The 24 VAC supply power terminal block is a gray, removable, 2-terminal plug that fits into a board-mounted jack on the upper left of the ZEC controller. Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug.
Figure 1. VAC Supply power terminal block wiring
Callout | Description |
---|---|
1 |
Supply power terminal block jack |
2 |
Supply power terminal block plug |
3 |
Wires from Johnson Controls 90 VAC to 24 VAC, Class 2, power transformer |
Important: The 24 VAC power should not be shared with other network devices.
Sharing power with other network devices may cause noise, interference, and ground loop
problems. You may damage the controller by sharing power with other devices.