| Specification | Description | |
|---|---|---|
| Product codes |
A11A: SPST, open low, manual reset A11B: SPST, open low, automatic recycle A11D: SPDT, manual reset A11E: SPDT, automatic recycle |
|
| Range cutout | 35°F to 45°F (2°C to 7°C) | |
| Differential |
A11A and A11D: Temperature must be 12°F (6.7°C) above cutout point before you can reset the control. A11B and A11E: 12°F (6.7°C) |
|
| Maximum temperature at bulb | 250°F (121°C) | |
| Sensing element | 1/8 in. x 20 ft (3.2 mm x 6.1 m) or 1/8 in. x 40 ft (3.2 mm x 12.2 m) | |
| Capillary length | 4 ft (1.2 m) | |
| Switch | Snap-acting contacts in dust-protected enclosure | |
| Material |
Case: 0.6 in. (1.6 mm) cold rolled steel Cover: 0.3 in. (0.8 mm) cold rolled steel |
|
| Finish | Galvanized steel | |
| Mounting bracket | Standard on all controls | |
| Shipping weight |
Individual pack: 1.8 lb (0.8 kg) Overpack of 20 units: 38 lb (17 kg) |
|