Table 1. Standard P-Series control models
Product code number Johnson Controls Switch action Setpoints-psig (kPa) Replaces
P100 reference Opens Closes Ranco® Robert-shaw® Saginomiya® Danfoss™ Klixon® Supco® Wilspec® International refrigeration products Gemline®

PR200-AC-1C

2

P100AC-1C

Open on pressure drop

5

(34)

20

(138)

MPL-7001

n/a

ACB-2UA318W

n/a

PS80-K2-F0305-020-005

SLP0520

HR201A02-0005D

SLP0520

n/a

PS200-AP-201C

P100AP-201C

10

(69)

32

(221)

MPL-7011

3100-050

ACB-2UA101

n/a

SLP1032

n/a

SLP1032

PS200-AP-105C

P100AP-105C

30

(207)

60

(414)

n/a

3100-004

ACB-2UA94

n/a

SLP3560

PS200-AP-2C

P100AP-2C

35

(241)

60

(414)

MPL-7004

3100-004

n/a

SLP3560

SLP3560

PS200-AP-361C

P100AP-361C

50

(345)

90

(620)

n/a

n/a

PS80-KS-F0328-090-005

SLP5090

HR201A09-0050D

SLP5090

PS200-AP-3C

1

P100AP-3C

150

(1,034)

225

(1,551)

MPF-7008

ACB-2UA685W

n/a

SFC1502-25

n/a

n/a

PS200-AP-4C

1

P100AP-4C

170

(1,172)

250

(1,724)

n/a

ACB-2UA631W

SFC1702-50

PS200-AP-200C

1

P100AP-200C

195

(1,344)

275

(1,896)

n/a

n/a

PS200-AP-332C 1

P100AP-332C

300

(2,068)

400

(2,758)

MPF7010

ACB-2UA627W

061F7514

SFC3004-00

PS200-CP-157C

P100CP-157C

Open on pressure rise

225

(1,551)

150

(1,034)

n/a

n/a

n/a

n/a

n/a

PR200-CC-9C 2

P100CC-9C

275

(1,896)

175

(1,207)

3100-112

ACB-2UB724W

PS200-CP-91C

P100CP-91C

300

(2,067)

200

(1,378)

n/a

ACB-2UB723W

PS80-K1-0341-300-200

HR202A30-0200D

SHP300200

PS200-CP-1C

P100CP-1C

400

(2,758)

300

(2,068)

MPH-7107

3100-151

ACB-2UB35

061FS14

PS80-K1-0359-400-300

SHP4003-00

HR202A30-0300D

SHP400300

PC 151

PS200-CP-2C

P100CP-2C

425

(2,930)

325

(2,241)

MPH-7108

3100-100

ACB-2UB282W

n/a

n/a

SHP4253-25

n/a

n/a

PC 100

PS200-CP-38C

P100CP-38C

500

(3,447)

325

(2,241)

n/a

n/a

n/a

n/a

n/a

PS100-CP-85C

P100CP-85C

665

(4,585)

565

(3,895)

SHP6655-65

PM200-DA-1C

P100DA-1C

410

(2,827)

Lockout

Manual

Reset

3100-103

ACBPB115M

29PSL012-24

SMR410

HM202A41-0000D

SMR410

PC 103

PM200-DA-86C

P100DA-86C

Open on pressure rise

575

(3,964)

Lockout

Manual

Reset

n/a

n/a

n/a

n/a

n/a

SMR575

n/a

n/a

n/a

PM200-DA-81C

P100DA-81C

630

(4,344)

Lockout

Manual

Reset

SMR630

1 Models are designed for condenser fan cycling.
2 Model includes conduit clamp for 9.5 mm [3/8 in.] flexible metal conduit.