| Specification | Description | |
|---|---|---|
| Signal output types | 0.5 VDC to 4.5 VDC ratiometric | |
|
Assembly torques Note: Refer to the manufacturer's
guidelines for exact assembly torques.
|
1/8 in. - 27 NPT, external thread ANSI B1.20.1 | 12 ft·lb (16.27 N·m) |
| 1/4 in. SAE 45° flare with Schrader® Valve depressor, internal thread | 12 ft·lb (16.27 N·m) | |
| 1/4 in. - 18 NPT, external thread ANSI B1.20.1 | 15 ft·lb (20.34 N·m) | |
| 1/4 in. - 18 NPTF external thread | 15 ft·lb (20.34 N·m) | |
| Electrical connector | Packard, Metri-Pack 150 series, P2S | |
| Units of measurement | Bar, psi | |
| Temperature range |
Compensated temperature: -40°F to 257°F (-40°C to 125°C) Media temperature, pressure side: -40°F to 257°F (-40°C to 125°C) Operating temperature, ambient air: -40°F to 212°F (-40°C to 100°C) Storage temperature: -40°F to 257°F (-40°C to 125°C) |
|
| Accuracy | Total accuracy: 1.5% to 2.0% between
-13°F and 257°F (-25°C and 125°C) Best-fit straight line (BFSL): +/- 0.5% Long term stability, 1 year: +/- 2.0% |
|
| Supply voltage | 4.5 VDC to 5.5 VDC | |
| Output voltage | 0.5 VDC to 4.5 VDC typical | |
| Maximum signal input current | 0.5 VDC to 4.5 VDC ratiometric: 3 mA | |
| Electrical protection | Standard response time: 2 ms Output impedance: greater than 25 Ω Minimum termination resistance: 10 kΩ. The resistance signal out can support this for volt out models.
Short-circuit protected: the signal cuts out at the maximum span to earth Minimum resistance from body to terminal: 100 MΩ at 500 VDC |
|
| Physical |
|
|
| Field installed electrical connection IP ratings | Packard, IP67 | |
|
Compliance
|
United States: Controllers, Refrigeration - Component, SDFY2.SA516 | |
| Canada: Controllers, Refrigeration - Component, SDFY8.SA516 | ||
|
|
Europe: LVD, EMC, RoHS, WEEE
ATEX Certificate No. (UL 22 ATEX 2840U) |
|
|
|
UKCA: This product meets the essential requirements of the UKCA | |