Occupied mode - Verasys - LC-BYP200-0 - LC-ZEC310-0 - Field Device - BYP200 - ZEC310

Verasys ZEC310 Zone Damper and BYP200 Bypass Damper Controllers Installation Guide

Brand
Verasys
Product name
BYP200
ZEC310
Document type
Installation Guide
Part number
24-10143-1248
Document revision
D
Revision date
2019-07-01
Language
English
  • The zone damper controller monitors supply air temperature.
  • When the zone temperature rises above the Occupied Cooling Setpoint, the primary air damper modulates open from Damper Cooling Min Position to Damper Max Position.
  • When the zone temperature drops below the Occupied Heating Setpoint, the primary air damper modulates from Damper Heating Min Position to Damper Max Position.
  • If the supply air does not satisfy the cooling or heating requirements, the primary air damper remains at the Damper Satisfied Min Position.