Selection chart - PENN Controls - LIT-1927345 - V48AB - V48AC - V48AD - V48AE - V48AF - V48AL - V48EK - Pressure Actuated Water Regulating Valve - V48 Low and All‐Range Pressure Refrigerant

V48 Series Three-Way Water Regulating Valve Catalog Page

Brand
PENN Controls
Product name
V48 Low and All‐Range Pressure Refrigerant
Document type
Catalog Page
Document number
LIT-1927345
Revision date
2021-08-17
Language
English
Note: Use these valves with noncorrosive refrigerants.
Table 1. V48 Series selection chart
Product code Pipe size, in. Range opening point of normally closed side, psi (kPa) Pressure element style Water supply pressure, psig (kPa) Inlet and outlet ports Max bellows overpressure, psig (kPa) Seat repair kit Replacement sensing element
V48AB-2C 1/2 145 to 190

(1,000 to 1,310)

30 in. capillary with 1/4 in. flare nut, Style 451 150

(1,034)

Threaded 320

(2,206)

STT15A‑605R SEP91A-602R SEC99AA-36C2
V48AC-2C 3/4 STT16A‑604R SEP91A-601R SEC99AA-36C 2
V48AD-2C 1 STT17A‑616R SEP91A-603R SEC99AA-36C 2
V48AE-2C 1 1/4 STT17A‑617R
V48AF-2C 1 1/2 1/4 in. external flare fitting, Style 5 STT17A‑604R SEP81A-601R
V48EK-2C 3/4 30 in. capillary with 1/4 in. flare nut, Style 46 Union 370

(2,551)

STT16A‑604R SEP127A-600R
V48AL-2C 1 320

(2,206)

STT17A‑616R SEP107A-602R
1 Standard capillary length on Style 45 elements is 30 in.
2 Replacement element supplied with 1/4 in. external SAE connector. Order SEC99AA capillary kit with two flare nuts separately if you require it. Use only on specified valves.