| Volts 50/60 Hz | UL 60730/UL 1059 | EN 60730 | ||||
|---|---|---|---|---|---|---|
| 24 | 120 | 208 | 240 | 24 | 230 | |
| Horsepower | – | 1 | 1 | 1 | – | – |
| Full load amperes | – | 16 | 10 | 10 | – | 8 |
| Locked rotor amperes | – | 96 | 60 | 60 | – | 48 |
| Resistive amperes | 16 | 16 | 10 | 10 | 16 | 16 |
| Pilot duty VA | 125 | 720 | 720 | 720 | 77 | 720 |
| Volts AC, 50/60 Hz | UL 60730/UL 1059EN 60730 | ||
|---|---|---|---|
| 4 VAC | 24 VAC | 120 VAC | |
| Resistive amperes1 | 10 | 10 | 10 |
| Pilot duty VA2 | 12 | 72 | 360 |
| Volts DC | UL 60730/UL 1059/EN 60730 | ||
|---|---|---|---|
| 4 VDC | 24 VDC | 48 VDC | |
| Resistive amperes3 | 1 | 1 | 1 |
1 Maximum dry circuit
rating: Resistive only, 400 mW at 28 VAC/VDC. After you use a
relay at the general rating level, the dry circuit rating is no
longer valid.
2 Meets
UL 100,000 cycle UL endurance test requirement at switch with
Tmin greater than or equal to
32°F (0°C).
3 Maximum dry circuit
rating: Resistive only, 400 mW at 28 VAC/VDC. After you use a
relay at the general rating level, the dry circuit rating is no
longer valid.