The following table shows the alarms that you can configure for the different inputs.
Name (Reference name) |
Alarm type | Event description | Availability condition |
---|---|---|---|
Binary Input x Mismatch Alarm (x = 1 to 4) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current state of the binary input does not match the user-defined alarm state. Alarm: This state indicates that the current state of the binary input matches the user-defined alarm state. |
Alarm Priority != Disable |
Analog Input x Low Alarm (x = 5 to 9) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the analog input is greater than or equal to the user-defined low limit value. Alarm: This state indicates that the current value of the analog input is less than the user-defined low limit value. |
Alarm Priority != Disable |
Analog Input x High Alarm (x = 5 to 9) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the analog input is less than or equal to the user-defined high limit value. Alarm: This state indicates that the current value of the analog input is greater than the user-defined high limit value. |
Alarm Priority != Disable |
Analog Input x Unreliable Alarm (x = 5 to 9) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the analog input is reliable. Alarm: This state indicates that the current value of the analog input is unreliable. |
- |
Netsensor x Temperature Low Alarm (x = 199 to 206) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the SA bus temperature sensor is greater than or equal to the user-defined low limit value. Alarm: This state indicates that the current value of the SA bus temperature sensor is less than the user-defined low limit value. |
Alarm Priority != Disable |
Netsensor x Humidity Low Alarm (x = 199 to 206) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the SA bus humidity sensor is greater than or equal to the user-defined low limit value. Alarm: This state indicates that the current value of the SA bus humidity sensor is less than the user-defined low limit value. |
Alarm Priority != Disable |
Netsensor x Temperature High Alarm (x = 199 to 206) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the SA bus temperature sensor is less than or equal to the user-defined high limit value. Alarm: This state indicates that the current value of the SA bus temperature sensor is greater than the user-defined high limit value. |
Alarm Priority != Disable |
Netsensor x Humidity High Alarm (x = 199 to 206) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the SA bus humidity sensor is less than or equal to the user-defined high limit value. Alarm: This state indicates that the current value of the SA bus humidity sensor is greater than the user-defined high limit value. |
Alarm Priority != Disable |
Netsensor x CO2 Low Alarm (x = 199 to 206) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the SA bus CO2 sensor is greater than or equal to the user-defined low limit value. Alarm: This state indicates that the current value of the SA bus CO2 sensor is less than the user-defined low limit value. |
Alarm Priority != Disable |
Netsensor x CO2 High Alarm (x = 199 to 206) |
User configurable (Critical/Service Priority/Service) |
Normal: This state indicates that the current value of the SA bus CO2 sensor is less than or equal to the user-defined high limit value. Alarm: This state indicates that the current value of the SA bus CO2 sensor is greater than the user-defined high limit value. |
Alarm Priority != Disable |