About this task

To restart the motor after a controlled stop, disconnect the supply power from the drive for at least 30 seconds and then reconnect the supply power to the drive.

If it is not easy to disconnect the supply power from the drive, follow these steps:

Procedure

  1. Disconnect the jumper between the SD and STF terminals on the low-voltage terminal blocks.
  2. Verify that the SINK/SOURCE jumper to the left of the low-voltage terminal blocks (Figure 1) is set to SINK.
  3. Press MODE until PU PU appears on the display.
  4. Press Up until OP.nd EXT appears on the display.
  5. Press MODE until 0.00 MON EXT appears on the display.
  6. Reconnect the jumper between the SD and STF terminals.

    The VFD68 is now commissioned, is in the external operation mode, and is ready to run the motor using the analog inputs.

  7. Press MODE to return to monitor mode. 0.00 MON PU appears on the screen.