VFD68Bxx and VFD68Cxx Drives - PENN Controls - VFD68Bxx - VFD68Cxx - VFD68Dxx - Three‐Phase Motor Speed Controller - VFD68 Three‐Phase Variable Frequency Drive

VFD68 Variable Frequency Drives Technical Bulletin

Brand
PENN Controls
Product name
VFD68 Three‐Phase Variable Frequency Drive
Document type
Technical Bulletin
Part number
24-7664-3051
Document revision
C
Revision date
2019-08-09
Language
English

About this task

Verify that the VFD68 is in PU mode with no jumper between SD and STF (Figure 1).

Procedure

  1. Verify that the jumper above terminal SC (Figure 1) is set to SINK.
  2. Verify that the AI2 mode switch to the left of terminal A (Figure 1) is set to V for applications with 0–5 V or 0–10 V voltage input or set to I for applications with 4–20 mA current input.
  3. Exit the PU (manual operation) mode by pressing PU/EXT until the EXT LED is highlighted, then use a jumper to connect SD to STF.

Results

The VFD68 is now commissioned, is in the external operation mode, and is ready to run the motor using the analog inputs.