A11 conformity declaration - PENN Controls - LIT-1927005 - A11A - A11B - A11D - A11E - Electromechanical Temperature Control - A11 Low Temperature Cutout Control

A11 Series Low Temperature Cutout Controls Catalog Page

Brand
PENN Controls
Product name
A11 Low Temperature Cutout Control
Document type
Catalog Page
Document number
LIT-1927005
Revision date
2021-08-20
Language
English
Table 1. Conformity declaration
Information Description
Purpose of the control Low temperature cutout control
Construction of the control Electromechanical independently mounted control
Number of cycles 30K cycles auto reset, 6K cycles manual reset
Method of mounting the control Permanently attached through hole in mounting bracket
Method of earthing the control Wiring binding screw terminal
Type 1 or Type 2 action Type 1.B; micro-disconnection
External pollution situation Pollution degree 3
Internal pollution situation Pollution degree 2
Rated impulse voltage 4,000 VAC
Ball pressure temperature Switch component 302°F (150°C)
Field wiring rating Use copper conductors only, rated at least 194°F (90°C)
Switch SPST (A11A, A11B), SPDT (A11D, A11E)
Enclosure UL: Type 1 (NEMA)
Wiring connection Three color-coded screw terminals, SPDT only, and one ground terminal
Conduit connection One 7/8 in. (22 mm) hole for 1/2 in. (12.7 mm) trade size (or PG16) conduit
Ambient conditions 0°F (-18°C) to 140°F (60°C)
Compliance North America cULus listed; UL60730, CSA E60730 File SA516