CO2 DCV uses up to four wall-mounted CO2 sensors to monitor CO2 levels. This ensures the zone receives high Indoor Air Quality (IAQ). The sensor measures CO2 levels on a scale of 0 to 2,000 parts per million (ppm). When the CO2 sensor with the highest CO2 reading detects that CO2 levels in the zone are above the setpoint (such as caused by a high number of occupants within the zone), the zone damper opens, to allow more outside air into the zone. Enable CO2 DCV in the Zone Setup screen of the System Manager or Zone Coordinator. Refer to the Verasys System User’s Guide (LIT-12012371) for more information.