Reusing a TE-6xxx series sensor - Metasys - MS-VMA1832-x - MS-VMA1826-x - Field Device - VMA18 VAV Modular Assembly

VMA1826/1832 VAV Controller Installation Guide

Product
Variable Air Volume > Modular Assemblies > VMA18 VAV Modular Assembly
Document revision
K
Revision date
2019-10-18
docpartnumberlabel
Part No.
Part number
24-10143-373
To reuse a TE-6xxx Series Sensor with the VMA controller, complete the instructions in this section. The Y adapter provided in the VMA18 accessory pack is required for this procedure.
CAUTION
The adapter must be installed at the VMA controller location. Damage to the SA Bus may occur if you do not use the Y adapter.

To install the adapter at the VMA controller location, see Installing the adapter at the VMA Controller location.

Figure 1. Y Adapter