For applications using a 4–20 mA P499A transducer (Figure 1), you must:

  • set P.266 and P.267 to 0
  • set the AI2 mode switch position to I (see VFD68Bxx and VFD68Cxx Drives)
  • calculate and change the C x parameters based on the desired operating pressure range for the condensing fans on your application
    Figure 1. Wiring a 4–20 mA Input Signal Transducer

    Table 1. Settings for Single 4–20 mA Transducer
    Setting Single Transducer, 4–20 mA
    P. 73 1 N/A
    P.266 1 0 (current input)
    P.267 1 0 (4–20 mA)
    Analog Input Terminal AI2
    AI2 Mode Switch2 I
1 For information on parameters, see Table 1.
2 See Figure 1.