Load Diversity - Verasys - LIT-12012331 - General System Information - Verasys System - 5.0

Verasys System Changeover Bypass Zoning System Design Application Note

Brand
Verasys
Product name
Verasys System
Document type
Application Note
Document number
LIT-12012331
Version
5.0
Revision date
2023-09-25
Language
English

When you create your COBP Zoning System design, do not mix interior zones that require cooling all year with exterior zones that may only require constant heating during the winter months. Group similar loads on an individual RTU, and use more than one zoning system if necessary. Use separate constant volume RTUs for special loads.