auto, it follows the fan mode set under the General Settings menu.

  • If set to Quiet, it follows the fan mode set under the General Settings menu, but keeps multi-speed and variable-speed fans at their lowest speeds. This option is the same as Auto for single-speed fans. For the TEC3x3x models the Quiet Mode does not apply.

Adjustable: On/Auto/Quiet
Effective Zone Temperature The current zone temperature for the zone. Read only
Units Status Displays if the controller is cooling, heating, idle, disabled, or the reason why cooling and heating is unavailable. Read only
Occupancy Status Displays the effective occupancy state for the controller. Read only
Setpoints Occupied Cooling Setpoint When occupied, the thermostat controls cooling to this level. Set above occupied heating setpoint. Defaults to 72°F. Adjustable: 60.0°F to 100.0°F
Occupied Heating Setpoint When occupied, the thermostat controls heating to this level. Set below occupied cooling setpoint. Defaults to 68°F. Adjustable: 45.0°F to 85.0°F
Unoccupied Cooling Setpoint When unoccupied, the thermostat controls cooling to this level. Defaults to 80°F. Adjustable: 60.0°F to 100.0°F
Unoccupied Heating Setpoint When unoccupied, the thermostat controls heating to this level. Set below unoccupied cooling setpoint. Defaults to 60°F. Adjustable: 45.0°F to 85.0°F
Standby Cooling Setpoint In order for the standby cooling setpoint to appear, set the occupancy mode to external. When set to external, the zone switches to this setpoint when motion is no longer sensed and the unit is occupied. Defaults to 74°F. Adjustable: 60.0°F to 100.0°F
Standby Heating Setpoint In order for the standby heating setpoint to appear, set the occupancy mode to external. When set to external, the zone switches to this setpoint when motion is no longer sensed and the unit is occupied. Defaults to 66°F. Adjustable: 45.0°F to 85.0°F
Occ Setpoint Select You can use this parameter to choose whether setpoints shift up and down together with the same range or if they should have separate minimum and maximum values. Adjustable: Setpoint Offset/Min and Max Setpoint
Heat Cool Setpoint Mode Option to switch between distinct heating and cooling setpoints or a common setpoint with user-defined deadband. Adjustable: Individual Setpoints/Common Setpoint
Setpoints: Dehumidification Dehumidification Humidity setpoint 20% to 80% RH
Setpoints: Temperature Occupied Cooling n/a n/a
Occupied Heating n/a n/a
Common Setpoint n/a n/a
Unoccupied Cooling n/a n/a
Unoccupied Heating n/a n/a
Standby Cooling n/a n/a
Standby Heating n/a n/a
Min Cooling Setpoint n/a n/a
Max Cooling Setpoint n/a n/a
Min Heating Setpoint n/a n/a
Max Heating Setpoint n/a n/a
Occ Setpoint Select n/a n/a
Min Setpoint n/a n/a
Max Setpoint n/a n/a
Heat Cool Setpoint Mode n/a n/a
Auto Changeover The difference in temperature above or below the setpoint before a unit in the common setpoint mode switches from heating to cooling or cooling to heating. 1 to 5 delta oF
Setpoints: Ventilation Zone CO2 Setpoint Setpoint for zone CO2 in ppm. n/a
Low OAT Setpoint Limit setpoint for low OAT threshold. Ventilation is reduced to minimum value to protect equipment coils below this temperature. 0 oF to 60 oF
Supply Air Temperature Low Limit Low limit setpoint for air supplied from the RTU. Ventilation is reduced if cool OAT causes the supply air temperature to drop below this limit. 40 oF to 65 oF
Supply Air Temperature High Limit High limit setpoint for air supplied from the RTU. Ventilation is reduced if high OAT causes the supply air temperature to increase above this limit. 40 oF to 65 oF
Schedule: Options Optimal Start Enable Enables or disables the optimal start algorithm to automatically start the equipment prior to the scheduled occupancy period. It does this in order to reach the occupied setpoint. At the same time the schedule transitions from unoccupied to occupied. Setting this option to yes only has an effect when the local schedule is used. Adjustable: No/Yes
Temp Occ Duration Sets the duration for which the controller remains in a temporary occupancy period that is triggered during an unoccupied period. Temporary occupancy is triggered by interacting with the touch screen while unoccupied or by activating a binary input configured for temporary occupancy. Adjustable: 0 min to 300 min
Motion Sensor Timeout Sets how long the controller waits to return to standby mode after the last detection of motion while in a scheduled occupied period. Setting the timeout to zero minutes disables standby mode. Adjustable: 0 min to 240 min
Manual Occupancy Mode Use this mode to override all schedules and other sources of occupancy. You can also put the controller indefinitely into an occupied or unoccupied state. Adjustable: No Override/Occupied/Unoccupied
Schedule Source Sets the source of the occupancy schedule on the TEC. Setting to Local utilizes the internal 7-day programmable schedule, and setting to External uses the command from a BAS if it is online. If the BAS is offline, the schedule reverts to the onboard schedule. Adjustable: External/Schedule
Display Settings Passcode Enabled Setting this to True means you can enter a 4-digit passcode into the configuration menu. You can only define a passcode via the local display. Adjustable: 4 Digit Code
Brightness Setting Sets the brightness of the display when you are interacting with the display. Adjustable: Range 0 - 10
Enable Backlight Timeout Sets whether the backlight should timeout and go to low brightness after three minutes. Adjustable: No/Yes
Language Sets the language shown on the screens. Adjustable: English/French/Spanish
Units Sets Imperial (IP) or Metric (SI) units on the display and exposed to a BAS. Adjustable: IP/SI
Time Sets the time on the controller. Read only
Time Zone Sets the time zone where the controller is installed.
Note: Some time zones display No DST. This stands for daylight savings time.
Adjustable: Varies
Set Time Format Sets the display time format on the controller. Adjustable: 12 Hour/24 Hour
Date Sets the date on the controller. Read only
Set Date Format Sets the display date format on the controller. Adjustable
Show Fan Icon On Home Sets whether the user fan override option is available on the home screen. This means you can select the fan mode overrides from the home screen. Adjustable: No/Yes
Show Temp On Home Sets whether the current zone temperature is displayed on the home screen. Adjustable: No/Yes
Show Humidity On Home Sets whether the current zone humidity is displayed on the home screen. Humidity is always displayed when the setting is enabled on a thermostat controller with a built-in humidity sensor. The humidity is displayed when a network override is active on thermostat controllers without a built-in humidity sensor. Adjustable: No/Yes
Show Off Button On Home Sets whether the master control On/Off icon is displayed on the home screen. Adjustable: No/Yes
Show Hold Button Sets whether the Hold/Run icon is displayed on the home screen. The Hold/Run icon is the square around the zone setpoint on the right side of the screen. Adjustable: No/Yes
Show Setpoint On Home Sets whether the current zone temperature setpoint is displayed on the home screen. Adjustable: No/Yes
Show Alarms On Home Sets whether the current alarm symbol is displayed on the home screen when warnings or alarms are active. Adjustable: No/Yes
Show Occ Status Sets whether the current occupancy status shows on the home screen. Adjustable: No/Yes
Show Unit Status Sets whether the operational status of the controller shows on the home screen. Adjustable: No/Yes
Show Date/Time Sets whether the date and time show on the home screen. Adjustable: No/Yes
Show Damper Pos on Home Enables or disables display of the damper position feedback sensor on the homescreen. Adjustable: No/Yes
Show CO2 on Home Enables or disables the display of the CO2 sensor on the homescreen. Adjustable: No/Yes
Control Setup: General Control Mode Sets the thermostat to operate only in cooling or heating modes, or to automatically switch between cooling and heating based on the zone temperature. Adjustable: Auto/Heating/Cooling
Unit Enable Enables or disables the control. This option is linked to the Off/On icon on the home screen. The home screen fan override can still turn the fan on when Unit Enable = False Adjustable: Enable/Shutdown
Fan Mode Sets the operational mode of the fan. The options include:

On - The fan runs continuously unless control is disabled.

Auto - The fan cycles with the equipment stages.

Smart - The fan operates continuously while occupied, and follows the Auto mode when unoccupied.

Adjustable: On/Auto/Smart
Max Setpoint Offset Sets the maximum deviation above or below the active programmed setpoint that the user can set from the home screen. Adjustable: Range 0 to 20
Fan On Delay Sets how long the fan waits to turn on after turning on a stage of heating or cooling. Adjustable: Range: 0 s to 120 s
Fan Off Delay Sets how long the fan waits to turn off after turning off the last stage of heating or cooling. Adjustable: Range: 0 s to 120 s
Frost Protection Prompts the controller to turn on heating when the zone temperature drops below 42°F regardless of whether the control is enabled. Adjustable: No/Yes
Reset PID Tuning Resets the PRAC+ tuning parameters of the PID controllers to the factory defaults. Adjustable: No/Yes
Auto Tuning Enable Enables the PRAC+ auto tuning algorithm to adjust PID tuning parameters for optimal control performance. Adjustable: No/Yes
Aux Mode

Sets the mode that the auxiliary output runs in. Options include:

Not Used - Opens the contact.

Occupied NO - Closes the contact when the controller is occupied.

Occupied NC - Opens the contact when the controller is occupied.

Occupied Fan NO - Closes the contact when the controller is occupied and the fan is running.

Occupied Fan NC - Opens the contact when the controller is occupied and the fan is running.

Off - Opens the contact.

On - Closes the contact.

Adjustable: Not Used / Occupied NO / Occupied NC / Occupied Fan NO / Occupied Fan NC / Off / On
Load Shed Adjust This sets how the setpoints move when a load shed command is issued. For example, if the Occupied Cooling Setpoint is 72°F the cooling setpoint moves towards 76°F if the adjustment is set to four. If the Occupied Heating Setpoint is 70°F the heating setpoint moves towards 66°F. Adjustable: Range: 0°F to 8°F
Load Shed Rate Limit This sets the rate at which the controller adjusts the setpoint until it hits the load shed adjust. Adjustable: Range: 0°F/min to 1 °F/min
Control Setup: General (continued) Fan Alarm Delay If the binary inputs are set to supply fan status, the controller uses this delay parameter to delay a supply fan alarm. If set to zero the alarm turns off. Adjustable: Range 0 min to 5 min
Fan Alarm Action When the supply fan alarm delay is above zero this parameter appears. This sets the action of the controller once a fan alarm is sensed. Adjustable: Range: 0 s to 300 s
Fan Alarm Reset When the supply fan alarm delay is above zero, this parameter appears. You can reset the fan alarm here, once it has been triggered. Adjustable: No/Yes
Fan Runtime Limit The fan runtime limit is used to set a periodic alarm for maintenance. Set the number of hours you want the fan to run for and after the limit is reached, an alarm generates. At this time perform the maintenance (i.e. change the filters, clean the coils) and then reset the alarm. Set this to zero when you want to disable it. Adjustable: Range 0 hrs to 9000 hrs
Fan Runtime Reset This parameter appears when the runtime limit is above zero. It is used to reset the runtime alarm. Adjustable: No/Yes
Supply Air Temperature Alarm Offset Defines the minimum change in supply air temperature when heating or cooling is active. If this offset is not exceeded within the delay, an alarm occurs.
Note: You can disable the alarm if you set this parameter to 0.
Adjustable: 0 delta °F to 10 delta °F
Supply Air Temperature Alarm Delay If the Supply Air Temperature Alarm Offset is greater than 0, the supply air temperature alarm is enabled. Use this parameter to set how long to delay the supply air temperature alarm. Adjustable: 300 s to 3,600 s
Scheduled Circulation Enable Enables or disables an hourly minimum runtime for the fan. Adjustable: No/Yes
Scheduled Circulation Only When Occupied Enables or disables the hourly minimum runtime sequence to only run during the occupied periods of the schedule. Adjustable: No/Yes
Minimum Hourly Fan Runtime Minimum hourly runtime setpoint. Adjustable: 5 min to 30 min
Economizer Fault Detection Enable Enable or disable Title 24 FDD fault code sequence. Adjustable: Disable/Enable
Control Setup: Inputs BI1 Config Sets the mode that the binary input operates in.
  • Occupancy – Direct override of Occupied/Unoccupied
  • Temp Occ – Trigger to place controller into Temporary Occupancy mode
  • Motion NO – External motion sensor with an open contact output when no motion is detected
  • Motion NC – External motion sensor with a closed contact output when no motion is detected
  • Dirty Filter – Input from the equipment to display a dirty filter fault on the thermostat
  • Service – Input from the equipment to display a service warning on the thermostat
  • Fan Lock – Air proof switch input to shut down control if no airflow is detected within ten seconds of turning the fan on
  • Open Door – Works in conjunction with the Motion NO/Motion NC sensor to control occupancy
  • Open Window – Sensor to shut down control if a window is opened. The controller disables control 60 seconds after detecting an opened window.
  • Supply Fan Status - Connect a current relay or air proving switch to the input for proof of fan. If the fan alarm delay is set above zero the controller issues an alarm if the commanded value does not match the measured value.
Adjustable:
  • Disabled

  • Occupancy

  • Temp Occ

  • Motion NO

  • Motion NC

  • Dirty Filter

  • Service

  • Open Door

  • Open Window

  • Supply Fan Status

BI2 Config
Supply Temp Sensor Sets the type of analog supply temperature sensor connected to the controller. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Supply Temp Offset Sets the offset applied to the supply/discharge temperature reading. Adjustable: Range: -5.0 to 5.0
Control Setup: Inputs (continued) Zone Temp Sensor Sets the type of analog zone temperature sensor connected to the controller. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Zone Temp Offset Sets the offset applied to the zone temperature displayed on the screen and used for control. Adjustable: -5.0 to 5.0
Outdoor Air Temp Sensor Sets the type of analog outdoor air temperature sensor connected to the controller. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Outdoor Air Temp Offset Sets the offset applied to the outdoor temperature reading. Adjustable: -5.0 to 5.0
Reset Sensors Resets sensor inputs back to factory state. This clears alarms for sensors which were connected at one point and are no longer connected. Adjustable: No/Yes
Zone Temp Alarm Enabled If set to yes, the controller evaluates the zone temperature and issues an alarm if the zone temperature rises about the high limit or falls below the low limit. Adjustable: No/Yes
Zone Temp Low Limit Appears when the zone temperature alarm is set to yes. Use this to set how low the zone temp drops before an alarm issues. Adjustable: 32°F to 150°F
Zone Temp High Limit Appears when the zone temperature alarm is set to yes. Use this to set how high the zone temp rises before an alarm issues. Adjustable: 32°F to 150°F
Control Setup: Tuning Temp Control Setup Sets Automatic PID Tuning, Manual PID Tuning, Deadband Override, or On/Off Control (On/Off Control is available for units with staged control outputs only).
  • Automatic PID Tuning - uses PRAC+ (all units) and PMAC (staged units only) to satisfy zone demand. Works best with proportional equipment. Also works with staged equipment in large zones (500 sq ft or greater) with a single piece of equipment operating that space.
  • Manual PID Tuning - uses manual tuning parameters to satisfy zone demand, similar to Automatic PID Tuning, but parameters need to be manually adjusted per zone.
  • Deadband Override - uses PRAC+ (all units) and PMAC (staged units only) to satisfy zone demand. Allows the user to specify the Deadband parameter that PRAC+ and PMAC use.
  • On/Off Control - uses a simple deadband and timer to satisfy zone demand (staged equipment only).
Adjustable: Automatic PID Tuning/Deadband Override/Manual PID Tuning/On Off Control
Reset PID Tuning When Reset Tuning is True, causes the PID to reset the Effective Proportional Band and the Effective Integral Time to the values in Proportional Band and Integral Time. Adjustable: No/Yes
Deadband Sets the Effective Deadband. Adjustable: 1.4 delta °F to 3 delta °F
Auto Economizer Tuning Determines if the adaptive tuning is allowed to operate for the OA damper. Adjustable: Disable/Enable
Heat Prop Band Sets the initial Effective Proportional Band. Adjustable: 5 delta °F to 30 delta °F
Heat Integral Time Sets the initial Effective Integral Time. Adjustable: 300 s to 1600 s
Heat Process Range Indicates the magnitude of the range that the process variable traverses as the Present Value of the PID varies between its minimum and maximum values. Adjustable: 10 delta °F to 100 delta °F
Heat Saturation Time Sets the Effective Saturation Time. Adjustable: 60 s to 900 s
Heat Time Constant Indicates the time required for a system to reach 63% of its final magnitude given a 100% step change. Adjustable: 360 s to 1,440 s
Heat Process Dead Time Indicates the time required for the process to begin to reflect the results of a step change. Adjustable: 20 s to 120 s
Heat Period Sets the Effective Period. Adjustable: 30 s to 120 s
Cool Prop Band Sets the initial Effective Proportional Band. Adjustable: 5 delta °F to 30 delta °F
Cool Integral Time Sets the initial Effective Integral Time. Adjustable: 300 s to 1,600 s
Cool Process Range Indicates the magnitude of the range that the process variable traverses as the Present Value of the PID varies between its minimum and maximum values. Adjustable: 10 delta °F to 100 delta °F
Control Setup: Tuning (continued) Cool Saturation Time Sets the Effective Saturation Time. Adjustable: 60 s to 900 s
Cool Time Constant Indicates the time required for a system to reach 63% of its final magnitude given a 100% step change. Adjustable: 360 s to 1,440 s
Cool Process Dead Time Indicates the time required for the process to begin to reflect the results of a step change. Adjustable: 20 s to 120 s
Cool Period Sets the Effective Period. Adjustable: 30 s to 120 s
Econ Prop Band Sets the initial Effective Proportional Band. Adjustable: 5 delta °F to 30 delta °F
Econ Integral Time Sets the initial Effective Integral Time. Adjustable: 300 s to 1,600 s
Econ Process Range Indicates the magnitude of the range that the process variable traverses as the Present Value of the PID varies between its minimum and maximum values. Adjustable: 10 delta °F to 100 delta °F
Econ Saturation Time Sets the Effective Saturation Time. Adjustable: 60 s to 900 s
Econ Time Constant Indicates the time required for a system to reach 63% of its final magnitude given a 100% step change. Adjustable: 360 s to 1,440 s
Econ Process Dead Time Indicates the time required for the process to begin to reflect the results of a step change. Adjustable: 20 s to 120 s
Econ Period Sets the Effective Period. Adjustable: 30 s to 120 s
Equipment Size Sets the internal zone temperature response. It can be normal (slower) or Oversized (faster). Adjustable: Normal/Oversized
Setup: Equipment Setup: Economizer Test Outdoor Air Damper Enables or disables an hourly minimum runtime for the fan. Adjustable: Enable/Disable
Economizer Damper % Command Enables or disables the hourly minimum runtime sequence to only run during occupied periods of the schedule. Adjustable: Enable/Disable
Outdoor Air Damper Test Status Minimum hourly runtime setpoint 5 min to 30 min
Setup: Ventilation Setup: Demand Control Ventilation Demand Control Ventilation Enable Enables or disables DCV during occupied schedule Adjustable: Enable/Disable
Occupant Sensor Ventilation Enable Enables or disables OCV during PIR detected occupnacy Adjustable: Enable/Disable
Pre Occupancy Purge Time Time prior to occupied that the unit can increase ventilation above normal to lower CO2 to below setpoint. 0 min to 600 min
Allow Min Ventilation During Occ Allow minimum ventilation position to ventilate space more than CO2 demand requires. Adjustable: Enable/Disable
Setup: Ventilation Setup: Epidemic Control Ventilation Epidemic Control Ventilation Enable Enables or disables ECV based on ASHRAE Core Recommendations for Reducing Airborne Infectious Aerosol Exposure. Adjustable: Enable/Disable
Enable Minimum Ventilation When Unocc Enables or disables using a minimum damper position when unoccupied when ECV is safe. Adjustable: Enable/Disable
Unoccupied Damper Minimum Position Unoccupied minimum damper setpoint 0% to 100%
Inc Ventilation Pre Occ Purge time The amount of time prior to occupnacy that increased ventilation occurs. 0 min to 600 min
Inc Ventilation Post Occ Purge Time The amount of time after occupancy that increased ventilation occurs. 0 min to 240 min
Enable Humidity Alarm Enables or disables a high humidity alarm for the zone. Adjustable: Enable/Disable
Setup: Commissioning Supply Air Temperature Current Supply Air Temperature value n/a
Effective Zone Temperature Current Zone Air Temperature value n/a
Heat Stage 1 Override heat stage 1 output for conventional units Adjustable: Yes/No
Heat Stage 2 Override heat stage 2 output for conventional units Adjustable: Yes/No
Cool Stage 1 Override cool stage 1 output for conventional units Adjustable: Yes/No
Cool Stage 2 Override cool stage 2 output for conventional units Adjustable: Yes/No
Compressor Override compressor output for heat pump units Adjustable: Yes/No
Reversing Valve Override reversing valve output for heat pump units Adjustable: Yes/No
Supplemental Heat Override supplemental heat output for heat pump units Adjustable: Yes/No
Econ Command Override econ command output 0% to 100%
Aux Override aux output for heat pump units Adjustable: Yes/No
Start Commission Enables or disables the commissioning override sequence Adjustable: Enable/Disable
Network Setup FC Comm Mode Sets BACnet or N2 communications mode. Only adjustable at the stat. For a Verasys system set this to BACnet. Read only
BACnet Instance ID Sets the instance ID of the controller when on a BACnet network. Adjustable: 1 to 4,194,303
BACnet Address Sets the physical network address on a BACnet network. Adjustable: 0 to 127
MSTP Baud Rate When set to auto the SBH sets the baud rate for the controller. Adjustable: Auto/1200/9600/19200/38400/76800
BACnet Encoding Type Sets the encoding type to use on the BACnet network. Verasys uses ISO 10646 (UCS-2). Adjustable: ISO 10646 (UCS-2)/ANSI X3.4 (US-ACSII)
Equipment Setup: General Number of Compressors Sets the number of compressors in a rooftop unit or heat pump. Adjustable: Not Used/One Stage/Two Stage
Runtime Equalization When enabled, the controller alternates between Y1 and Y2 calls when cycling 2-stage compressors, to ensure both compressors are equally used. Adjustable: No/Yes
Number of Heating Stages Sets the number of heat stages in a rooftop unit. This option does not exist on heat pumps. Heat Pumps support a single stage of supplemental heating on top of compressor heating. Adjustable: Not Used/One Stage/Two Stage
Compressor Min On Time Sets the minimum time that a compressor runs under normal control conditions. Adjustable: 0 s to 360 s
Compressor Min Off Time Sets the minimum time that a compressor must be off for before turning on again. Adjustable: 0 s to 360 s
Heating Min On Time Sets the minimum time that the heating valve/stage is open under normal conditions. Adjustable: 0 s to 360 s
Heating Min Off Time Sets the minimum time that the heating valve/stage is closed before opening again. Adjustable: 0 s to 360 s
Cooling Lockout Temp Sets the outdoor temperature below which cooling does not run regardless of zone temperature. Adjustable: 0°F to 100°F
Heating Lockout Temp Sets the outdoor temperature above which heating does not run regardless of zone temperature. Note: Frost Protection overrides this lockout. Adjustable: 0°F to 100°F
Unoccupied Off Delay Sets the off delay time that the unit will continue to heat or cool after demand has been met when in Unoccupied mode. 0 min to 10 min
Equipment Setup: Economizer Economizer Installed Sets if economizer damper control is required on the rooftop or heat pump unit. Adjustable: No/Yes
Minimum Position Sets the minimum economizer position when the fan is running. Adjustable: 0% to 100%
Closed Voltage Sets the voltage corresponding to the damper being fully shut. Adjustable: 0 V to 10 V
Open Voltage Sets the voltage corresponding to the damper being fully opened. Adjustable: 0 V to 10 V
Dry Bulb Setpoint Sets the outdoor air temperature. When in dry bulb mode and the TEC only has outdoor and zone temperature, the economizer does not operate above this temp. Adjustable: 40°F to 80°F
Outdoor Enthalpy Setpoint Sets the outdoor air enthalpy. When the TEC has outdoor temperature, outdoor humidity and zone temperature, the economizer cooling does not operate when in single enthalpy mode. Adjustable: 10 to 50 Btu/lb dry air
Equipment Setup: Heat Pump Heat Pump Supported Sets whether the W1 output is used to control a reversing valve (O/B) and if Y1/Y2 controls compressors for both cooling and heating. Supp Heating Installed – Sets if a stage of supplemental heating is connected to the W2 output. Many heat pumps with integrated control units use traditional thermostat controller wiring (Y, W, and G inputs). Only set this option to Yes on the heat pump units where the thermostat controller controls an O/B input on the equipment. Adjustable: No/Yes
Supp Heating Supported Sets the minimum economizer position when the fan is running. Adjustable: No/Yes
Comp Low Lockout Temp Sets the temperature below which compressor heating does not run. -20°F to 100°F
Supp High OA Lockout Temp Sets the temperature above which supplemental heating does not run. -20°F to 100°F
Reverse Valve Polarity Sets the voltage corresponding to the damper being fully shut. Adjustable: Normal Heat/Normal Cool
System Status Occupancy Source Displays the current source of the TEC controller’s occupancy. Read only
Unit Status Displays if the controller is cooling, heating, idle, disabled, or the reason why cooling and heating is unavailable. Read only
Outdoor Air Temperature If installed, displays the outdoor air temperature value in the controller. Read only
Outdoor Humidity If installed, displays the outdoor humidity value in the controller. Read only
Supply Air Temperature If installed, displays the supply air temperature value in the controller. Read only
Return Air Humidity n/a n/a
Indoor Air Quality n/a n/a
Damper Feedback n/a n/a
Economizer Available Displays the status if the outdoor conditions are suitable for economizer cooling. Read only
Cooling OAT Lockout Displays if cooling is being locked out due to low outdoor air temperature. Read only
Heating OAT Lockout Displays if heating is being locked out due to high outdoor air temperature. Read only
Comp Low OAT Lockout Displays if compressor heating is locked out due to low outdoor air temperature. Read only
Zone Temp Source Displays the source of the zone temperature reading in the TEC controller. Read only
Fan Accumulated Runtime Displays the accumulated runtime. Read only
BI1 Status Displays the current status of BI1. Read only
BI2 Status Displays the current status of BI2. Read only
Zone Dew Point Temperature Displays the zone dew point temperature n/a
Free Cooling Available Displays if the outdoor air conditions allow for free cooling using the economizer damper n/a
Control Status Control % Command Displays the current PID controller percent command. Read only
Cooling % Command n/a n/a
Heating % Command Displays the current PID controller percent command. Read only
Supplemental Heat % Command If supplemental heating is installed, this parameter displays the current percent command for supplemental heating. Read only
Economizer % Command Displays the current PID controller percent command. Read only
Cool Stage 1 Displays if the first stage of cooling is on. Read only
Cool Stage 2 Displays if the second stage of cooling is on. Read only
Heat Stage 1 Displays if the first stage of heating is on. Read only
Heat Stage 2 Displays if the second stage of heating is on. Read only
Fan Displays the current fan command Read only
Dehumidifier Command Displays if the aux output is on for dehumidification using a stand-alone dehumidifier. n/a
Hot Gas Reheat Command Displays if the aux output is on for dehumidification using the hot gas reheat valve. n/a
Mixed Air Low Limit Cycle Displays if the economizer damper is being closed due to low mixed air temperatures. n/a
Status: DCV Status Not Economizing When Should These points are FDD fault codes to support Title 24 section 120.2(I) and can be used to support certification requirements in form JA6.3. n/a
Economizing When Should Not
Damper Not Modulating
Excess Outdoor Air
Air Temperature Sensor Failure
Economizer Enabled For Operation
Compressor Enable Displays if the compressors are enabled or disabled for cooling. n/a
Heating Enable Displays if heating enabled or disabled. n/a
Controller Info Model Name Displays the firmware version of the controller. Read only
Software Version Shows the address of the controller. The address is set by the dip switches on the controller. Read only
Unit Name The name of the unit. Adjustable: 30 characters
Device Name The name of the device. This name shows up on the device list. Adjustable: 30 characters
Device Description The description of the device. This description shows up on the device list. Adjustable: 30 characters
Trends Effective Zone Temperature 100 samples are taken at a 15 minute period. Read only
Active Setpoint 100 samples are taken at a 15 minute period. Read only
Humidity 100 samples are taken at a 15 minute period. Read only
BI1 Status 100 samples are taken at a 15 minute period. Read only
BI2 Status 100 samples are taken at a 15 minute period. Read only
Operational Outdoor Air Temperature 100 samples are taken at a 15 minute period. Read only
Supply Air Temperature 100 samples are taken at a 15 minute period. Read only
Fan Command 25 samples in total. 1 sample taken every change of value. Read only
Cool Stage 1 On 25 samples in total. 1 sample taken every change of value. Read only
Cool Stage 2 On 25 samples in total. 1 sample taken every change of value. Read only
Heat Stage 1 On 25 samples in total. 1 sample taken every change of value. Read only
Heat Stage 2 On 25 samples in total. 1 sample taken every change of value. Read only
Economizer PID Cmd 100 samples are taken at a 15 minute period. Read only
Heat PID Cmd 100 samples are taken at a 15 minute period. Read only
Cool/Dehum PID Cmd 100 samples are taken at a 15 minute period. Read only
Indoor Air Quality 100 samples are taken at 15 min intervals Read only
Damper Feedback 100 samples are taken at 15 min intervals Read only
Outdoor Air Humidity 100 samples are taken at 15 min intervals Read only
Table 7. LC-VAC1002-0 Input Output Module parameters and objects
Menu Object or Parameter Description Adjustable
Home Page Binary Input 1 Status The input is defined on the Commissioning tab. Read only
Binary Input 2 Status
Binary Input 3 Status
Binary Input 4 Status
Analog Input 5 Status
Analog Input 6 Status
Analog Input 7 Status
Analog Input 8 Status
Analog Input 9 Status
Netsensor 1 Temperature
Netsensor 2 Temperature
Netsensor 3 Temperature
Netsensor 4 Temperature
Netsensor 5 Temperature
Netsensor 1 Humidity
Netsensor 2 Humidity
Netsensor 3 Humidity
Netsensor 4 Humidity
Netsensor 5 Humidity
Output 1 Status
Output 2 Status
Output 3 Status
Output 4 Status
Output 5 Status
Output 6 Status
Output 7 Status
Output 8 Status
Output 9 Status
Energy Meter 1 Consumption
Energy Meter 2 Consumption
Energy Meter 3 Consumption
Energy Meter 4 Consumption
Alarms Alarms To see the history of alarms, click All Alarms. Read only
Status: Inputs Binary Input 1 Status The input is defined on the Commissioning tab. Read only
Binary Input 2 Status
Binary Input 3 Status
Binary Input 4 Status
Analog Input 5 Status
Analog Input 6 Status
Analog Input 7 Status
Analog Input 8 Status
Analog Input 9 Status
Status: Outputs Output 1 Status The input is defined on the Commissioning tab. Read only
Output 2 Status
Output 3 Status
Output 4 Status
Output 5 Status
Output 6 Status
Output 7 Status
Output 8 Status
Output 9 Status
Status: Netsensor Plug and Play Netsensor 1 Temperature The input is defined on the Commissioning tab. Read only
Netsensor 1 Humidity
Netsensor 2 Temperature
Netsensor 2 Humidity
Netsensor 3 Temperature
Netsensor 3 Humidity
Netsensor 4 Temperature
Netsensor 4 Humidity
Netsensor 5 Temperature
Netsensor 5 Humidity
Summary: General Energy Meter 1 Address Sets the address of the energy meter. Adjustable: Enter the last 3 digits of the serial number.
Energy Meter 2 Address
Energy Meter 3 Address
Energy Meter 4 Address
Summary: Energy Meter 1 Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Energy Consumption Shows the electrical meter consumption since the last reset.
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Input 1 If present, shows the consumption of the pulse meter hooked to input 1. The input is defined on the Commissioning tab.
Input 2 If present, shows the consumption of the pulse meter hooked to input 2. The name of the input is defined under the Commissioning tab.
Clear Statistics Clears or resets the statistics of the meter. Adjustable: True/False
Summary: Energy Meter 2 Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Energy Consumption Shows the electrical meter consumption since the last reset.
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Input 1 If present, shows the consumption of the pulse meter hooked to input 1. The input is defined on the Commissioning tab.
Input 2 If present, shows the consumption of the pulse meter hooked to input 2. The name of the input is defined under the Commissioning tab.
Clear Statistics Clears or resets the statistics of the meter. Adjustable: True/False
Summary: Energy Meter 3 Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Energy Consumption Shows the electrical meter consumption since the last reset.
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Input 1 If present, shows the consumption of the pulse meter hooked to input 1. The input is defined on the Commissioning tab.
Input 2 If present, shows the consumption of the pulse meter hooked to input 2. The input is defined on the Commissioning tab.
Clear Statistics Clears or resets the statistics of the meter. Adjustable: True/False
Summary: Energy Meter 4 Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Energy Consumption Shows the electrical meter consumption since the last reset.
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Input 1 If present, shows the consumption of the pulse meter hooked to input 1. The input is defined on the Commissioning tab.
Input 2 If present, shows the consumption of the pulse meter hooked to input 2. The input is defined on the Commissioning tab.
Clear Statistics Clears or resets the statistics of the meter. Adjustable: True/False
Commissioning: Energy Meter 1: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Last Demand Shows the amount of energy consumed in the last demand window time.
Demand Window Time Sets the period in which the demand is monitored. Adjustable: 5 min to 60 min
Elapsed Demand Window Shows the amount of time elapsed in the demand window time. Read only
Demand Window Count Shows the number of demand windows since the last reset.
Energy Consumption The electrical meter consumption of all phases since the last reset.
Clear Statistics Clears or resets the statistics of the meter. Adjustable
Input 1 Sets whether Input 1 is used to accumulate. Adjustable: Present/Absent
Input 2 Sets whether Input 2 is used to accumulate.
Commissioning: Energy Meter 1: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 1: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 1: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 1: Input 1 Description Shows the description of this pulse input. Adjustable
Pulse Counter Shows the number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor Shows the value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Energy Meter 1: Input 2 Description The description of this pulse input. Adjustable
Pulse Counter Shows the number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor Shows the value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Energy Meter 2: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Last Demand Shows the amount of energy consumed in the last demand window time.
Demand Window Time Sets the period in which the demand is monitored. Adjustable: 5 min to 60 min
Elapsed Demand Window Shows the amount of time elapsed in the demand window time. Read only
Demand Window Count Shows the number of demand windows since the last reset.
Energy Consumption Shows the electrical meter consumption of all phases since the last reset.
Clear Statistics Clears or resets the statistics of the meter Adjustable
Input 1 Sets whether Input 1 is used to accumulate. Adjustable: Present/Absent
Input 2 Sets whether Input 2 is used to accumulate.
Commissioning: Energy Meter 2: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit., Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 2: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 2: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 2: Input 1 Description Shows the description of this pulse input. Adjustable
Pulse Counter Shows the number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor The value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Energy Meter 2: Input 2 Description Shows the description of this pulse input. Adjustable
Pulse Counter Shows the number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor The value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Energy Meter 3: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Last Demand Shows theamount of energy consumed in the last demand window time.
Demand Window Time Sets the period in which the demand is monitored. Adjustable: 5 min to 60 min
Elapsed Demand Window Shows the amount of time elapsed in the demand window time. Read only
Demand Window Count Number of demand windows since the last reset.
Energy Consumption Shows the electrical meter consumption of all phases since the last reset.
Clear Statistics Clears or resets the statistics of the meter. Adjustable
Input 1 Sets whether Input 1 is used to accumulate. Adjustable: Present/Absent
Input 2 Sets whether Input 2 is used to accumulate.
Commissioning: Energy Meter 3: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption The electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 3: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption The electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 3: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit The value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit The value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 3: Input 1 Description The description of this pulse input. Adjustable
Pulse Counter The number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor The value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value Adjustable
Commissioning: Energy Meter 3: Input 2 Description Shows the description of this pulse input. Adjustable
Pulse Counter Shows the number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor Shows the value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Energy Meter 4: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Last Demand Shows the amount of energy consumed in the last demand window time.
Demand Window Time Sets the period in which the demand is monitored. Adjustable: 5 min to 60 min
Elapsed Demand Window The amount of time elapsed in the demand window time. Read only
Demand Window Count Number of demand windows since the last reset.
Energy Consumption The electrical meter consumption of all phases since the last reset.
Clear Statistics Clears or resets the statistics of the meter. Adjustable
Input 1 Sets whether Input 1 is used to accumulate. Adjustable: Present/Absent
Input 2 Sets whether Input 2 is used to accumulate.
Commissioning: Energy Meter 4: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 4: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 4: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption The electrical meters phase consumption since the last reset.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 90 V to 600 V
Low Alarm Limit Shows the value for the Low Alarm Limit.
Differential Sets the alarm differential. Adjustable: 0 V to 10 V
Commissioning: Energy Meter 4: Input 1 Description The description of this pulse input. Adjustable
Pulse Counter The number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor The value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Energy Meter 4: Input 2 Description The description of this pulse input. Adjustable
Pulse Counter The number of pulses since last reset. Read only
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description.
Scale Factor The value of each pulse. Multiplying the scale factor by the pulse count gives the present value. Adjustable: 0.01 to 1,000
Change Units Change the display units of the present value. Adjustable
Commissioning: Inputs: Binary Input 1 Present Sets whether or not this input is in use. Adjustable: Present/Absent
States Text Sets the enumeration that the object shows on screen. Adjustable
Input The current state of the input; the name of this is reflected in the Description field. Read only
Description The description of the input. Adjustable
Delay Type If this a momentary input, this parameter sets the delay type for the input. Adjustable: None/Off/On/Both
Off Delay If the delay type is set to Off or Both, this sets the Delay Off timer. Adjustable: 1 min to 360 mins
On Delay If the delay type is set to On or Both, this sets the Delay On timer.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
Alarm Text Sets the text that is sent with the alarm. Adjustable
Alarm State Sets which state issues the alarm.
Alarm Delay Delays the alarm if needed. Adjustable: 0 mins to 100 mins
Commissioning: Inputs: Binary Input 2 Present Sets whether or not this input is in use. Adjustable: Present/Absent
States Text Sets the enumeration that the object shows on screen. Adjustable
Input The current state of the input; the name of this is reflected in the Description field. Read only
Description The description of the input. Adjustable
Delay Type If this a momentary input, this sets the delay type for the input. Adjustable: None/Off/On/Both
Off Delay If the delay type is set to Off or Both, this sets the Delay Off timer. Adjustable: 1 min to 360 mins
On Delay If the delay type is set to On or Both, this sets the Delay On timer.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
Alarm Text Sets the text that is sent with the alarm. Adjustable
Alarm State Sets which state issues the alarm.
Alarm Delay Delays the alarm if needed. Adjustable: 0 mins to 100 mins
Commissioning: Inputs: Binary Input 3 Present Sets whether this input is being used or not. Adjustable: Present/Absent
States Text Sets the enumeration that the object shows on screen. Adjustable
Input The current state of the input; the name of this is reflected in the Description field. Read only
Description The description of the input Adjustable
Delay Type If this a momentary input, this parameter sets the delay type for the input. Adjustable: None/Off/On/Both
Off Delay If the delay type is set to Off or Both, this sets the Delay Off timer. Adjustable: 1 min to 360 mins
On Delay If the delay type is set to On or Both, this sets the Delay On timer.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
Alarm Text Sets the text that is sent with the alarm. Adjustable
Alarm State Sets which state issues the alarm.
Alarm Delay Delays the alarm if needed. Adjustable: 0 mins to 100 mins
Commissioning: Inputs: Binary Input 4 Present Sets whether or not this input is in use. Adjustable: Present/Absent
States Text Sets the enumeration that the object shows on screen. Adjustable
Input The current state of the input; the name of this is reflected in the Description field. Read only
Description The description of the input. Adjustable
Delay Type If this a momentary input, this sets the delay type for the input. Adjustable: None/Off/On/Both
Off Delay If the delay type is set to Off or Both, this sets the Delay Off timer. Adjustable: 1 min to 360 mins
On Delay If the delay type is set to On or Both, this sets the Delay On timer.
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
Alarm Text Sets the text that is sent with the alarm. Adjustable
Alarm State Sets which state issues the alarm.
Alarm Delay Delays the alarm if needed. Adjustable: 0 mins to 100 mins
Commissioning: Inputs: Analog Input 5 Point Type Sets what kind of input the point is defined as. Adjustable: Undefined/Temperature/Humidity/CO2/Light Sensor/Refrigerant/Building Pressure/Steam Pressure/Voltage/Current
Description The description of the input. Adjustable
Input The current value of the input; the name of this is reflected in the Description field. Read only
Change Units Change the units for user defined voltage or current inputs. Adjustable
Change Display Precision Change the display precision, which also changes the change of value (COV) increment, for user defined voltage or current inputs.
Setup When point type is set to Temperature Inputs, this sets the type of sensor used. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Input Range Low When point type is set to Voltage and Current, this parameter sets the voltage or current for the minimum value. Adjustable: 0 to 10, V or mA depending on the input
Input Range High When the point type is set to Voltage and Current, this parameter sets the voltage or current for the max value. Adjustable: 5 to 20, V or mA depending on the input
Voltage Range When point type is set to Building Pressure, this parameter sets the voltage input for the sensor. Adjustable: 0 to 10 V/2 to 10 V/0 to 5 V
Device Type Point type is set to Steam Pressure and assumes the sensor is DPT2090-25G. This parameter sets whether the sensor sends a current or voltage. If it sends voltage, the range is 0-5.5 VDC. If it sends current, the range is 4-20 mA. Adjustable: Current/Voltage
Output Range Low Point type set to Building Pressure, Voltage, or Current. Sets the minimum value of the range for the sensor. Adjustable: -100,000 to 100,000
Output Range High Point type set to Building Pressure, Voltage, or Current. Sets the maximum value of the range for the sensor. Adjustable: -100,000 to 100,000
Offset Use this parameter to offset the present value of the analog input. Adjustable: +/-10% of full range (dynamic)
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
Unreliable Sensor Sets the text that is sent when the sensor is unreliable.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: Dynamic based on point type
Low Alarm Limit Shows the value for the Low Alarm Limit.
Alarm Delay Delays the alarm if needed.
Alarm Differential Sets the alarm differential. Adjustable: +/- 10% of full range (dynamic)
Trend Enables or disables the trend. Adjustable: Enable/Disable
Interval Sets the interval of the trend samples. Adjustable: 0 s to 900 s
Commissioning: Inputs: Analog Input 6 Point Type Sets what kind of input the point is defined as. Adjustable: Undefined/Temperature/Humidity/CO2/Light Sensor/Refrigerant/Building Pressure/Steam Pressure/Voltage/Current
Description The description of the input. Adjustable
Input The current value of the input; the name of this is reflected in the Description field. Read only
Change Units Change the units for user defined voltage or current inputs. Adjustable
Change Display Precision Change the display precision, also changes the COV increment, for user defined voltage or current inputs.
Setup When point type is set to Temperature Inputs, this parameter sets the type of sensor used. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Input Range Low When point type is set to Building Pressure Voltage and Current. Sets the voltage or current for the minimum value. Adjustable: 0 to 10, V or mA depending on input
Input Range High When point type is set to Voltage and Current. This parameter sets the voltage or current for the max value. Adjustable: 5 to 20, V or mA depending on input
Voltage Range When point type is set to Building Pressure. This parameter sets the voltage input for the sensor. Adjustable: 0 to 10 V/2 to 10 V/0 to 5 V
Device Type Point type is set to Steam Pressure and assumes the sensor is DPT2090-25G. This parameter sets whether the sensor sends a current or voltage. If it sends voltage, the range is 0-5.5 VDC. If it sends current, the range is 4 to 20 mA. Adjustable: Current/Voltage
Output Range Low Point type set to Building Pressure, Voltage, or Current. Sets the minimum value of the range for the sensor. Adjustable: -100,000 to 100,000
Output Range High Point type set to Building Pressure, Voltage, or Current. Sets the maximum value of the range for the sensor. Adjustable: -100,000 to 100,000
Offset Use this to offset the present value of the analog input. Adjustable: +/-10% of full range (dynamic)
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
Unreliable Sensor Sets the text that is sent when the sensor is unreliable.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: Dynamic based on point type
Low Alarm Limit Shows the value for the Low Alarm Limit.
Alarm Delay Delays the alarm if needed.
Alarm Differential Sets the alarm differential. Adjustable: +/-10% of full range (dynamic)
Trend Enables or disables the trend. Adjustable: Enable/Disable
Interval Sets the interval of the trend samples. Adjustable: 0 s to 900 s
Commissioning: Inputs: Analog Input 7 Point Type Sets what kind of input the point is defined as. Adjustable: Undefined/Temperature/Humidity/CO2/Light Sensor/Refrigerant/Building Pressure/Steam Pressure/Voltage/Current
Description The description of the input. Adjustable
Input The current value of the input; the name of this is reflected in the Description field. Read only
Change Units Change the units for user defined voltage or current inputs. Adjustable
Change Display Precision Change the display precision (also changes the COV increment) for user defined voltage or current inputs.
Setup When point type is set to Temperature Inputs, this sets the type of sensor used. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Input Range Low When point type is set to Building Pressure Voltage and Current. Sets the voltage or current for the minimum value. Adjustable: 0 to 10, V or mA depending on input
Input Range High When point type is set to Voltage and Current. Sets the voltage or current for the max value. Adjustable: 5 to 20, V or mA depending on input
Voltage Range When point type is set to Building Pressure. This sets the voltage input for the sensor. Adjustable: 0 to 10 V/2 to 10 V/0 to 5 V
Device Type Point type is set to Steam Pressure and assumes the sensor is DPT2090-25G. This sets whether the sensor sends a current or voltage. If it sends voltage, the range is 0-5.5 VDC. If it sends current, the range is 4-20 mA. Adjustable: Current/Voltage
Output Range Low Point type set to Building Pressure, Voltage, or Current. Sets the minimum value of the range for the sensor. Adjustable: -100,000 to 100,000
Output Range High Point type set to Building Pressure, Voltage, or Current. Sets the maximum value of the range for the sensor. Adjustable: -100,000 to 100,000
Offset Use this to offset the present value of the analog input. Adjustable: +/-10% of full range (dynamic)
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
Unreliable Sensor Sets the text that is sent when the sensor is unreliable.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: Dynamic based on point type
Low Alarm Limit Shows the value for the Low Alarm Limit.
Alarm Delay Delays the alarm if needed.
Alarm Differential Sets the alarm differential. Adjustable: +/-10% of full range (dynamic)
Trend Enables or disables the trend. Adjustable: Enable/Disable
Interval Sets the interval of the trend samples. Adjustable: 0 s to 900 s
Commissioning: Inputs: Analog Input 8 Point Type Sets what kind of input the point is defined as. Adjustable: Undefined/Temperature/Humidity/CO2/Light Sensor/Refrigerant/Building Pressure/Steam Pressure/Voltage/Current
Description Shows the description of the input. Adjustable
Input Shows the current value of the input; the name of this is reflected in the Description field. Read only
Change Units Change the units for user defined voltage or current inputs. Adjustable
Change Display Precision Change the display precision for user defined voltage or current inputs. Also changes the COV increment.
Setup When point type is set to Temperature Inputs, this sets the type of sensor used. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Input Range Low Point type is set to Building Pressure Voltage and Current. Sets the voltage or current for the minimum value. Adjustable: 0 to 10, V or mA depending on input
Input Range High Point type is set to Voltage and Current. Sets the voltage or current for the max value. Adjustable: 5 to 20, V or mA depending on input
Voltage Range Point type is set to Building Pressure. This sets the voltage input for the sensor. Adjustable: 0 to 10 V/2 to 10 V/0 to 5 V
Device Type Point type is set to Steam Pressure and assumes the sensor is DPT2090-25G. This sets whether the sensor sends a current or voltage. If it sends voltage, the range is 0-5.5 VDC If it sends current, the range is 4-20 mA. Adjustable: Current/Voltage
Output Range Low Point type is set to Building Pressure, Voltage, or Current. Sets the minimum value of the range for the sensor. Adjustable: -100,000 to 100,000
Output Range High Point type is set to Building Pressure, Voltage, or Current. Sets the maximum value of the range for the sensor. Adjustable: -100,000 to 100,000
Offset Use this to offset the present value of the analog input. Adjustable: +/-10% of full range (dynamic)
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
Unreliable Sensor Sets the text that is sent when the sensor is unreliable.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: Dynamic based on point type
Low Alarm Limit Shows the value for the Low Alarm Limit.
Alarm Delay Delays the alarm if needed.
Alarm Differential Sets the alarm differential. Adjustable: +/-10% of full range (dynamic)
Trend Enables or disables the trend. Adjustable: Enable/Disable
Interval Sets the interval of the trend samples. Adjustable: 0 s to 900 s
Commissioning: Inputs: Analog Input 9 Point Type Sets what kind of input the point is defined as. Adjustable: Undefined/Temperature/Humidity/CO2/Light Sensor/Refrigerant/Building Pressure/Steam Pressure/Voltage/Current
Description The description of the input. Adjustable
Input The current value of the input; the name of this is reflected in the Description field. Read only
Change Units Change the units for user defined voltage or current inputs. Adjustable
Change Display Precision Change the display precision for user defined voltage or current inputs. Also changes the COV increment.
Setup When point type is set to Temperature Inputs, this sets the type of sensor used. Adjustable: Nickel/Platinum/A99B/2.25K NTC/10K NTC/10K NTC Type 3
Input Range Low Point type is set to Building Pressure Voltage and Current. Sets the voltage or current for the minimum value. Adjustable: 0 to 10, V or mA depending on input.
Input Range High Point type is set to Voltage and Current. Sets the voltage or current for the maximum value. Adjustable: 5 to 20, V or mA depending on input.
Voltage Range Point type is set to Building Pressure .This sets the voltage input for the sensor. Adjustable: 0 to 10 V/2 to 10 V/0 to 5 V
Device Type Point type is set to Steam Pressure and assumes the sensor is DPT2090-25G. This sets whether the sensor sends a current or voltage. If it sends voltage, the range is 0-5.5 VDC. If it sends current, the range is 4-20 mA. Adjustable: Current/Voltage
Output Range Low Point type set to Building Pressure, Voltage, or Current. Sets the minimum value of the range for the sensor. Adjustable: -100,000 to 100,000
Output Range High Point type set to Building Pressure, Voltage, or Current. Sets the maximum value of the range for the sensor. Adjustable: -100,000 to 100,000
Offset Use this to offset the present value of the analog input. Adjustable: +/-10% of full range (dynamic)
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Text Sets the text that is sent with the alarm for High Alarm Limit. Adjustable
Low Alarm Text Sets the text that is sent with the alarm for Low Alarm Limit.
Unreliable Sensor Sets the text that is sent when the sensor is unreliable.
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: Dynamic based on point type
Low Alarm Limit Shows the value for the Low Alarm Limit.
Alarm Delay Delays the alarm if needed.
Alarm Differential Sets the alarm differential. Adjustable: +/-10% of full range (dynamic)
Trend Enables or disables the trend. Adjustable: Enable/Disable
Interval Sets the interval of the trend samples. Adjustable: 0 s to 900 s
Commissioning: Outputs: Output 1 Description The description of the Output. Adjustable
Output The current state of the Output; the name reflects the description. Read only
Override The ability to override the Output. Adjustable: Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 2 Description The description of the Output. Adjustable
Output The current state of the Output; the name reflects the description. Read only
Override The ability to override the Output. Adjustable:Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 3 Description The description of the Output. Adjustable
Output The current state of the Output; the name reflects the description. Read only
Override The ability to override the Output. Adjustable: Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 4 Description The description of the output. Adjustable
Output The current state of the output; the name reflects the description. Read only
Override The ability to override the output. Adjustable:Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 5 Description The description of the output. Adjustable
Output The current state of the output; the name reflects the description. Read only
Override The ability to override the output. Adjustable: Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 6 Description The description of the output. Adjustable
Output The current state of the output; the name reflects the description. Read only
Override The ability to override the output. Adjustable:Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 7 Description Shows the description of the output. Adjustable
Output Shows the current state of the output; the name reflects the description. Read only
Override The ability to override the output. Adjustable: Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 8 Description The description of the output. Adjustable
Output Shows the current state of the output; the name reflects the description. Read only
Override The ability to override the output. Adjustable:Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Outputs: Output 9 Description The description of the output. Adjustable
Output The current state of the output; the name reflects the description. Read only
Override The ability to override the output. Adjustable: Auto/Off/On
Polarity Field Determines the action of the Output Normal/Reverse
Commissioning: Netsensor Plug and Play: Netsensor 1 Temperature Shows the temperature of the Netsensor at address 199. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the temperature input. Adjustable: -5°F to 5°F
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0°F to 250°F
Low Alarm Limit Shows the value for the Low Alarm Limit. Adjustable: 0°F to 250°F
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0°F to 100°F
Humidity Shows the humidity of the Netsensor at address 199. Read only
Description The description of the Netsensor. Adjustable
Offset Use this to offset the present value of the humidity input. Adjustable: -5 to 5% RH
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0% to 100% RH
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0% to 100% RH
Interval Sets the interval of the trend samples. Adjustable: 1 min to 15 min
Commissioning: Netsensor Plug and Play: Netsensor 2 Temperature Shows the temperature of the Netsensor at address 200. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the temperature input Adjustable: -5°F to 5°F
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0°F to 250°F
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0°F to 100°F
Humidity Shows the humidity of the Netsensor at address 200. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the humidity input. Adjustable: -5 RH to 5% RH
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0% to 100% RH
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0% to 100% RH
Interval Sets the interval of the trend samples. Adjustable: 1 min to 15 min
Commissioning: Netsensor Plug and Play: Netsensor 3 Temperature Shows the temperature of the Netsensor at Address 201. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the temperature input. Adjustable: -5°F to 5°F
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0°F to 250°F
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0°F to 100°F
Humidity Shows the humidity of the Netsensor at address 201 Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the humidity input. Adjustable: -5 to 5% RH
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0% to 100% RH
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0% to 100% RH
Interval Sets the interval of the trend samples. Adjustable: 1 min to 15 min
Commissioning: Netsensor Plug and Play: Netsensor 4 Temperature Shows the temperature of the Netsensor at Address 202 Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the temperature input. Adjustable: -5°F to 5°F
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0°F to 250°F
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0°F to 100°F
Humidity Shows the humidity of the Netsensor at address 202. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the humidity input. Adjustable: -5 to 5% RH
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0% to 100% RH
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0% to 100% RH
Interval Sets the interval of the trend samples. Adjustable: 1 min to 15 min
Commissioning: Netsensor Plug and Play: Netsensor 5 Temperature Shows the temperature of the Netsensor at address 203. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the temperature input. Adjustable: -5°F to 5°F
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0°F to 250°F
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0°F to 100°F
Humidity Shows the humidity of the Netsensor at address 203. Read only
Description Shows the description of the Netsensor. Adjustable
Offset Use this to offset the present value of the humidity input. Adjustable: -5 to 5% RH
Alarm Priority If set to something other than Disable, the object issues alarms. The state set is the priority set for the alarm. Adjustable: Disable/ Critical / Service Priority / Service
High Alarm Limit Shows the value for the High Alarm Limit. Adjustable: 0 to 100% RH
Low Alarm Limit Shows the value for the Low Alarm Limit.
Time Delay Delays the alarm if needed. Adjustable: 0 min to 60 min
Alarm Differential Sets the alarm differential. Adjustable: 0% to 100% RH
Interval Sets the interval of the trend samples. Adjustable: 1 min to 15 min
Controller: Firmware Firmware Status The status of the firmware loaded in the controller. Read only
Calibration Data Fault Appears if proper calibration is not loaded at the factory.
Firmware Main Version Displays the firmware version of the controller.
Application Version Displays the version of the application.
Application Name Displays the name of the application.
Equipment Template Version Displays the version of the template.
Equipment Archive Version Displays the version of the equipment archive.
Equipment View Version Displays the version of the view definition.
Controller: Time Time Shows the time set by the SBH. To change the date and time, go to the Settings > System Setting on the SBH and adjust the date and time.This adjustment syncs to all online devices. Read only
Date Shows the date that the controller is set to.
Time Zone Shows the time zone the controller is adjusting to. Adjustable
Controller: Network Device Name Shows the name of the device on the device list. Adjustable: 30 characters
Device Description Shows the description of the device on the device list.
Device OID BACnet Device OID for the system bus. On a standalone Verasys System, this parameter is not used. If connected to a 3rd party facility management system, the parameter sets the BACnet ID for the zone coordinator. Adjustable: Range: 1 to 4,194,303
Address Shows the address of the controller; the address is adjustable via the SBH and the display on the controller. Adjustable: 0 to 127
Communication Status Shows the status of the zone system bus communication. Read only
FC Comm Mode Set to wired field bus.
Note: This feature is not available yet.
Baud Rate When set to auto, the SBH200 sets the baud rate for the controller. Adjustable: Auto/1200/9600/19200/38400/76800
Operating Baud Rate Shows the baud rate of the controller. Read only
BACnet Encoding Type Shows the encoding type set and the character set that the controller uses. Adjustable: ISO 10646 (UCS-2)/ANSI X3.4 (US-ASCII)/Microsoft DBCS code page 932 (Japanese Shift JIS)/ISO 106464 (UTF-8)
Controller: Misc Language Sets the language of the controller. Read only
Units Sets the units of the controller. Adjustable: Imperial/Metric
Relearn system A relearn system tells the controller that sensors that were removed and are showing as unreliable is intentional. The system resets the reliability status for these points. Adjustable: False/True
Details: Energy Meter 1: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Energy Consumption Shows the electrical meter consumption of all phases since the last reset. Read only
Details: Energy Meter 1: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 1: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption The electrical meter phase consumption since the last reset
Details: Energy Meter 1: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 1: Input 1 Description Shows the description of this pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 1: Input 2 Description Shows the description of this pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 2: System Description Sets the name of the Energy Meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Energy Consumption Shows the electrical meter consumption of all phases since the last reset. Read only
Details: Energy Meter 2: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details:Energy Meter 2: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 2: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 2: Input 1 Description The description of this pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 2: Input 2 Description Shows the description of the pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 3: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Energy Consumption Shows the electrical meter consumption of all phases since the last reset. Read only
Details: Energy Meter 3: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 3: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 3: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meters phase consumption since the last reset.
Details: Energy Meter 3: Input 1 Description Shows the description of the pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 3: Input 2 Description Shows the description of the pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 4: System Description Sets the name of the energy meter. Adjustable
Peak Demand Shows the maximum amount of energy consumed in the demand window time. Read only
Voltage Shows the average voltage of the meter phases.
Current Shows the average current of the meter phases.
Frequency Shows the measured frequency of the signal.
Current Demand Shows the amount of energy consumed in the demand window time.
Energy Consumption Shows the electrical meter consumption of all phases since the last reset. Read only
Details: Energy Meter 4: R Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 4: S Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 4: T Phase Voltage Shows the voltage of the meter phases. Read only
Current Shows the current of the meter phases.
Energy Consumption Shows the electrical meter phase consumption since the last reset.
Details: Energy Meter 4: Input 1 Description Shows the description of the pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Energy Meter 4: Input 2 Description Shows the description of the pulse input. Adjustable
Present Value If present, shows the consumption of the pulse meter hooked to the input. The name of the input is defined by the description. Read only
Details: Inputs: Binary Input 1 Input The name of the input is defined under the Commissioning tab. The valve box displays the current value of the input. Read only
Details: Inputs: Binary Input 2
Details: Inputs: Binary Input 3
Details: Inputs: Binary Input 4
Details: Inputs: Analog Input 5 Input The name of the input is defined under the Commissioning tab. The valve box displays the current value of the input. Read only
Details: Inputs: Analog Input 6
Details: Inputs: Analog Input 7
Details: Inputs: Analog Input 8
Details: Inputs: Analog Input 9
Details: Outputs: Output 1 Output The name of the input is defined under the Commissioning tab. Read only
Details: Outputs: Output 2
Details: Outputs: Output 3
Details: Outputs: Output 4
Details: Outputs: Output 5
Details: Outputs: Output 6
Details: Outputs: Output 7
Details: Outputs: Output 8
Details: Outputs: Output 9
Details: Netsensor Plug and Play: Netsensor 1 Temperature Shows the temperature of the device at address 199. Read only
Humidity Shows the humidity of the device at address 199.
Details: Netsensor Plug and Play: Netsensor 2 Temperature Shows the temperature of the device at address 200. Read only
Humidity Shows the humidity of the device at address 200.
Details: Netsensor Plug and Play: Netsensor 3 Temperature Shows the temperature of the device at address 201. Read only
Humidity Shows the humidity of the device at address 201.
Details: Netsensor Plug and Play: Netsensor 4 Temperature Shows the temperature of the device at address 202. Read only
Humidity Shows the humidity of the device at address 202.
Details: Netsensor Plug and Play: Netsensor 5 Temperature Shows the temperature of the device at address 203. Read only
Humidity Shows the humidity of the device at address 203.
Trends: Inputs: Binary Input 1 Binary Input 1

Total: 25 samples, 1 sample taken every change of value.

Read only
Trends: Inputs: Binary Input 2 Binary Input 2
Trends: Inputs: Binary Input 3 Binary Input 3
Trends: Inputs: Binary Input 4 Binary Input 4
Trends: Inputs: Analog Input 5 Analog Input 5

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
Trends: Inputs: Analog Input 6 Analog Input 6
Trends: Inputs: Analog Input 7 Analog Input 7
Trends: Inputs: Analog Input 8 Analog Input 8
Trends: Inputs: Analog Input 9 Analog Input 9
Trends: Outputs Output 1

Total: 25 samples, 1 sample taken every change of value.

Read only
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Trends: Netsensor 1: Zone Temperature Temperature

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
Trends: Netsensor 1: Zone Humidity Humidity
Trends: Netsensor 2: Zone Temperature Temperature
Trends: Netsensor 2: Zone Humidity Humidity
Trends: Netsensor 3: Zone Temperature Temperature
Trends: Netsensor 3: Zone Humidity Humidity
Trends: Netsensor 4: Zone Temperature Temperature
Trends: Netsensor 4: Zone Humidity Humidity
Trends: Netsensor 5: Zone Temperature Temperature
Trends: Netsensor 5: Zone Humidity Humidity
Trends: Energy Meter 1: System Consumption

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
Demand
Trends: Energy Meter 1: R Phase R Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
R Phase Current
Trends: Energy Meter 1: S Phase S Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
S Phase Current
Trends: Energy Meter 1: T Phase T Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
T Phase Current
Trends: Energy Meter 1: Input 1 Input 1 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 1: Input 2 Input 2 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 2: System Consumption

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
Demand
Trends: Energy Meter 2: R Phase R Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
R Phase Current
Trends: Energy Meter 2: S Phase S Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
S Phase Current
Trends: Energy Meter 2: T Phase T Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
T Phase Current
Trends: Energy Meter 2: Input 1 Input 1 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 2: Input 2 Input 2 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 3: System Consumption

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
Demand
Trends: Energy Meter 3: R Phase R Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
R Phase Current
Trends: Energy Meter 3: S Phase S Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
S Phase Current
Trends: Energy Meter 3: T Phase T Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
T Phase Current
Trends: Energy Meter 3: Input 1 Input 1 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 3: Input 2 Input 2 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 4: System Consumption

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
Demand
Trends: Energy Meter 4: R Phase R Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
R Phase Current
Trends: Energy Meter 4: S Phase S Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
S Phase Current
Trends: Energy Meter 4: T Phase T Phase Voltage

Total: 200 samples, user defined sample interval in Commissioning menu.

Read only
T Phase Current
Trends: Energy Meter 4: Input 1 Input 1 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Trends: Energy Meter 4: Input 2 Input 2 Present Value Total: 25 samples, 1 sample taken every change of value. Read only
Table 8. LC-VAC1001-0 Lighting Controller parameters and objects
Menu Object or Parameter Description Adjustable
Home Page Lighting 1 Circuit Command The current state of configurable output 1. Read only
Lighting 2 Circuit Command The current state of configurable output 2.
Lighting 3 Circuit Command The current state of configurable output 3.
Lighting 4 Circuit Command The current state of configurable output 4.
Lighting 5 Circuit Command The current state of configurable output 5.
Lighting 6 Circuit Command The current state of configurable output 6.
Lighting 7 Circuit Command Thecurrent state of configurable output 7.
Lighting 8 Circuit Command The current state of configurable output 8.
Lighting 9 Circuit Command The current state of configurable output 9.
Alarms Alarms The Alarms tab displays all alarms that are active. Click on all alarms and view alarm history. Read only
Status Unit Status Shows the status of the controller. Read only
Light Level Status Shows the status of the light level.
Light Level Shows the analog light level in ft candles.
Lighting Level Setpoint If the light level is below this setpoint, it is night and if it is above this setpoint plus the differential, it is day. Adjustable: 0.0 ft to 200 ft candles
Lighting Level Differential When transitioning back to day, this parameter sets how many more ft candles are needed to switch to day. Adjustable: 0.0 ft to 100 ft candles
Zone 1 Command Shows the current state of the zone. Read only
Zone 1 Schedule Shows the current state of the zone schedule.
Zone 1 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 1 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 2 Command Shows the current state of the zone. Read only
Zone 2 Schedule Shows the current state of the zone schedule.
Zone 2 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 2 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 3 Command Shows the current state of the zone. Read only
Zone 3 Schedule Shows the current state of the zone schedule.
Zone 3 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 3 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 4 Command Shows the current state of the zone. Read only
Zone 4 Schedule Shows the current state of the zone schedule.
Zone 4 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 4 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 5 Command Shows the current state of the zone. Read only
Zone 5 Schedule Shows the current state of the zone schedule.
Zone 5 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 5 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 6 Command Shows the current state of the zone. Read only
Zone 6 Schedule Shows the current state of the zone schedule.
Zone 6 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 6 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 7 Command Shows the current state of the zone. Read only
Zone 7 Schedule Shows the current state of the zone schedule.
Zone 7 Override The ability to override the zone. In the Auto state, the zone works from the logic setup for the zone. Adjustable: Auto/Off/On
Zone 7 Override Status If the Zone has been placed in temporary override, override status displays here. If not in temp override, the status displays off. Read only
Zone 8 Command Shows the current state of the zone. Read only
Zone 8 Schedule Shows the current state of the zone schedule.
Summary: Network Communication Status The status of the network communication. Read only
Summary: Inputs Light Level Status Shows the status of the light level. Read only
Light Level Shows the analog light level in ft candles.
Summary: Outputs Lighting 1 Circuit Command The command given to current status of configurable output 1. Read only
Lighting 2 Circuit Command The current status of configurable output 2.
Lighting 3 Circuit Command The current status of configurable output 3.
Lighting 4 Circuit Command The current status of configurable output 4.
Lighting 5 Circuit Command The current status of configurable output 5.
Lighting 6 Circuit Command The current status of configurable output 6.
Lighting 7 Circuit Command The current status of configurable output 7.
Lighting 8 Circuit Command The current status of configurable output 8.
Lighting 9 Circuit Command The current status of configurable output 9.
Commissioning: Network Device Name Sets the name of the device Adjustable: 30 characters
Address The address of the controller. This address is adjustable in the SBH and the display on the controller. Adjustable: 4 to 127 characters
Commissioning: Control Setup Lighting Sensor Mode

Sets the logic to determine the mode for the light sensor.

Binary Only: Sets sensor to Day or Night from the binary input.

Analog Only: Sets sensor to Day or Night from the analog input.

Both ON/Both OFF: Uses both the binary and analog inputs. Both ON sets the sensor to Night, and Both off sets the sensor to Day.

Both ON/Analog OFF - Uses both the binary and analog inputs. Both ON sets the sensor to Night and Analog off sets the sensor to Day.

Analog ON/Both OFF - Uses both the binary and analog inputs. Sets the sensor to Night from the analog input. Sets the sensor to Day when set to Both OFF.

Both ON/Any Off - Uses both the binary and analog inputs. Both ON sets the sensor to Night and either binary or analog input sets the sensor to Day.

Adjustable:

Binary Only

Analog Only

Both ON/Both OFF

Both ON/Analog OFF

Analog ON/Both OFF

Both ON/Any OFF

Number of Lighting Circuits Sets the number of circuits that this controller controls. Unused circuits do not show on the screens, except on the trends. Adjustable: 1 to 9
Number of Lighting Zones Sets the number of controller lighting zones. Each zone may control more than one circuit and may have different criteria to turn the zone on. Unused zones do not show on the screens, except on the schedules. Adjustable: 1 to 9

Zone 1 Control Mode

Zone 2 Control Mode

Zone 3 Control Mode

Zone 4 Control Mode

Zone 5 Control Mode

Zone 6 Control Mode

Zone 7 Control Mode

Zone 8 Control Mode

Zone 9 Control Mode

Sets the logic to determine on and off for zones 1 to 9.

Sensor Only: Controls the zone with the logic from the Lighting Sensor Mode. Night turns the zone ON and Day turns the zone OFF.

Schedule Only: Turns the zone on and off from the Zone 1 Schedule.

Both ON/Both OFF: Uses both the sensor and the schedule. Sensor set to Night and Schedule ON sets the zone to ON. Sensor set to Day and Schedule OFF sets the zone to OFF.

Both ON/Schedule OFF: Uses both the sensor and the schedule. Sensor set to Night and Schedule ON sets the zone to ON. Schedule OFF sets the zone to OFF.

Schedule ON/Both OFF: Uses both the sensor and the schedule. Sets the schedule to on. Sensor set to Day and Schedule OFF sets the zone to OFF.

Both ON/Any OFF: Uses both the sensor and the schedule. Sensor set to Night and Schedule ON sets the zone to ON. The sensor set to Day or the schedule set to OFF sets the zone to OFF.

Adjustable:

Sensor Only

Schedule Only

Both ON/Both OFF

Both ON/Schedule OFF

Schedule ON/Both OFF

Both ON/Any OFF

Commissioning: Control Setup (continued) Lighting Circuit 1 Zone Select Select which zone associates with lighting circuit 1. Adjustable: Zone 1/Zone2/Zone 3/Zone 4/Zone 5/Zone 6/Zone 7/Zone 8/Zone 9
Lighting Circuit 2 Zone Select Select which zone associates with lighting circuit 2.
Lighting Circuit 3 Zone Select Select which zone associates with lighting circuit 3.
Lighting Circuit 4 Zone Select Select which zone associates with lighting circuit 4.
Lighting Circuit 5 Zone Select Select which zone associates with lighting circuit 5.
Lighting Circuit 6 Zone Select Select which zone associates with lighting circuit 6.
Lighting Circuit 7 Zone Select Select which zone associates with lighting circuit 7. Adjustable: Zone 1/Zone2/Zone 3/Zone 4/Zone 5/Zone 6/Zone 7/Zone 8/Zone 9
Lighting Circuit 8 Zone Select Select which zone associates with lighting circuit 8.
Lighting Circuit 9 Zone Select Select which zone associates with lighting circuit 9.
Circuit 1 Command Polarity

Sets whether the command for ON is 24V or 0V:

Normal: 24V = On

Reverse: 0V = On

Adjustable: Normal/Reverse
Circuit 2 Command Polarity
Circuit 3 Command Polarity
Circuit 4 Command Polarity
Circuit 5 Command Polarity
Circuit 6 Command Polarity
Circuit 7 Command Polarity
Circuit 8 Command Polarity
Circuit 9 Command Polarity
Zone 1 Override is Momentary Switches the input from Maintained to Momentary. Adjustable: True/False
Zone 1 Override Duration Set the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Zone 2 Override is Momentary Switches the input from Maintained to Momentary. Adjustable: True/False
Zone 2 Override Duration Set the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Zone 3 Override is Momentary Switches the input from Maintained to Momentary. Adjustable: True/False
Zone 3 Override Duration Sets the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Zone 4 Override is Momentary Switches the input from

Maintained to Momentary.

Adjustable: True/False
Zone 4 Override Duration Sets the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Zone 5 Override is Momentary Switches the input from Maintained to Momentary. Adjustable: True/False
Zone 5 Override Duration Sets the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Zone 6 Override is Momentary Switches the input from Maintained to Momentary. Adjustable: True/False
Zone 6 Override Duration Sets the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Zone 7 Override is Momentary Switches the input from Maintained to Momentary. Adjustable: True/False
Zone 7 Override Duration Set the override duration for the zone when the Momentary switch or button is triggered. Adjustable: 1 min to 240 min
Controller: Firmware Firmware Status Shows the status of the firmware on the controller. Read only
Firmware Version Displays the firmware version of the controller.
Application Version Displays the version of the application.
Controller: Time Time Shows the time that is set by the SBH. To change the date and time, go to the Settings > System Settings on the SBH and adjust the date and time. This adjustment syncs to all online devices. Read only
Date Shows the date that the controller is set to.
Time Zone Shows the time zone the controller adjusts to. Adjustable
Controller: Network Device Name The name of the device on the device list. Adjustable: 30 characters
Device Description The description of the device on the device list.
Device OID This is the BACnet Device OID for the system bus. If on a standalone Verasys System, this parameter is not used. If connected to a 3rd party facility management system, it sets the BACnet ID for the zone coordinator. Adjustable: Range: 1 to 4,194,303
Address The address of the controller. This address is adjustable via the SBH and the display on the controller. Adjustable: 0 to 127
Communication Status The status of the zone bus communication. Read only
FC COMM Mode Set to wired field bus.
Note: This feature is not available yet.
Adjustable
Baud Rate When set to auto, the SBH200 sets the baud rate for the controller. Adjustable: Auto/1200/9600/19200/38400/76800
Operating Baud Rate Shows the baud rate of the controller Read only
BACnet Encoding Type The encoding type set and the character set that the controller uses Adjustable: ISO 10646 (UCS-2)/ANSI X3.4 (US-ASCII)/Microsoft DBCS code page 932 (Japanese Shift JIS)/ISO 106464 (UTF-8)
Controller: Misc Language Sets the language of the controller Read only
Units Sets the units of the controller Adjustable: Imperial/Metric
Display Contrast Sets the contrast for the display Adjustable: 2 to 6
Unit Serial Number The ability to document a serial number or string Adjustable: 30 characters
Model Name The model name of the controller Read only
Details: Lighting Control Unit Status The status of the controller Read only
Flash    
Details: Inputs Light Level Status The status of the binary input. Read only
Light Level The value of the analog input.
Zone 1 Override Input The value of the binary input.
Zone 2 Override Input
Zone 3 Override Input
Zone 4 Override Input
Zone 5 Override Input
Zone 6 Override Input
Zone 7 Override Input
Details: Output Lighting 1 Circuit Command The command given to configurable output 1. Read only
Lighting 1 Circuit Override The ability to override lighting circuit 1. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 2 Circuit Command The command given to configurable output 2 Read only
Lighting 2 Circuit Override The ability to override lighting circuit 2. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 3 Circuit Command The command given to configurable output 3. Read only
Lighting 3 Circuit Override The ability to override lighting circuit 3. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 4 Circuit Command The command given to configurable output 4. Read only
Lighting 4 Circuit Override The ability to override lighting circuit 4. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 5 Circuit Command The command given to configurable output 5. Read only
Lighting 5 Circuit Override The ability to override lighting circuit 5. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 6 Circuit Command The command given to configurable output 6. Read only
Lighting 6 Circuit Override The ability to override lighting circuit 6. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 7 Circuit Command The command given to configurable output 7. Read only
Lighting 7 Circuit Override The ability to override lighting circuit 7. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 8 Circuit Command The command given to configurable output 8. Read only
Lighting 8 Circuit Override The ability to override lighting circuit 8. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Lighting 9 Circuit Command The command given to configurable output 9. Read only
Lighting 9 Circuit Override The ability to override lighting circuit 9. In the Auto state, the circuit uses the logic setup for the zone. Adjustable: Auto/Off/On
Details: Change Name Zone x Name You can change the name of each zone. Adjustable
Circuit x Name You can change the name of each circuit. Adjustable
Trends Light Level Status Total: 10 samples, 1 sample taken every change of value. Read only
Light Level 100 samples are taken every 15 minutes.
Lighting 1 Circuit Command Total: 10 samples, 1 sample taken every change of value. Read only
Lighting 2 Circuit Command Total: 10 samples, 1 sample taken every change of value.
Lighting 3 Circuit Command
Lighting 4 Circuit Command
Lighting 5 Circuit Command
Lighting 6 Circuit Command
Lighting 7 Circuit Command
Lighting 8 Circuit Command
Lighting 9 Circuit Command