Enabling Single Sign On with the Keep Me Signed In feature for ADFS Accounts - Metasys - LIT-1201528 - General System Information - Metasys System - 12.0.50

Security Administrator System Technical Bulletin

Product name
Metasys System
Document type
Technical Bulletin
Document number
LIT-1201528
Version
12.0.50
Revision date
2023-06-02

Microsoft’s Keep Me Signed In feature is disabled by default with ADFS. To enable Keep Me Signed In, complete the following steps:

Procedure

  1. On the ADFS server, run the PowerShell command Set- AdfsProperties -EnableKmsi $true.
    Figure 1. PowerShell

  2. Go to the Metasys UI browser and click LOG IN WITH MY ORGANIZATIONAL ACCOUNT (ADFS). Enter your user name and password and click the Keep me signed in checkbox. This creates a cookie with a lifetime of 24 hours so that each time you come back to the Metasys UI application, it automatically logs you in. Click Sign In.
  3. Close your browser and open it back up.
  4. Open the Metasys UI to automatically log you in.