Range and differential specifications - PENN Controls - LIT-125400 - P10FC - P10BG - P10BC - P10PA - Electromechanical Pressure Control - P10 Low Pressure Control

P10 Series Low Range Pressure Control Product Bulletin

Product
Controls > Pressure Controls > P10 Low Pressure Control
Document type
Product Bulletin
Document number
LIT-125400
Revision date
2023-12-20
Product status
Active
Table 1. P10 range and differential specifications
Model Range, psig (kPa) Differential, psi (kPa) Maximum allowable pressure, psig (kPa)
Minimum range Mid-range Maximum range
Minimum Maximum Minimum Maximum Minimum Maximum
P10BG

2 to 20

(14 to 140)

0.15 fixed

(1.0)

0.20 fixed

(1.4)

0.25 fixed

(1.7)

60

(414)

P10BC, P10FC, P10PA

3 to 20

(20 to 140)

1.5

(10)

4.5

(31)

2.0

(14)

6.0

(41)

2.5

(17)

7.5

(52)

150