The following tables show the terminal contact numbers on the controller that you can use with each relay. See Ordering information for information about all TC controller relay functions. Refer to your controller's installation guide for information about your model's relay functions.

Table 1. K1 relay terminal numbers
TC controller Common SPST or SPDT N.O. SPDT N.C.
TC3221 2 3 n/a
TC3222 2 3 n/a
TC3223 2 3 n/a
TC3224 2 6 n/a
TC3B21 2 3 n/a
TC3B22 2 3 n/a
TC3B23 2 3 n/a
TC3X21 7 8 6
Table 2. K2 relay terminal numbers
TC controller Common SPST or SPDT N.O. SPDT N.C.
TC3222 5 6 7
TC3223 5 6 7
TC3224 6 3 n/a
TC3B22 5 6 7
TC3B23 5 6 7
Table 3. K3 relay terminal numbers
TC controller Common SPST N.O.
TC3223 2 1
TC3224 6 1
TC3B23 2 1
Table 4. K4 relay terminal numbers
TC controller Common SPST N.O.
TC3224 6 5