The Network Optimize/Reform Button allows the ZFR1825 Coordinator to use any of three functions:
- Signal Strength
- Network Optimize
- Network Reform
Use the Signal Strength mode to aid in signal strength testing. Signal Strength mode causes the LEDs on the ZFR Pro routers to turn on and display signal strength for two hours.
Use the Network Optimize mode to clear the mesh device routing tables of the ZFR Pro Routers and attempt to find shorter and/or stronger signal paths to the ZFR1825 Coordinator.
Note: The Network Optimize process can take up to 15 minutes to complete.
Use the Network Reform if new ZFR Pro or WRZ devices are failing to join the ZFR Pro Mesh network. Refer to the Verasys Wireless Pro System Technical Bulletin (LIT-12012940) for more information about the Network Reform function.
1 Once the
Signal Strength LED begins blinking rapidly, release the button
(between 5 to 10 seconds).
2 Once
the Signal Strength LED stops blinking rapidly and stays ON,
release the button (approximately 10 seconds).