Selection chart - PENN Controls - LIT-1927175 - P10FC - P10BG - P10BC - P10PA - Electromechanical Pressure Control - P10 Low Pressure Control

P10 Series Low Pressure Control Catalog Page

Product
Controls > Pressure Controls > P10 Low Pressure Control
Document number
LIT-1927175
Revision date
2023-12-20
Table 1. Selection chart
Product code Number of stages Contact action Range psi (kPa) Factory setting Pressure connector
psig (kPa) Switch differential, psi (kPa)
P10BC-7C 1 SPDT

3 to 20

(21 to 138)

R to Y cut-in

12

2 Barbed fitting
P10BG-3C 1 SPDT

2 to 20

(15 to 138)

R to Y cut-in

12

0.2 1/8 in. internal NPSF
P10FC-4C 2 SPDT

3 to 20

(21 to 138)

R to Y cutout, low stage

8 (55)

R to Y cut-in, high stage

12 (82)

Low stage

2 (14)

High stage

2 (14)

1/8 in. barbed fitting
P10PA-11C 3 Single-pole, single-throw (SPST)

3 to 20

(21 to 138)

Stage one open high

6 (41)

Stages two and three open high

18 (120)

Stage one

3 (21)

Stages two and three

0.4 (3)

1/8 in. barbed fitting