About this task
The Network Reset function resets Wi-Fi and Ethernet settings. Use this function when you forget your Wi-Fi connection information. To reset the Wi-Fi and Ethernet settings, complete the following steps:
Procedure
- Press and hold the RESET button for two seconds. The FAULT LED flickers slowly.
- Release the RESET button within three seconds. The FAULT LED continues to flicker slowly.
- Within five seconds, press the RESET button again, and then immediately release it to confirm that you want to reset Wi-Fi and Ethernet settings. If you do not press the reset button to confirm within five seconds, the reset operation is canceled.
Results
Result: The Wi-Fi SSID and passphrase and Ethernet are set to factory defaults. The LEDs stop flickering for two seconds, then the LEDs return to normal operation based on the current state of the device.
See Table 1 for more information about LED designations and flicker behavior.