Before you begin

To power the SBH300 with a locally sourced 24 VDC power supply, use the following power supply equipment:
  • Dedicated nominal 24 VDC output, capable of at least 30W.
  • Connector barrel with a 5.5 mm outer sleeve and 2.1 mm inner sleeve, wired for center positive polarity.

Procedure

  1. Connect the center of the barrel to the DC+ and outer barrel to the DC- of the power supply.
  2. Connect the DC plug of the power supply to the power supply port of the SBH300.
  3. Connect the power supply to the power cord.
  4. Connect the power cord to an outlet supplying voltage that matches the input voltage marked on the power supply.