Attribute | Object type | Object Id | Enum set / range | Writeable |
---|---|---|---|---|
Unit status | MV | 29500 |
0 = Idle 1 = SD Alarm 2 = Purge Command 3 = Self Test … |
False |
Time zone | MV | 29501 |
1 = (UTC+00:00) Monrovia, Reykjavik 2 = (UTC+00:00) Greenwich Mean Time: Dublin, Edinburgh, Lisbon, London 3 = (UTC+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna 4 = (UTC+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague ... |
True |
Language | MV | 29502 |
1 = Czech (Czech Republic) 2 = Chinese (China) 3 = Danish (Denmark) 4 = Dutch (Belgium) ... |
True |
Units | MV | 29503 |
0 = IP 1 = SI |
True |
FCB Baud Rate | MV | 29504 |
0 = Auto 1 = 1200 2 = 9600 3 = 19200 … |
True |
Supply Fan Status BI | MV | 29506 |
0 = Off 1 = On |
False |
Purge BI | MV | 29507 |
0 = Normal Operation 1 = Purge |
False |
Filter Status BI | MV | 29508 |
0 = Clean 1 = Dirty |
False |
Service Alarm | MV | 29509 |
0 = Normal 1 = Alarm |
False |
Low Temperature Limit Fault BI | MV | 29510 |
0 = Normal 1 = Alarm |
False |
Zone Occupancy | MV |
29511 |
0 = Occupied 1 = Unoccupied 2 = Not Set |
False |
Occupancy Sensor BI | MV | 29512 |
0 = Unoccupied 1 = Occupied |
False |
Temporary Occupancy | MV | 29513 |
0 = Normal 1 = Trigger |
True |
Supply Fan BO | MV | 29514 |
0 = Off 1 = On |
False |
Cooling Stage 1 BO | MV | 29515 |
0 = Off 1 = On |
False |
Cooling Stage 2 BO | MV | 29516 |
0 = Off 1 = On |
False |
Cooling Stage 3 BO | MV | 29517 |
0 = Off 1 = On |
False |
Cooling Stage 4 BO | MV | 29518 |
0 = Off 1 = On |
False |
Heating Stage 1 BO | MV | 29519 |
0 = Off 1 = On |
False |
Heating Stage 2 BO | MV | 29520 |
0 = Off 1 = On |
False |
Heating Stage 3 BO | MV | 29521 |
0 = Off 1 = On |
False |
Heating Stage 4 BO | MV | 29522 |
0 = Off 1 = On |
False |
Compressor Stage 1 BO | MV | 29523 |
0 = Off 1 = On |
False |
Compressor Stage 2BO | MV | 29524 |
0 = Off 1 = On |
False |
Reversing Valve BO | MV | 29526 |
0 = Off 1 = On |
False |
Reversing Valve Polarity | MV | 29527 |
0 = Normally Heat 1 = Normally Cool |
True |
Hot Gas Bypass Valve BO | MV | 29528 |
0 = Off 1 = On |
False |
Supp Heating Stage 1 BO | MV | 29529 |
0 = Off 1 = On |
False |
Supp Heating Stage 2 BO | MV | 29530 |
0 = Off 1 = On |
False |
Humidifier BO | MV | 29531 |
0 = Off 1 = On |
False |
OAT Cooling Lockout Enabled | MV | 29532 |
0 = Disable 1 = Enable |
True |
OAT Heating Lockout Enabled | MV | 29533 |
0 = Disable 1 = Enable |
True |
Rotate Cooling Stage | MV | 29534 |
0 = Normal 1 = Trigger |
True |
Rotate Enable | MV | 29535 |
0 = Disable 1 = Enable |
True |
Rotate Heating Stage | MV | 29536 |
0 = Normal 1 = Trigger |
True |
Load Shed Active | MV | 29537 |
0 = No 1 = Yes |
False |
Econ Fault Active | MV | 29538 |
0 = Normal 1 = Alarm |
False |
Air Temperature Sensor Fault | MV | 29539 |
0 = Normal 1 = Alarm |
False |
Econ Operational Fault | MV | 29540 |
0 = Normal 1 = Alarm |
False |
Econ Not Operational Fault | MV | 29541 |
0 = Normal 1 = Alarm |
False |
Econ Excessive Outside Air | MV | 29542 |
0 = Normal 1 = Alarm |
False |
Damper Modulation Fault | MV | 29543 |
0 = Normal 1 = Alarm |
False |
Cooling Ineffective Alarm | MV | 29544 |
0 = Normal 1 = Alarm |
False |
Heating Ineffective Alarm | MV | 29545 |
0 = Normal 1 = Alarm |
False |
Fan Runtime Alarm | MV | 29546 |
0 = Normal 1 = Alarm |
False |
Fan Runtime Reset | MV | 29547 |
0 = Off 1 = Reset |
True |
Occupancy Override | MV | 29548 |
0 = Occupied 1 = Unoccupied 2 = Bypass 3 = Standby 4 = Not Set |
True |
Device Address | AV | 29500 | 4 to 127 | True |
Device Object ID | AV | 29501 | 0 to 4194302 | True |
Mixed Air Damper Position AI | AV | 29502 | 0% to 00% | False |
Outdoor Air Temperature Sensor AI | AV | 29503 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Operational Outdoor Air Temperature | AV | 29504 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Supply Air Temperature AI | AV | 29505 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Mixed Air Temperature AI | AV | 29506 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Return Air Temperature AI | AV | 29507 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Zone Temperature | AV | 29508 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Setpoint Adjust | AV | 29509 | -5°F to 5°F (-20°C to -15°C) | False |
Zone Humidity | AV | 29510 | 0% to 100%RH | False |
Zone Humidity AI | AV | 29511 | 0% to 100%RH | False |
Zone Quality | AV | 29512 | 0 to 2000 ppm | False |
Return CO2 Sensor AI | AV | 29513 | 0 to 2000 ppm | False |
Supply Fan Speed AO | AV | 29514 | 0% to 100% | False |
Mixed Air Damper AO | AV | 29515 | 0% to 100% | False |
Minimum OA Damper AO | AV | 29516 | 0% to 100% | False |
Cooling % Command | AV | 29517 | 0% to 100% | False |
Heating % Command | AV | 29518 | 0% to 100% | False |
Heat Pump % Command | AV | 29519 | 0% to 100% | False |
Humidification AO | AV | 29520 | 0% to 100% | False |
Warm/Cool Adjust Range | AV | 29521 | 0.01°F to 5°F (-17.7°C to -15°C) | True |
Temperature Setpoint | AV | 29522 | 60°F to 85°F (15.5°C to 29.4°C) | True |
Deadband | AV | 29523 | 1°F to 7°F (-17.2°C to -13.8°C) | True |
Effective Cooling Setpoint | AV | 29524 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Unocc Cooling Setpoint | AV | 29525 | 60°F to 85°F (15.5°C to 29.4°C) | True |
Standby Cooling Setpoint | AV | 29526 | 60°F to 85°F (15.5°C to 29.4°C) | True |
Effective Heating Setpoint | AV | 29527 | -50°F to 250°F (-45.6°C to 121.1°C) | False |
Standby Heating Setpoint | AV | 29528 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
Unocc Heating Setpoint | AV | 29529 | 60°F to 85°F (15.5°C to 29.4°C) | True |
Temp Occupancy Time | AV | 29530 | 0 to 240 minutes | True |
Fan Only Speed | AV | 29531 | 0% to 100% | True |
Min Fan Speed | AV | 29532 | 0% to 100% | True |
Max Fan Speed | AV | 29533 | 0% to 100% | True |
Clg Stage 1 Speed | AV | 29534 | 0% to 100% | True |
Clg Stage 2 Speed | AV | 29535 | 0% to 100% | True |
Clg Stage 3 Speed | AV | 29536 | 0% to 100% | True |
Clg Stage 4 Speed | AV | 29537 | 0% to 100% | True |
Htg Stage 1 Speed | AV | 29538 | 0% to 100% | True |
Htg Stage 2 Speed | AV | 29539 | 0% to 100% | True |
Htg Stage 3 Speed | AV | 29540 | 0% to 100% | True |
Htg Stage 4 Speed | AV | 29541 | 0% to 100% | True |
Minimum OA Percent | AV | 29542 | 0% to 100% | True |
Economizer Switchover Setpoint | AV | 29543 | 40°F to 80°F (4.4°C to 26.6 °C) | True |
Low Limit Temp Setpt | AV | 29544 | 40°F to 80°F (4.4°C to 26.6 °C) | True |
Supply Air Low Limit Setpoint | AV | 29545 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
CO2 Reset A | AV | 29546 | 0 to 2000 ppm | True |
CO2 Reset B | AV | 29547 | 0 to 2000 ppm | True |
Min Pos High Setpoint | AV | 29548 | 0% to 100% | True |
Failsoft Cooling Value | AV | 29549 | 0% to 100% | True |
Failsoft Heating Value | AV | 29550 | 0% to 100% | True |
OA Cooling Lockout Setpoint | AV | 29551 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
OA Heating Lockout Setpoint | AV | 29552 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
Supply Air Setpoint Cooling Min | AV | 29553 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
Supply Air Setpoint Heating Max | AV | 29554 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
Cooling Min On Time | AV | 29555 | 0 to 3600 seconds | True |
Cooling Min Off Time | AV | 29556 | 0 to 3600 seconds | True |
Interstage On Delay Time | AV | 29557 | 30 to 900 seconds | True |
Interstage Off Delay Time | AV | 29558 | 30 to 900 seconds | True |
Heating Min On Time | AV | 29559 | 30 to 1800 seconds | True |
Heating Min Off Time | AV | 29560 | 30 to 1800 seconds | True |
Low OA Lockout Setpoint | AV | 29561 | -50°F to 250°F (-45.6°C to 121.1°C) | True |
Compressor Min On Time | AV | 29562 | 30 to 1800 seconds | True |
Compressor Min Off Time | AV | 29563 | 30 to 1800 seconds | True |
Supp Min On Time | AV | 29564 | 30 to 1800 seconds | True |
Supp Min Off Time | AV | 29565 | 30 to 1800 seconds | True |
Humidity Setpoint | AV | 29566 | 0% to 100%RH | True |
Dehumidification Setpoint | AV | 29567 | 0% to 100%RH | True |
Load Shed Adjust | AV | 29568 | 0°F to 5°F (-17.7°C to -15°C) | True |
Load Shed Rate Limit | AV | 29569 | 0°F to 1°F /min (-17.7°C to -17.2°C /min) | True |
Damper Pos Error | AV | 29570 | 0% to 100% | True |
Damper Min Pos Fault Tolerance | AV | 29571 | 0% to 100% | True |
Econ Fault Delay | AV | 29572 | 5 to 60 minutes | True |
Heat Cool Alarm Differential | AV | 29573 | 0°F to 5°F (-17.7°C to -15°C) | True |
Heat Cool Alarm Delay | AV | 29574 | 5 to 60 minutes | True |
Fan Runtime | AV | 29575 | 0 to 20000 hours | False |
SF Alarm Delay | AV | 29576 | 60 to 1200 seconds | True |
Fan Runtime Limit | AV | 29577 | 0 to 20000 hours | True |