Resetting the VFD68 Drive - PENN Controls - VFD68Bxx - VFD68Cxx - Three‐Phase Motor Speed Controller - VFD68 Three‐Phase Variable Frequency Drive

VFD68 Variable Frequency Drives (230 or 460 VAC) Installation Guide

Brand
PENN Controls
Product name
VFD68 Three‐Phase Variable Frequency Drive
Document type
Installation Guide
Part number
24-7664-3108
Document revision
F
Revision date
2019-08-16
Language
English
WARNING
  • Risk of Personal Injury.
  • Before you reset the VFD68 Drive, verify that all persons are clear of the controlled equipment. Resetting the VFD68 Drive may immediately start the controlled equipment, and failure to verify that all persons are clear of the controlled equipment before resetting the VFD68 Drive may result in severe personal injury or death.
Avertissement
  • Risque de blessure.
  • Avant de réinitialiser le VFD68 Drive, assurez-vous qu'aucune personne n'est à proximité de l'équipement. La réinitialisation du VFD68 Drive peut faire redémarrer l'équipement contrôlé immédiatement et le non-respect de cette précaution pourrait entraîner des blessures graves, voire mortelles.
Important: To prevent the motor from starting immediately after a fault reset, remove the jumper that connects terminal SD to terminal STF before clearing the reset.

If the motor stops due to a fault, you can reset the VFD by using either of the following two methods.