A11 Low Temperature Cutout Controls technical specifications - PENN Controls - LIT-1927005 - A11E - A11D - A11A - A11B - Electromechanical Temperature Control - A11 Low Temperature Cutout Control

A11 Series Low Temperature Cutout Controls Catalog Page

Product
Controls > Temperature Controls > A11 Low Temperature Cutout Control
Document number
LIT-1927005
Revision date
2021-08-20
Table 1. A11 Low Temperature Cutout Controls technical specifications
Specification Description
Product codes

A11A: SPST, open low, manual reset

A11B: SPST, open low, automatic recycle

A11D: SPDT, manual reset

A11E: SPDT, automatic recycle

Range cutout 35°F to 45°F (2°C to 7°C)
Differential

A11A and A11D: Temperature must be 12°F (6.7°C) above cutout point before you can reset the control.

A11B and A11E: 12°F (6.7°C)

Maximum temperature at bulb 250°F (121°C)
Sensing element 1/8 in. x 20 ft (3.2 mm x 6.1 m) or 1/8 in. x 40 ft (3.2 mm x 12.2 m)
Capillary length 4 ft (1.2 m)
Switch Snap-acting contacts in dust-protected enclosure
Material

Case: 0.6 in. (1.6 mm) cold rolled steel

Cover: 0.3 in. (0.8 mm) cold rolled steel

Finish Galvanized steel
Mounting bracket Standard on all controls
Shipping weight

Individual pack: 1.8 lb (0.8 kg)

Overpack of 20 units: 38 lb (17 kg)