Specification | Description |
---|---|
Product | C450CPN-4C and C450CQN-4C: System 450 Control Module models are sensing
controls and operating controls with LCD, four-button touchpad, and SPDT
analog output C450CPN-4C: Control Module with one analog output C450CQN-4C: Control Module with two analog outputs |
Power Consumption | C450CPN-4C: 1.3 VA maximum using 0 to 10 V out; 1.5 VA maximum using 4
to 20 mA out C450CQN-4C: 2.0 VA maximum using 0 to 10 V out; 2.4 VA maximum using 4 to 20 mA out |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) when using 0–10 VDC
outputs; -40 to 40°C (-40 to 104°F) when using 4–20 mA outputs
Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Input Signal | 0 to 5
VDC for humidity sensors and static pressure transducers 0.5 to 4.5 VDC for ratiometric pressure transducers 1,035 ohms at 25°C (77°F) for A99 PTC temperature sensors 1,000 ohms at 21.1°C (70°F) for TE-6xxx Nickel temperature sensors |
Analog Output |
Voltage Mode (0–10 VDC):
10 VDC maximum output voltage 10 mA maximum output current Requires an external load of 1,000 ohms or more The AO operates in Voltage Mode when connected to devices with impedance greater than 1,000 ohms. Devices that fall below 1,000 ohms may not operate as intended with Voltage Mode applications. |
Current Mode (4–20 mA):
Requires an external load between 0 to 300 ohms The AO operates in Current Mode when connected to devices with impedance less than 300 ohms. Devices that rise above 300 ohms may not operate as intended with Current Mode applications. |
|
Analog Input Accuracy | Resolution: 14 bits |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450CPN-4C: 195 g (0.43 lb) C450CQN-4C: 195 g (0.43 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450CEN-1: System 450 Control Modules are sensing controls and
operating controls with LCD and four-button touchpad UI, Ethernet
communications capability, and no outputs. C450CEN-1C: Control Module with Ethernet communications capability |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Input Signal | 0 to 5 VDC; 1,035 ohms at 25°C (77°F) for an A99 PTC Temperature Sensor |
Analog Input Accuracy | Resolution: 16 bits |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 63 x 63 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450CEN-1C: 207 g (0.46 lb) |
Compliance |
United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450CRN-1C: System 450 Control Modules are sensing controls and operating controls with LCD and four-button touchpad UI and no outputs. This control module is an RS485, RTU compliant Modbus subordinate device. |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Input Signal | 0 to 5 VDC; 1,035 ohms at 25°C (77°F) for an A99 PTC Temperature Sensor |
Analog Input Accuracy | Resolution: 16 bits |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 63 x 63 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450CRN-1C: 207 g (0.46 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450CPW-400C System 450 Control Module is a sensing control and operating control with LCD, four-button touchpad, and analog output with pulse-width modulation capability. |
Power Consumption | C450CPW-400C: 1.3 VA maximum using 0 to 10 V out; 1.5 VA maximum using 4 to 20 mA out |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) when using 0 to 10 VDC outputs;
-40 to 40°C (-40 to 104°F) when using 4 to 20 mA outputs Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Input Signal | 0 to 5
VDC for humidity sensors and static pressure transducers 0.5 to 4.5 VDC for ratiometric pressure transducers 1,035 ohms at 25°C (77°F) for A99 PTC temperature sensors 1,000 ohms at 21.1°C (70°F) for TE-6xxx Nickel temperature sensors |
Analog Output |
Voltage Mode (0–10 VDC):
10 VDC maximum output voltage 10 mA maximum output current Requires an external load of 1,000 ohms or more The AO operates in Voltage Mode when connected to devices with impedance greater than 1,000 ohms. Devices that fall below 1,000 ohms may not operate as intended with Voltage Mode applications. |
Current Mode (4–20 mA):
Requires an external load between 0 to 300 ohms The AO operates in Current Mode when connected to devices with impedance less than 300 ohms. Devices that rise above 300 ohms may not operate as intended with Current Mode applications. |
|
Analog Input Accuracy | Resolution: 14 bits |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450CPW-400C: 195 g (0.43 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450CBN-4C and C450CCN-4C: System 450 Control Module models are sensing
controls and operating controls with LCD, four-button touchpad, and SPDT
relay output C450CBN-4C: Control Module with one SPDT output relay C450CCN-4C: Control Module with two SPDT output relays |
Power Consumption | C450CBN-4C: 0.9 VA maximum C450CCN-4C: 1.3 VA maximum |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Input Signal | 0 to 5
VDC for humidity sensors and static pressure transducers 0.5 to 4.5 VDC for ratiometric pressure transducers 1,035 ohms at 25°C (77°F) for A99 PTC temperature sensors 1,000 ohms at 21.1°C (70°F) for TE-6xxx Nickel temperature sensors |
Output Relay Contacts |
General: 1/2 HP at 120/240 VAC, SPDT |
Specific: AC Motor Ratings 120 VAC
208 / 240 VAC
_______________________________ 10 Amperes AC Noninductive at 24 / 240 VAC Pilot Duty: 125 VA at 24/240 VAC |
|
Analog Input Accuracy | Resolution: 14 bits |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450CBN-4C: 209 g (0.46 lb) C450CCN-4C: 222 g (0.49 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450RBN-3C and C450RCN-3C: System 450 Reset Control Module models are
sensing controls and operating controls with LCD, four-button touchpad,
and SPDT relay output C450RBN-3C: Control Module with one SPDT output relay C450RCN-3C: Control Module with two SPDT output relays |
Power Consumption | C450RBN-3C: 0.9 VA maximum C450RCN-3C: 1.3 VA maximum |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Input Signal | 0 to 5
VDC for humidity sensors 1,035 ohms at 25°C (77°F) for A99 PTC temperature sensors |
Output Relay Contacts |
General: 1/2 HP at 120/240 VAC, SPDT |
Specific: AC Motor Ratings 120 VAC
208 / 240 VAC
_______________________________ 10 Amperes AC Noninductive at 24 / 240 VAC Pilot Duty: 125 VA at 24/240 VAC |
|
Clock Accuracy | ±4 minutes per year |
Clock Backup Power | 12 hours (capacitor reserve) |
Setback Events | One occupied and one unoccupied event per day; 7 day schedule |
Analog Input Accuracy | Resolution: 14 bits |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450RBN-3C: 209 g (0.46 lb) C450RCN-3C: 222 g (0.49 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450SPN-4C: System 450 Expansion Module with one Analog
output C450SQN-4C: System 450 Expansion Module with two Analog outputs |
Power consumption | C450SPN-4C: 1.1 VA max using 0 to 10 V out; 1.3 VA maximum
using 4 to 20 mA out C450SQN-4C: 1.8 VA max using 0 to 10 V out; 2.2 VA maximum using 4 to 20 mA out |
Supply power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America), 50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient operating conditions | Temperature: -40 to 66°C (-40 to 150°F) when using 0 to 10 VDC
outputs;-40 to 40°C (-40 to 104°F) when using 4 to 20 mA outputs
Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient shipping and storage conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Analog output |
Voltage Mode (0 to 10 VDC):
10 VDC maximum output voltage 10 mA maximum output current Requires an external load of 1,000 ohms or more The AO operates in Voltage Mode when connected to devices with impedance greater than 1,000 ohms. Devices that drop below 1,000 ohms may not operate as intended with Voltage Mode applications. |
Current Mode (4 to 20 mA):
Requires an external load between 0 to 300 ohms The AO operates in Current Mode when connected to devices with impedances less than 300 ohms. Devices that exceed 300 ohms may not operate as intended with Current Mode applications. |
|
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450SPN-4C: 150 g (0.33 lb) C450SQN-4C: 150 g (0.33 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450SBN-4C: System 450 Expansion Module with one SPDT
output relay C450SCN-4C: System 450 Expansion Module with two SPDT output relays |
Power Consumption | C450SBN-4C: 0.8 VA maximum C450SCN-4C: 1.2 VA maximum |
Supply Power | Internal
Supply Power: C450YNN-1C Power Supply Module External Supply Power: 24 VAC (20 to 30 VAC) Safety Extra-Low Voltage (SELV) (Europe), Class 2 (North America),50/60 Hz, 10 VA minimum Note: A System 450 control module or module assembly can use
an internal or an external supply power source, but must not be
connected to both simultaneously.
|
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Output Relay Contacts |
General: 1/2 HP at 120/240 VAC, SPDT |
Specific: AC Motor Ratings 120 VAC
208 / 240 VAC
_______________________________ 10 Amperes AC Noninductive at 24 / 240 VAC Pilot Duty: 125 VA at 24/240 VAC |
|
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450SBN-4C: 172 g (0.38 lb) C450SCN-4C: 186 g (0.41 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |
Specification | Description |
---|---|
Product | C450YNN-1C: System 450 Power Supply Module; 120 or 240 VAC stepdown to 24 VAC Class 2 (North America) or SELV (Europe) |
Supply Power | 110/120 VAC or 220/240 VAC at 50/60 Hz (100 mA maximum) |
Secondary Power | 24 VAC, 10 VA |
Ambient Operating Conditions | Temperature: -40 to 66°C (-40 to 150°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Ambient Shipping and Storage Conditions | Temperature: -40 to 80°C (-40 to 176°F) Humidity: Up to 95% RH noncondensing; maximum dew point 29°C (85°F) |
Enclosure | Type 1, IP20 High-Impact Thermoplastic |
Dimensions (H x W x D) | 127 x 61 x 61 mm (5 x 2-3/8 x 2-3/8 in.) |
Weight | C450YNN-1C: 390 gm (0.86 lb) |
Compliance | United States: cULus Listed; UL 60730-1, File E27734; FCC Compliant to CFR47, Part 15, Subpart B, Class B |
Canada: cULus Listed; CAN/CSA-E60730-1, File E27734; Industry Canada (IC) Compliant to Canadian ICES-003, Class B limits | |
|
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and Low Voltage Directive. |
Australia and New Zealand: RCM mark, Australia/NZ Emissions Compliant |