Important: Do not control both single-phase and three-phase motors with the same VFD68 Drive.

A VFD68 Drive can control multiple motors wired in parallel; however, the sum of the FLA ratings for the motors must not exceed the maximum output current rating of the VFD68 drive, including any de-rating due to altitude. See Table 1 for derating information.