Use the local display or MAP Gateway to set up the device addresses. Verasys application controllers are master devices on MS/TP sensor buses. Before operating field controllers on a bus, you must set a valid and unique device address for each controller on the bus through the local display or MAP gateway. Device addresses 4 through 127 are the valid addresses for these controllers.
Refer to the Verasys BACnet MS/TP Communications Technical Bulletin (LIT-12012362) for more information on field controller device addresses and how to set them on MS/TP buses.
Device Address |
Use on Description |
---|---|
0 |
Reserved for system bus supervisory controller. Not for use on field controllers |
1 to 3 |
Reserved for peripheral devices. Not for use on field controllers |
117 |
Reserved for the Smart Building Hub |
4 to 127 |
Used for MS/TP devices (field controllers) that are hard-wired to an sensor bus or system bus |