Appendix 1: Check Fault History - PENN Controls - VFD68Bxx - VFD68Cxx - VFD68Dxx - Three‐Phase Motor Speed Controller - VFD68 Three‐Phase Variable Frequency Drive

VFD68 Variable Frequency Drives Technical Bulletin

Product
Document revision
C
Revision date
2019-08-09
Part number
24-7664-3051

About this task

The last eight Fault, Error, or Warning indicator messages are stored in the VFD. To view these messages, use the following procedure and see Figure 1:

Procedure

  1. Power the VFD and set it to the MON mode (MON LED is on).
  2. Press the MODE button twice to enter Fault History mode (E---).
  3. Rotate the setting dial slightly.
    • If an Indicator Fault, Error, or Warning has occurred, the display blinks while showing an indicator message.
    • If no Fault, Error, or Warning has occurred, the display shows E 0.
  4. Press the setting dial to view the actual indicator message number (message number 1 is the most recent).
  5. Rotate the setting dial to view all eight indicator messages.

Results

To exit the Fault History Mode, press the MODE button until the MON LED is on.

Figure 1. Check Fault History