Change the Settings in the WNC1800 Gateway - Metasys - LIT-12012319 - Wireless Device - WNC: Wireless Network Coordinator/Gateway

WNC1800/ZFR182x Pro Series Wireless Field Bus System Quick Reference Guide

Brand
Metasys
Product name
WNC: Wireless Network Coordinator/Gateway
Document type
Reference Guide
Document number
LIT-12012319
Revision date
2017-02-01
Language
English

If you are using the WNC1800 Gateway with a Supervisory Controller or to view or manage the WNC1800 Gateway from an Ethernet connection, you must configure the WNC Ethernet settings.

Once you are logged onto the WNC1800 Gateway using the Wi-Fi Access Point feature, go to Settings > Ethernet and set the Ethernet Field to On. If Auto DHCP is set to On, the IP Address, Subnet Mask, and Default Gateway fields will automatically populate. However, if you need use a static IP addressing, set Auto DHCP Configure to Off and fill in the IP Address, Subnet Mask and Default Gateway fields with values from your IT Department.

Figure 1. WNC Ethernet Settings