Table 1 provides information about terminal block functions, ratings, and requirements.
In addition to the guidelines in Table 1, follow these guidelines when wiring the System/Zone Buses and supply power:
- Run all low-voltage wiring and cables separate from high-voltage wiring.
- All FC and SA Bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.
- Use Shielded cable for all FC and SA Bus cables.
- Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011670) for detailed information regarding wire size and cable length requirements for the Zone Bus.