Important: Do not connect supply power to the ZFR1825 Coordinator before finishing wiring and checking all wiring connections. Short circuits or improperly connected wires may result in permanent damage to the ZFR1825 Coordinator.
Important: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations. The ZFR1825 Coordinator is a low-voltage (less than 30 VAC) device. Do not exceed the ZFR1825 Coordinator’s electrical ratings.
Important: Prevent any static electric discharge to the ZFR1825 Coordinator. Static electric discharge can damage the ZFR1825 Coordinator and void any warranties.
Important:
Do not connect the ZFR1825 Coordinator to the power supply before setting the PAN OFFSET switches.
Follow these guidelines when wiring a ZFR1825 Coordinator:
- Route the wires at least 50 mm (2 in.) away from the vent slots on the sides of the ZFR1825 Coordinator housing.
- Provide slack in the wires. Keep wires routed neatly around the ZFR1825 Coordinator to promote good ventilation, Light-Emitting Diode (LED) visibility, and ease of service.