T26 electrical ratings - PENN Controls - LIT-1922255 - T22BBC - T22ABC - T22AAA - T25A - T26A - T22SDA - T22SEB - T22TFB - T22SFB - T26J - T22JAA - T22JCC - T26T - T26S - T22CBC - Line-Voltage Thermostat - T25 Line‐Voltage Thermostat - T26 Line‐Voltage Thermostat - T22 Line‐Voltage Thermostat

T22, T25, and T26 Series Line Voltage Wall Thermostat for Heating and Cooling Catalog Page

Product
Document type
Catalog Page
Document number
LIT-1922255
Revision date
2021-09-29
Table 1. T26A and T26S electrical ratings
Description cULus
Volts AC 50/60 Hz 120 208 240 277
Full load amperes 12.0 6.9 6.0 -
Lock rotor amperes 72.0 41.4 36.0 -
Resistive amperes 10.0 10.0 10.0 10.0
Pilot duty 125 VA, 24 VAC to 277 VAC
Table 2. T26J electrical ratings
Description cULus
Volts AC 50/60 Hz 120 208 240
Full load amperes 12.0 6.9 6.0
Lock rotor amperes 72.0 41.4 36.0
Pilot duty 125 VA, 24 VAC to 277 VAC
Table 3. T26T electrical ratings
Description cULus
Volts AC 50/60 Hz 120 208 240 277
Full load amperes 16.0 9.2 8.0 -
Lock rotor amperes 96.0 55.2 48.0 -
Resistive amperes 22.0 22.0 22.0 22.0
Pilot duty 125 VA, 24 VAC to 277 VAC