Selecting a VFD68 Drive for Controlling Multiple Motors - PENN Controls - VFD68Bxx - VFD68Cxx - VFD68Dxx - Three‐Phase Motor Speed Controller - VFD68 Three‐Phase Variable Frequency Drive

VFD68 Variable Frequency Drives Technical Bulletin

Brand
PENN Controls
Product name
VFD68 Three‐Phase Variable Frequency Drive
Document type
Technical Bulletin
Part number
24-7664-3051
Document revision
C
Revision date
2019-08-09
Language
English
Important: Do not control both single-phase and three-phase motors with the same VFD68 drive.

A VFD68 drive can control multiple motors; however, the sum of the Full Load Amperes (FLA) ratings for the motors must not exceed the maximum output amperage rating of the VFD68 drive, including any de-rating due to altitude. See Table 1 for de-rating information.