| Product code number | Johnson Controls | Switch action | Setpoints-psig (kPa) | Replaces | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| P100 reference | Opens | Closes | Ranco® | Robert-shaw® | Saginomiya® | Danfoss™ | Klixon® | Supco® | Wilspec® | International refrigeration products | Gemline® | ||
|
PR200-AC-1C 2 |
P100AC-1C |
Open on pressure drop |
5 (34) |
20 (138) |
MPL-7001 |
n/a |
ACB-2UA318W |
n/a |
PS80-K2-F0305-020-005 |
SLP0520 |
HR201A02-0005D |
SLP0520 |
n/a |
|
PS200-AP-201C |
P100AP-201C |
10 (69) |
32 (221) |
MPL-7011 |
3100-050 |
ACB-2UA101 |
n/a |
SLP1032 |
n/a |
SLP1032 |
|||
|
PS200-AP-105C |
P100AP-105C |
30 (207) |
60 (414) |
n/a |
3100-004 |
ACB-2UA94 |
n/a |
SLP3560 |
|||||
|
PS200-AP-2C |
P100AP-2C |
35 (241) |
60 (414) |
MPL-7004 |
3100-004 |
n/a |
SLP3560 |
SLP3560 |
|||||
|
PS200-AP-361C |
P100AP-361C |
50 (345) |
90 (620) |
n/a |
n/a |
PS80-KS-F0328-090-005 |
SLP5090 |
HR201A09-0050D |
SLP5090 |
||||
|
PS200-AP-3C 1 |
P100AP-3C |
150 (1,034) |
225 (1,551) |
MPF-7008 |
ACB-2UA685W |
n/a |
SFC1502-25 |
n/a |
n/a |
||||
|
PS200-AP-4C 1 |
P100AP-4C |
170 (1,172) |
250 (1,724) |
n/a |
ACB-2UA631W |
SFC1702-50 |
|||||||
|
PS200-AP-200C 1 |
P100AP-200C |
195 (1,344) |
275 (1,896) |
n/a |
n/a |
||||||||
|
PS200-AP-332C 1 |
P100AP-332C |
300 (2,068) |
400 (2,758) |
MPF7010 |
ACB-2UA627W |
061F7514 |
SFC3004-00 |
||||||
|
PS200-CP-157C |
P100CP-157C |
Open on pressure rise |
225 (1,551) |
150 (1,034) |
n/a |
n/a |
n/a |
n/a |
n/a |
||||
|
PR200-CC-9C 2 |
P100CC-9C |
275 (1,896) |
175 (1,207) |
3100-112 |
ACB-2UB724W |
||||||||
|
PS200-CP-91C |
P100CP-91C |
300 (2,067) |
200 (1,378) |
n/a |
ACB-2UB723W |
PS80-K1-0341-300-200 |
HR202A30-0200D |
SHP300200 |
|||||
|
PS200-CP-1C |
P100CP-1C |
400 (2,758) |
300 (2,068) |
MPH-7107 |
3100-151 |
ACB-2UB35 |
061FS14 |
PS80-K1-0359-400-300 |
SHP4003-00 |
HR202A30-0300D |
SHP400300 |
PC 151 |
|
|
PS200-CP-2C |
P100CP-2C |
425 (2,930) |
325 (2,241) |
MPH-7108 |
3100-100 |
ACB-2UB282W |
n/a |
n/a |
SHP4253-25 |
n/a |
n/a |
PC 100 |
|
|
PS200-CP-38C |
P100CP-38C |
500 (3,447) |
325 (2,241) |
n/a |
n/a |
n/a |
n/a |
n/a |
|||||
|
PS100-CP-85C |
P100CP-85C |
665 (4,585) |
565 (3,895) |
SHP6655-65 |
|||||||||
|
PM200-DA-1C |
P100DA-1C |
410 (2,827) |
Lockout Manual Reset |
3100-103 |
ACBPB115M |
29PSL012-24 |
SMR410 |
HM202A41-0000D |
SMR410 |
PC 103 |
|||
| PM200-DA-86C |
P100DA-86C |
Open on pressure rise |
575 (3,964) |
Lockout Manual Reset |
n/a |
n/a |
n/a |
n/a |
n/a |
SMR575 |
n/a |
n/a |
n/a |
| PM200-DA-81C |
P100DA-81C |
630 (4,344) |
Lockout Manual Reset |
SMR630 |
|||||||||
1 Models are designed for condenser fan cycling.
2 Model includes conduit clamp for 9.5 mm [3/8 in.] flexible