About this task
When the SBH300 is connected to a MS/TP network through a wired connection or a wireless TMR connection, you can access Verasys controllers and third-party BACnet MS/TP devices. The SBH300 connects to the MS/TP network through the System Bus.
To view a device on the network to see its setpoints, alarms, and other parameters, use a web-enabled device with a supported internet browser connected to the SBH300 Wi-Fi network.
Procedure
- To connect the SBH300 to the Verasys System, use the four-terminal System Bus port. Wire the System Bus communications to the blue four-terminal connector.
- If the SBH is at the end of a line, set the end-of-line (EOL) switch to ON.
- Connect the Wi-Fi adapter to one of the USB ports.