Important: Ensure that the PAN Offset switches are set to the same value for the ZFR1825 Coordinator and each associated ZFR Pro Router, TEC3000, and WRZ Series Sensor in a mesh network.
Important:
To avoid wireless mesh network conflicts, do not connect the ZFR1825 Coordinator to the power supply before setting the PAN Offset switches.
Set the PAN Offset value of the ZFR1825 Coordinator using the Dual Inline Package (DIP) switches to configure the ZFR1825 Coordinator to communicate with the ZFR Pro Routers and TEC3000 thermostats assigned to it. See Figure 1 and Figure 1.
The PAN Offset value equals the sum of the numbers set to ON. For example, if the DIP switches labeled1, 4, and 8 are set to ON, the PAN Offset value is 13 (1 + 4 + 8 = 13).
When selecting a PAN Offset value for a wireless system:
- Use a unique PAN Offset value for each wireless mesh network at a job site.
- Use the same PAN Offset value for each wireless device in a wireless mesh network - the ZFR1825 Coordinator and each associated ZFR Pro Router, TEC3000, and WRZ Series Sensor.