Setting the Device Addresses - Verasys - VAC1000 - VAC1001 - VAC1002

Verasys 18 Point 24 VAC Application Controller Installation Guide

Brand
Verasys
Product name
VAC1000
VAC1001
VAC1002
Document type
Installation Guide
Part number
24-10143-01477
Document revision
C
Revision date
2021-06-02
Language
English

Use the local display or MAP Gateway to set up the device addresses. Verasys application controllers are master devices on MS/TP sensor buses. Before operating field controllers on a bus, you must set a valid and unique device address for each controller on the bus through the local display or MAP gateway. Device addresses 4 through 127 are the valid addresses for these controllers.

Refer to the Verasys BACnet MS/TP Communications Technical Bulletin (LIT-12012362) for more information on field controller device addresses and how to set them on MS/TP buses.

Table 1. System Bus Device Address Description

Device Address

Use on Description

0

Reserved for system bus supervisory controller. Not for use on field controllers

1 to 3

Reserved for peripheral devices. Not for use on field controllers

117

Reserved for the Smart Building Hub

4 to 127

Used for MS/TP devices (field controllers) that are hard-wired to an sensor bus or system bus