Table 1. Manufacturer damper data
Manufacturer Default direction to close
Environmental Technologies Inc. Clockwise
Krueger Counterclockwise
Titus Counterclockwise
Tuttle and Bailey® Counterclockwise
Table 2. Quickfill defaults
Box duct size Area (sq ft) Pickup gain (sq ft)
ETI with a 45 degree rotation ETI with a 90 degree rotation Krueger Tuttle and bailey Titus
4 0.09 1.71 1.63 2.32 2.80 1.63
5 0.14 1.69 1.66 2.31 3.00 1.95
6 0.20 1.67 2.90 2.32 2.90 3.07
7 0.27 n/a n/a 2.32 3.00 2.57
8 0.35 1.61 2.52 2.33 2.90 2.39
9 0.44 n/a n/a 2.33 n/a 2.30
10 0.55 1.63 2.41 2.32 3.00 2.31
12 0.79 1.61 2.38 2.32 3.00 2.76
14 1.07 1.59 2.29 2.33 3.00 2.02
16 1.40 1.61 2.29 2.33 3.00 2.12
18 n/a 1.59 2.43 n/a 3.00 n/a
19 n/a n/a 2.92 n/a n/a n/a
20 0.78 1.61 n/a n/a n/a 2.19
22 0.78 1.60 2.65 2.33 3.00 2.19
24 n/a n/a n/a n/a n/a n/a
26 1.00 n/a n/a n/a n/a 2.57
30 n/a n/a n/a n/a 3.00 n/a
40 2.67 n/a n/a n/a n/a 2.22