VMA1610-0U and -1U |
VMA1620-0U and -1U |
||
|---|---|---|---|
|
Communication Protocol |
BACnet MS/TP |
||
|
Engines |
MS-NAE5510-1U, MS-NAE5510-2U, MS-NAE4510-2U, MS-NAE3510-2U, MS-NCE2560-0U |
||
|
Point Types |
Signals Accepted |
||
|
Universal Input (UI) |
Analog Input, Voltage Mode, 0–10 VDC Analog Input, Resistive Mode, 0–2k ohm, RTD (1k NI [Johnson Controls], 1k PT, A998SI), NTC (10k Type L, 2.252k Type 2) Binary Input, Dry Contact Maintained Mode |
1 |
1 |
|
Binary Output (BO) |
24 VAC Triac |
3 |
|
|
Configurable Output (CO) |
Analog Output, Voltage Mode, 0–10 VDC Binary Output Mode, 24 VAC Triac |
2 |
|
|
Integrated Actuator |
Internal |
1 |
1 |
|
Integrated Flow Sensor |
Internal |
1 |
1 |