Automatic calculation - Titus - LIT-12014051 - Valve - Venturi Valve

Titus Venturi Air Valve Installation Guide

Brand
Titus
Product name
Venturi Valve
Document type
Installation Guide
Document number
LIT-12014051
Revision date
2023-04-05
Language
English

About this task

The calc button opens a calculation dialog box where you can enter the sensor pressure range and output voltages.

Procedure

  1. To enable to automatic calculation, click the Calc button.
  2. To calculate the gain and offset values automatically, click the Compute button. The values are entered into the Gain PressSens and Offset PressSens boxes.
  3. If the values entered are correct, click the Set PressSens Gain and Set PressSens Offset button to send the values to the controller.