| Model | Range, psig (kPa) | Differential, psi (kPa) | Maximum allowable pressure, psig (kPa) | |||||
|---|---|---|---|---|---|---|---|---|
| Minimum range | Mid-range | Maximum range | ||||||
| Minimum | Maximum | Minimum | Maximum | Minimum | Maximum | |||
| P10BG |
2 to 20 (14 to 140) |
0.15 fixed (1.0) |
0.20 fixed (1.4) |
0.25 fixed (1.7) |
60 (414) |
|||
| P10BC, P10FC, P10PA |
3 to 20 (20 to 140) |
1.5 (10) |
4.5 (31) |
2.0 (14) |
6.0 (41) |
2.5 (17) |
7.5 (52) |
150 (1,034) |