About this task

The BACnet IP Broadcast Management Device (BBMD) facilitates an SBH on one subnet to communicate with a supervisory device on another subnet.

To set up the router feature for the BBMD, complete the following steps on the SBH and the supervisor:

Procedure

  1. On the SBH, navigate to Settings > BBMD.
  2. Configure the following for each BBMD:
    • IP Address: the IP address of the supervisor that the BBMD communicates with.
    • UDP Port: the UDP port number of the supervisor that the BBMD communicates with. It is different from the UDP port of the SBH itself.
    • IP Broadcast Mask: ensure that it matches on both the SBH and the supervisor.